MCS MAGNUM CHILLER Chiller Plant Manager(CPM)

Transcription

MCS MAGNUM CHILLERChiller Plant Manager(CPM)5580 Enterprise Pkwy.Fort Myers, FL 33905Office: 239-694-0089Fax: 239-694-0031Manual & Sequence of OperationsVersion 1.4www.mcscontrols.comMCS TotalSolutionfor all yourControlNeedsRevision-2018-11-13Energy Efficient and RoHS Compliant

MCS-PLANT MANAGERREVISION 1.4Revision/Disclaimer PageDateAuthorDescription of Changes04-23-2015DEWCreate Manual05-04-2015DEWEdits from Remy07-22-2015DEWEdits from 8DEWAdd setpoints 106 and 107 from D205-10-18DEWAdd setpoints 108 and 109 from D209-10-18DEWAdd setpoint 112, changes to setpoint 108 &10909-11-18DEWAdd 12 volt boards11-13-18DEWChange to setpoint #5 and #6 and #109The MCS Commitment is to provide practical solutions for the industriesneeds and to be both a leader and partner in the effective use ofmicroprocessor controls.Micro Control Systems, Inc.5580 Enterprise ParkwayFort Myers, Florida 33905PH:(239) 694-0089 FAX:(239) 694-0031www.mcscontrols.comAll information contained within this document is considered to be proprietary information of Micro Control Systems, Inc.No information or data from this document shall be published, used, reproduced, transmitted, or disclosed to others outside yourorganization without the prior expressed written consent of Micro Control Systems, Inc. This document and the informationcontained herein shall be treated as proprietary. Reasonable provisions shall be provided to ensure that this informationremains proprietary by your employees, agents, and other personnel that may have access to this document.Copyright 20182

MCS-PLANT MANAGERREVISION 1.4Table of ContentsTable of Contents. 3Chapter - 1.Introduction to CPM (Chiller Plant Manager). 5Chapter - 2.About CHILLER Chiller Plant Manager. 62.1.2.2.2.3.2.4.2.5.2.6.Chiller Chiller Plant Manager (CPM) V17.6Specifications MCS-Magnum Revision 8.5.6MCS-Magnum-N Revision 9.1.7MCS-SI16-A04- Version 1.3.8MCS-RO10 - Version 1.2.8MCS-Magnum-N-12 Revision 9.1.92.8.1Optional Single Output Power Supply.92.7.MCS-IO-BASE and MCS-IO-EXT.102.8.MCS-RO-BASE and MCS-RO-EXT.112.9.MCS-SI-BASE and MCS-SI-EXT.12Chapter - 3.Chapter - 4.4.1.4.2.4.3.4.4.MCS-KEYPAD - Keys and their functions.14Powering the CPM.15Pump Control Algorithm.15Chiller Control Algorithm.17CPM Unit Lockouts.17Standard Capacity Control Logic.17Chapter - 5.Common Definitions for Capacity Control Logic.18Stage Up Hold.18Staging Delay.18Fully Loaded.18Fully Unloaded.185.4.1Target.185.4.2Control Zone.185.4.3Controlling Sensor.195.4.4The Rate of Change of the Control Input.195.4.5Step Delay.195.5.Ratio Adjustments.195.1.5.2.5.3.5.4.Chapter - 6.CPM - STATES.20CPM Unit States.20Individual Chiller States.20Individual Pump States.21Pump Group Capacity Control States.216.1.6.2.6.3.6.4.Chapter - 7.7.1.CPM Config Screens.23MAG CPM (MAGNUM Chiller Chiller Plant Manager).237.1.1General Info .247.1.1.1.Chillers.247.1.1.1.1.‘Primary Chillers’.247.1.1.1.2.Chillers are Hardwired?.24Chapter - 8.7.2.7.3.7.4.7.5.7.6.7.7.7.8.7.9.7.10.MAG CPM - General Info.24Relays.25Control Options.25Bypass Valves.25Lost BMS Communication.25Isolation Valves Located On:.26Schedule Controls.26Staging Method.26When to Rotate.26Sensors.263

MCS-PLANT MANAGERREVISION 1.4Chapter - 9.9.1.MAG CPM - Chiller Info.27Chiller Info screen.27Chapter - 10.MAG CPM - Pump Info.2810.1. Pumps and # of Pump Groups Info screen.2810.1.1Pump Group.28Chapter - 11.MAG CPM - Condenser Info.2911.1. # of Condensers.2911.1.1Condenser Control Switches, Lights.2911.1.2Condenser Groups.29Chapter - 12.12.1.MAG CPM - Exhaust Info.30Not programmed into firmware yet.30Chapter - 13.13.1.MAG CPM - Cooling Info.31Not programmed into firmware yet.31Chapter - 14.Magnum CPM Setpoints.3214.1. Setpoint RM.3314.1.4TIME.3314.1.5TARGET.3314.1.6CPM TARGET.3414.1.7CPM RATIO.3414.1.8DELAY.34Chapter - 15.CPM - SET POINTS.354

MCS-PLANT MANAGERChapter - 1.REVISION 1.4Introduction to CPM (Chiller Plant Manager)This software is designed to control a site that consists of multiple chiller packages that are being controlled by individualMCS MAGNUMS.Each MCS MAGNUM controls its own chiller package and sends the CPM information as to its state.The Chiller Plant Manger will control the process pumps to ensure that the required water flow is maintained and thenstage the chiller packages to meeting the cooling requirements of the site. The Chiller Plant Manager is based upon theCPM V17 and Chiller HVAC V17 software family.The Chiller Plant Manager will maintain water flow by controlling the pumps. To determine the site needs, the ChillerPlant Manager will compare the control temperature to the temperature target and develop the step capacity needed.The Chiller Plant Manager can also review an input signal that limits its loading capacity. This is used for load limiting.Communications between the Chiller Plant Manager and the MCS-MAGNUMS on the chiller packages is accomplishedover the RS485 network. Messages are transmitted to the MCS-MAGNUMS that indicate if that package can run andthe maximum number of steps if fixed step system or maxi

Manual & Sequence of Operations Version 1.4. MCS MAGNUM CHILLER Chiller Plant Manager(CPM) Revision-2018-11-13. MCS-PLANT MANAGER REVISION 1.4 2. The MCS Commitment is to provide practical solutions for the industries needs and to be both a leader and partner in the effective use of . microprocessor controls. Micro Control Systems, Inc. 5580 Enterprise Parkway Fort Myers, Florida