GE Measurement & Control2300 Vibration MonitorsBently Nevada* Asset Condition MonitoringDescriptionThe 2300 Vibration Monitors provide cost-effective continuousvibration monitoring and protection capabilities for less critical andspared machinery. They are specifically designed to continuouslymonitor and protect essential medium to low criticality machineryin a wide range of industries including: oil & gas, power generation,water treatment, pulp & paper, manufacturing, mining, cement,and other industries.The 2300 Vibration Monitors deliver vibration monitoring and highvibration level alarming. They include two channels of seismic orproximity measurement inputs from various accelerometer,velomitor and proximitor types, a speed input channel for timesynchronous measurements, and outputs for relay contacts. The2300/20 monitor features a configurable 4-20 mA output whichinterfaces more points to a DCS. The 2300/25 monitor featuresSystem 1* connectivity for Trendmaster SPA interface whichenables users to leverage existing DSM SPA infrastructure.The 2300 Vibration Monitors are designed for use on a broadrange of machine trains or individual casings where the sensorpoint count fits the monitor’s channel count and where advancedsignal processing is desired.Document: 105M0340Rev. L (09/16)Page 1 of 13

Monitor Key Features2300/202300/25 Two 4-20mA outputs Trendmaster SPA interface Two relay outputs with programmable setpoints Two relay outputs with programmable setpoints Ethernet 10/100 Base-T communication forconfiguration using Bently Nevada MonitorConfiguration software (included) Ethernet 10/100 Base-T communication forconfiguration using Bently Nevada MonitorConfiguration software (included) One dedicated speed and Keyphasor* channelsupporting Proximity probes, Magnetic pickupand Proximity switch type sensors One dedicated speed and Keyphasor channelsupporting Proximity probes, Magnetic pickupand Proximity switch type sensors Three buffered transducer outputs (includingKeyphasor signal) providing short circuit and EMIprotection. Buffered outputs for each signal arethrough BNC connectors. Three buffered transducer outputs (includingKeyphasor signal) providing short circuit and EMIprotection. Buffered outputs for each signal arethrough BNC connectors. Continuous monitoring and protection Continuous monitoring and protection LCD display showing vibration measurements,setpoints, and speed LCD display showing vibration amplitude,setpoints, and speed Two acceleration/velocity/proximity inputs withsynchronized sampling for advanced diagnostics Two acceleration/velocity/proximity inputs withsynchronized sampling for advanced diagnostics Key measurements (Direct pk, Direct rms, Derivedpk, Velocity pk, Velocity rms, Displacement pp,Displacement rms, Speed) real-time providedwith alarm configuration Key measurements (Direct pk, Direct rms, Derivedpk, Velocity pk, Velocity rms, Displacement pp,Displacement rms, Speed) real-time providedwith alarm configuration LEDs show the monitor status LEDs show the monitor status Local contacts for positive engagement ofchannel bypass, configuration lockout, and reset Local contacts for positive engagement ofchannel bypass, configuration lockout, and reset Modbus over Ethernet Modbus over EthernetRecommended for Demonstration Kit2300/20 KIT-003-02-01 1 - 2300/20 Monitor 1 - 6 ft. (1.8M) shielded Ethernet cable 2 - Accelerometer sensors 2 - 15 ft. (4.8M) accelerometer cables 100M9465-01 BN Monitor ConfigurationSW/FW DVDTo be ordered separately:110M7102-01 Power supply for DIN rail mounting,100/240AC to 24DC/1.3A(-25 C 70 C, 22.5*99*107 mm)Document: 105M0340Rev. L (09/16)Page 2 of 13

SpecificationsSpeed/Keyphasor InputsInputs / Outputs Supported Keyphasor transducers include:oProximity probePower Input:oProximity switch DC Input: 18 36VDC, max 7.5WoMagnetic Pickup Supports ICP Accelerometers Channel Type:oConfigurable Bandpass filter: 0.2 Hz to 20kHz Supports multiple events per revolution andevent ratios for speed inputs up to 20 kHz Threshold voltage resolution: 0.1VDCoScale Factor range: 5 to 1000 mV/goFull scale range: 2 to 80 g peakoSupply Voltage: -22.8 to –25.2 VDCoBias output voltage: -12VDC (for AM3100T2Z2)oMaximum Rated Current: 15 mAConfigurable Upper OK limit: -0.25 to -22 V(greater than lower ok)oShort Circuit Current: 15.1 mA to 23.6 mAooAccuracy: 1% of full scale rangeoConfigurable Lower OK limit: -0.25 to -22 V(less than upper ok)oInput Impedance: 3-wire Voltage Mode, 10kΩoCurrent Sink Source: 3.3 mA 5%oRpm range: 1 to 120,000oOpen Circuit Voltage: -21 to -24 VDC Supports Velocity Channel Type:oConfigurable Bandpass filter: 0.2 Hz to 20kHz Proximity Transducer Interface: Proximity Switch Interface:oSupply Voltage: -10 to -24 VDCoLower Not Ok limit: -2.75 0.05 VoRpm range: 1 to 120,000oScale Factor range: 5 to 1000 mV/in/soFull scale range: 0 to 50 in/s peakoInput voltage up to 125V (250Vp-p)oConfigurable Upper OK limit: -0.25 to -22 V(greater than lower ok)oRpm range: 200 to 120,000oConfigurable Lower OK limit: -0.25 to -22 V(less than upper ok) Supports Radial Vibration Channel Type:oConfigurable Bandpass filter: 0.2 Hz to 20kHz Magnetic Pick up:Contact InputsMonitor provides the capability of 3 contact inputswith terminals. One is used for configuration lock,one is for latched alarm/relay reset function, and the3rd one is used for monitor Alarm/Relay Inhibit. Activate: 0 to 10 kΩoScale Factor range: 5 to 1000 mV/mil De-activate: 150 kΩ to infiniteoFull scale range: 0 to 160 mil peak-peakButton InputsoConfigurable Upper OK limit: -0.25 to -22 V(greater than lower ok) External button to reset latched alarm and relayoConfigurable Lower OK limit: -0.25 to -22 V(less than upper ok) One buried button provides 3 functions:oDisplay monitor information including: Accuracy: 1% of full scale range User account name Supports custom accelerometers (2 or 3 wires) IP address Independent 24-bit ADCs on both channels FW/HW versionDocument: 105M0340Rev. L (09/16)Page 3 of 13

oLCD contrast adjustmentoReset settings to default including: User account name Password Network configurationoMaximum switched contact voltage andcurrent: 6A @24VAC / 5A @30VAC / 5.8A@24VDC / 4A @30VDC4-20mA Output (2300/20) Two 4-20mA outputsJumper between COM & Chassis GND 4 to 20mA output values are proportional to thefull-scale of the associated measurement There is a 2-pin terminal interface which allowsconnection of COM and Chassis GND together. Each output can be software configured tooutput any variable Alternatively, COM can be connected to earthground separately through a terminal. Voltage compliance: 0 to 12Vdc range acrossloadBuffered Output Load resistance: 0 to 600Ω There are three buffered outputs available on themonitor through BNC connectors: Resolution: 0.3662uAo2 Vibration Outputso1 Speed OutputRelay Output There are two dry-contact relay outputs May be normally energized or de-energized No output feedback determination Accuracy: 1% over operating temperature range Update rate: 100ms Configurable with default 2mA clamp current No output feedback determinationSPA Output (2300/25) Input signal range Relay circuit specification in Non-Hazardousarea:oType: Single pole, double throwoSealing: Epoxy sealedoContact life:100,000 cycles @ 5 amps 250 VAC200,000 @ 1 amp, 24 VDCoInsulation resistance:1000 MΩ minimum @ 500 VDCoRelay closed contact resistance:1 Ω maximumoRelay open contact resistance:1 MΩ minimumoMaximum switched contact voltage:250V AC /250V DCoMaximum breaking contact current:6A @250VAC / 6A @24VDCoMaximum switched power:1500VA AC / 150 Watts DC Relay circuit specification in Hazardous area:oHigh AC: 8VppoLow AC: 1.6VppoDC GAP: 0 to -20Vdc (max measurable ACsignal is 1Vpp) AccuracyoHigh/Low AC: 1% of Full-Scale at 100HzoDC GAP: 0.5V (measurable AC accuracy: 20mV) Frequency responseo10Hz to 3000Hz 5%LEDs OK: Indicates when the monitor is operatingproperly Protection fault: Indicates that there is ahardware fault that is impacting alarmdetermination User inhibit: indicates the alarm/relays have beenintentionally inhibited from operation Bypass: indicates user initiated bypass action Relay status: indicates if relays have beenactivatedDocument: 105M0340Rev. L (09/16)Page 4 of 13

TX/RX: Indicates the Ethernet status and monitorcommunicating with remote software2014/35/EU Low VoltageStandard: Speed channel statusEN61010-1: 2010 Channel Alarm Status:European Community Directives:LV Directive 2014/35/EUoAlert LED: engages if any channel is in alertstateoDanger LED: engages if any channel is indanger stateLCDLCD display allows viewing machine speed, vibrationmeasurements value, setpoints, and Standards:EN61000-6-2 Immunity for Industrial EnvironmentsEN61000-6-4 Emissions for Industrial EnvironmentsEN61326-1 Electrical equipment for measurement,control and laboratory use - EMC requirementsEuropean Community Directives:EMC Directive 2014/30/EUHazardous Area Approvals RJ-45 for 10Base-T/100Base-TX Ethernet cablingFor a detailed listing of country and productspecific approvals, refer to the Approvals QuickReference Guide (document 108M1756) located atthe following website: www.GEmeasurement.com. Cable length: 100 meters (328 ft.) maximumCSA/NRTL/CEnvironmental LimitsClass I, Division 2/Zone 2AEx/Ex nA nC [ic] IIC T4 GcClass I, Div. 2, Groups A, B, C, DATEX/IECEx Ethernet, 10Base-T and 100Base-TX. Conformsto IEEE802.3Operating Temperature: -30 C to 65 C (-22 F to 149 F)II 3 GEx nA nC [ic] IIC T4 GcStorage Temperature:ATEX 2014/34/EU -40 C to 85 C (-40 F to 185 F)Humidity: Up to 95%, non-condensingVibration Limitation: 3gBattery Life for Real Time Clock: Powered: 38 years @ 50 C (122 F) Un-powered: 12 years @ 50 C (122 F)Compliance and CertificationsGeneral and Electrical Safety:UL Std. No. 61010-1 (3rd Edition)CAN/CSA C22.2 No. 61010-1-12Intrinsic Safety Parameters:For Proximitor Transducer:Uo: 24V; Io: 46mA; Co: 200nF; Lo: 1mHFor Accelerometer Transducer:Uo: 24V; Io: 3.3mA; Co: 200nF; Lo: 1mHFOR SPA POWER (2300/25 Only):Ui 15V; Ii 150mA; Pi 560mW; Ci 0; Li 0FOR SPA SIGNAL (2300/25 Only):Ui 12V; Ii 12mA; Pi 36mW; Ci 0; Li 0PhysicalDimensions (Width x Depth x Height)127mm x 127mm x 76.2mm (5in x 5in x 3in)Weight1.03kg (2.26lbs)Document: 105M0340Rev. L (09/16)Page 5 of 13

002MountingPanel mount or DIN rail (adapter included)1 - 2300/20 or 2300/25 MonitorOrdering Information1 - 6 ft. shielded Ethernet cableFor a detailed listing of country and productspecific approvals, refer to the Approvals QuickReference Guide (document 108M1756) located atthe following website: www.GEmeasurement.com.1 - 13x15x8 in. fiberglass housing withwindow1 - Accelerometer sensor1 - 15 ft. (4.8m) accelerometer cable2300 Series Vibration Monitor(Excluding Keyphasor sensor and 24VDCpower supply1)2300/20-AA-BB: Monitor with 4-20ma Outputs(including DIN rail mount assembly, manual andmonitor configuration software)0031 - 2300/20 or 2300/25 Monitor1 - 6 ft. shielded Ethernet cable2300/25-AA: Monitor with SPA Outputs (includingDIN rail mount assembly, manual and monitorconfiguration software)2 - Accelerometer sensors2 - 15 ft. (4.8m). accelerometer cablesAA: Approvals Option00None02Multiple Explosive AtmosphereCertifications (ATEX/IECEx/CSA)(Excluding Keyphasor sensor, enclosureand 24 VDC power supply1)BB: Approvals Option00None02Multiple Explosive AtmosphereCertifications (ATEX/IECEx/CSA)BB: Software License for System 1 Evo Connection00Monitor without License01Monitor with LicenseCC: Software License for System 1 Evo Connection00Monitor without License01Monitor with License2300/20 KIT-AAA-BB-CC: Bently Nevada 2300/20Condition Monitoring System Kit2300/25 KIT-AAA-BB: Bently Nevada 2300/25Condition Monitoring System KitAAA: Configuration0011 - 2300/20 or 2300/25 Monitor1 - 6 ft. (1.8m) shielded Ethernet cable1 – 13 x 15 x 8 in. (338 x 389 x 209mm)fiberglass housing with window2 - Accelerometer sensors2 – 15 ft. (4.8m) accelerometer cables(Excluding Keyphasor sensor and 24 VDCpower supply 1)3071/13-AA-BB: System 1 2300 Series Device ImportAA: Not available for 2300 monitor00BB: Quantity of 2300 Monitoring Systems## - Numeric Entry [1- n]Notes: 3071/13 is only applicable for 2300 monitors thatare installed/purchased without the System 1Evolution device license. System 1 Evolution software requires a separateorder. Refer to the System 1 datasheetDocument: 105M0340Rev. L (09/16)Page 6 of 13

(document 108M5214) for detailed orderinginformation. The maximum number of 2300 monitorconnections is 350 in System 1 16.1. (This numberwill be increased in later versions.)105M6193-01 AA option is for vbOnline Pro Device.Fiberglass NEMA 4X/IP68weatherproof housing with windowin door (includes mounting plate formonitor)Dimensions:(Width x Depth x Height)338.3 x 389.1 x 209.8mm(13.3 x 15.3 x 8.2in)1We provide 3 kinds of power supplies with different temperaturerange and different power. Please check Accessories below forthe details.Accessories106M7607-01Power supply for DIN rail mounting,100/240AC to 24DC/1.5ACertifications (ATEX)(-25 C 70 C, 35*99*95 mm)(One power can drive max 4monitors)110M7102-01Power supply for DIN rail mounting,100/240AC to 24DC/1.3ACertifications (CID2 by UL)(-25 C 70 C, 22.5*99*107 mm)(One power can drive max 4monitors.)106M6694-01Power supply for DIN rail mounting,110/220AC to 24VDC/5ACertifications (ATEX, IECEx, CID2 byUL)(-40 C 70 C, 40*130*125 mm)(One power can drive max 10monitors.)AM3100T2-Z2Accelerometer sensorDocument: 105M0340Rev. L (09/16)Page 7 of 13

330500 Velomitor330400/330425 Accelerometer sensor330505 Velomitor330525 Velomitor190501 Velomitor100M0741Proximity SwitchDocument: 105M0340Rev. L (09/16)Page 8 of 13

284947Magnetic PickupSplash Proof Cable for AM3100T2-Z2Accelerometer9571 Mod : 285031-AA* Cable for 2 wire extensionwith a splash proof

Bently Nevada* Asset Condition Monitoring Description The 2300 Vibration Monitors provide cost-effective continuous vibration monitoring and protection capabilities for less critical and spared machinery. They are specifically designed to continuously monitor and protect essential medium to low criticality machinery in a wide range of industries including: oil & gas, power generation, water .