APPENDIX K - City Of Lacey

Transcription

APPENDIX K

Lift Station Electrical Control PackageAPPENDIX KK 2-10Electrical Drawings 7-49-E thru 7-57-E Color (11X17)K 11-20 Approved Materials ChecklistK 21-22 Labeling DocumentK 24-32 Electrical Drawings 7-49-E thru 7-57-E B&W (11X17)Electrical Drawings 7-49-E thru 7-57-E (24X36) are available upon requestK-108/2017

K-208/2017

K-308/2017

K-408/2017

K-508/2017

K-608/2017

K-708/2017

K-808/2017

K-908/2017

K - 1008/2017

APPROVED MATERIALS (BOM)SPECIAL CONSTRUCTION NOTESITEM123456CITY OF LACEY DESCRIPTIONMANUFACTURERPART #*Control System Manufacturing shall use listed parts and install them usingthe Special Construction Notes.ENGINEERSPECIFIED PART#(see foot note)RADIO EQUIPMENTDATA RADIOCALAMPINTEGRA TR 242-4048-***PLC TO RADIO SERIAL CABLE "CUSTOM"ALLEN BRADLEY1761-CBL-PM02RADIO TO ARRESTOR COAX JUMPER"CUSTOM""SMA" type male to "N" type maleLIGHTENING ARRESTORPOLYPHASERIS-B50LN-C2RADIO BRACKET“CUSTOM”ETHERNET PORTEATONM22-RJ45-SACABINET LIGHTCOOPERHU1024D830P24" DAISY CHAIN CONNECTORCOOPERHU103P120" DAISY CHAIN CONNECTORCOOPERHU104PCut connector off of one end and land under CR2.TVSSGENERALELECTRIC9L15ECC001Mount TVSS to the back plate.The 9 pin end must be re-pinned to null modem configuration.No Adapter!SEE DETAIL SHEET 7-57-EBond to ATS with #8 AWG CU wire.Allow minimum 1" clearance above and below the radio and flush with thefront of the Pump Control Panel.INTRUSION SWITCH ASSEMBLYRECEPTACLEEATONE50RASWITCH BODYEATONE50SA5 HEADEATONE50DR1LEVER 0SS HOODRITTAL3239.080Mount intrusion switch to Main Control Cabinet ceiling track with a bracket.Intrusion switch is configured normally closed held open. When the controlcabinet door is closed, the lever switch arm is pushed back and the contactswithin the switch are held open. When the control cabinet door is opened,the lever arm is released and contacts within the switch close. At this pointCR2 is energized. CR2 has two C–form contacts (two poles). One poleswitches the cabinet light via the normally open contacts the other poleswitches the intrusion input via normally closed contacts. The PLC programcreates an intrusion alarm when there is no input to I:0/2. WHEN THEMAIN CONTROL CABINET IS CLOSED, THERE IS AN INPUT TO I:0/2.CABINET VENTILATION*Engineer to determine part number based on voltage/amperageand fill in the missing part number represented by *the asterisk.K - 11Mount fan on lower right.Mount intake and exhaust hoods forward in the Main Control Cabinet towardthe door, allowing clearance for the Service Entrance Disconnect. Filtermust be installed.08/2017

APPROVED MATERIALS (BOM)SPECIAL CONSTRUCTION NOTESITEM7891011121314151617CITY OF LACEY DESCRIPTIONMANUFACTURERPART #PHASE MONITORCROUZETH3USPHASE MONITOR FUSE HOLDERBUSSMANCHCC31PHASE MONITOR FUSESBUSSMANKTK-R-1/10CB5 - TVSSEATONWMZT3C30POWER DISTRIBUTION BLOCKBUSSMAN16323-3 Include coverDUAL THERMOSTATSTEGOZR 01172.0-01FOR 2 PUMP STATIONHOFFMANCSD363012 with steel back plateFOR 3 PUMP STATIONHOFFMANCSD423612 with steel back plate*Control System Manufacturing shall use listed parts and install them usingthe Special Construction Notes.ENGINEERSPECIFIED PART#(see foot note)Load Side - one connection per point i.e. CB1 and CB2 would require 6points. Wire connected to any breaker must exceed the breakers ampacity.PUMP CONTROL PANELTRANSFORMERGround center tap to back plate.Compression or ring tongue type lugs.10KEATONS48G11S10NAUTOMATIC TRANSFER SWITCHASCOD3ATSA3****GXC - 11BEMETER HEADONE THAT MEETS PSE'S CURRENT SPECIFICATIONSTorque to spec.SERVICE ENTRANCE DISCONNECTENCLOSUREEATONWFDN***Needs to be drilled so that it can be locked in the on position.Shipped with the Main Control Cabinet (to be mounted by the fieldelectrician). Torque to spec.NEUTRAL KITEATONDG***N*Control systems manufacturer to install neutral kit.BREAKEREATONEHD3***Control systems manufacturer to install breaker.TRANSFORMER PRIMARY BREAKEREATONFD2030L*Engineer to determine part number based on voltage/amperageand fill in the missing part number represented by *the asterisk.K - 1208/2017

APPROVED MATERIALS (BOM)SPECIAL CONSTRUCTION NOTESITEM1819CITY OF LACEY DESCRIPTIONTRANSFORMER SECONDARY BREAKERMANUFACTURERPART #EATONEHD205OLLUT 5 1400BREAKER PANELEATONCH12L125RINTRINSICALLY SAFE RELAY PANEL ENCLOSUREHOFFMANA12N106 with white steel backplateMAG 5100 ELEMENT and MAG 6000 TRANSMITTERSIEMENS7ME6580***142 1JA2COIL CABLESIEMENSFDK: 001STCABEMPTY PIPE CABLESIEMENSFDK: 001SPCABFLOW TRANSMITTER REMOTE MOUNT BRACKETSSIEMENSFDK: 085U1053GROUNDING RINGSSIEMENSTGX:001F0***POTTING KITSIEMENSFDK: 085U0220UPS RECEPTACLEPHOENIX2963860GFCIHUBBELLDRUBGFI15 DGK*Control System Manufacturing shall use listed parts and install them usingthe Special Construction Notes.ENGINEERSPECIFIED PART#(see foot note)LEVEL CONTROL20202122232425All wires shall be tinned stranded MTW/AWM/TEW. NO VINYLCOVERING. Wires connected to breakers will be black #12 .All 120 VAC control wires are to be red #14.All 120 VAC neutrals will be white.One neutral and ground for each branch circuit.Barrier to be outlined with red tape on the bottom of the Main ControlCabinet prior to shipping.Knock out a 1" penetration centered in the bottom of the ISR panel.FLOW METER*Engineer to determine part number based on voltage/amperageand fill in the missing part number represented by *the asterisk.K - 13Grounding rings are required for all installations.08/2017

APPROVED MATERIALS (BOM)SPECIAL CONSTRUCTION NOTESITEM262728293031CITY OF LACEY DESCRIPTION33PART #OUTSIDE AREA LIGHT SWITCHBRYANTCSB120BWBELL BOXCOOPERTP7010COVERBRYANTSS1CABINET HEATERHOFFMANDHA2001APANELVIEW HMIALLEN BRADLEY2711P - T7C4A8*Control System Manufacturing shall use listed parts and install them usingthe Special Construction Notes.Scaled to read the pumps running amps in the center of the scale .i.e.If the pump is designed to run at 10 amps, the meter should be scaled 1–20amps.AMMETER2 1/2 "PC&SST70MOTOR CIRCUIT BREAKER THRU - DOOR OPERATOREATONEHMVD - 12RIDECHW - F**22 MM HW SERIES LED LAMPIDECLST - H2*FULL VOLTAGE ADAPTERIDECHW-DA1FBLUE LENSIDECHW1A - L1 – SCONTACT BLOCKSIDECHW - F**OPERATORIDECHW1B - ****22 MM HW SERIES CONTACT BLOCKSIDECHW - F**OPERATORIDECHW1S - *TClocked straight up and down for the "ON" position. Mount Breaker andOperator independently, so the Operator can be removed and the Breakerremains mounted on the back plate. Operator Rod needs to be cut to theproper length. Install Cotter Pins.H–O–A SWITCH22 MM HW SERIES CONTACT BLOCKS32MANUFACTURERENGINEERSPECIFIED PART#(see foot note)CONTROL POWER INDICATORHIGH WET WELL OVERRIDE SELECTOR SWITCH*Engineer to determine part number based on voltage/amperageand fill in the missing part number represented by *the asterisk.K - 1408/2017

APPROVED MATERIALS (BOM)SPECIAL CONSTRUCTION NOTESITEM343536373839404142CITY OF LACEY DESCRIPTIONMANUFACTURERPART #*Control System Manufacturing shall use listed parts and install them usingthe Special Construction Notes.ENGINEERSPECIFIED PART#(see foot note)HIGH WET WELL LEVEL INDICATOR/RESET SWITCH22 MM HW SERIES LED LAMPIDECLST - H2*FULL VOLTAGE ADAPTERIDECHW-DA1FRED LENSIDECHW1A - L1 – RCONTACT BLOCKSIDECHW - F**OPERATORIDECHW1B - ****UPS SHELF“CUSTOM”MOTOR CIRCUIT BREAKEREATONHMCPE***Wire connected to any breaker must exceed the breakers ampacity.CURRENT TRANSFORMERCROMPTON2RL-***Paired with the Ammeter, may need to wrap CT to achieve an accuratecurrent reading.SOFT STARTEATONS8-11 *****AIR SCRUBBER BREAKEREATONHMCPE**ON/OFF HASPLOCK - 3 POLEEATONEFPHLLITTLE JOHN BREAKEREATONHMCPE**ON/OFF HASPLOCK - 3 POLEEATONEFPHLCB7 - LINE POWER CONDITIONEREATONFAZ-C5/1-NANEON FUSE BLOWN INDICATORSPRECHER SCHUHV7-H4AC FUSESBUSSMANGDL - **/KLM - **/ABC - **The shelf needs to be heavy enough to support the weight of the UPS andlarger than the UPS base. For earthquake readiness, the UPS must also bestrapped to the Main Control Cabinet back plate.Set to limiting current start mode.Set fault reset to auto.Wire connected to the soft start must exceed the breakers ampacity.AC FUSE HOLDERS*Engineer to determine part number based on voltage/amperageand fill in the missing part number represented by *the asterisk.K - 1508/2017

APPROVED MATERIALS (BOM)SPECIAL CONSTRUCTION NOTESITEM43444546474849505152CITY OF LACEY DESCRIPTIONMANUFACTURERPART #*Control System Manufacturing shall use listed parts and install them usingthe Special Construction Notes.ENGINEERSPECIFIED PART#(see foot note)DC FUSE HOLDERSLED FUSE BLOWN INDICATORSPRECHER SCHUHV7-H5DC FUSESBUSSMANABC - **/KLM - **12 VDC POWER SUPPLYSOLASDP3 - 15 - 100T24 VDC POWER SUPPLYSOLASDP4 - 24 - 100LT24 VDC SOFT START POWER SUPPLYEATONPSG240EPROGRAMMABLE LOGIC CONTROLLER AND I/OAllow 1" clearance per manufacturer requirements.All wires shall be tinned stranded MTW/AWM/TEW.NO VINYL COVERING.12 VDC Positive - Orange #1612 VDC Negative - Yellow #16Allow 1" clearance per manufacturer requirements.All wires shall be tinned stranded MTW/AWM/TEW.NO VINYL COVERING.24 VDC Positive - Dark blue #1624 VDC Negative - White with blue stripe #16Allow 50 mm clearance top and bottom, 20 mm on the sides, permanufacturer requirements.All wires shall be tinned strandedMTW/AWM/TEW.NO VINYL COVERING.24 VDC Positive Dark blue #16 24 VDC Negative - White with blue stripe #16Allow 2" clearance per manufacturer requirements.MICROLOGIX 1100ALLEN BRADLEY1763-L16DWDANALOG INPUT MODULEALLEN BRADLEY1762-IF4DIGITAL INPUT MODULEALLEN BRADLEY1762-IQ16ETHERNET SWITCHN-TRON105TX-SLCONTROL RELAYSIDECRH*B-ULRELAY BASEIDECSH*B-05PULSE RELAY CR5ALLEN BRADLEY700-HLS1Z24Pulse wires shall be tinned stranded MTW/AWM/TEW.NO VINYL COVERING.Positive - Dark blue #16Negative - White with blue stripe #16LINE POWER CONDITIONERALLEN BRADLEY4983-DC120-05Allow 1" clearance per manufacturer requirements.TIME DELAY RELAYCROUZETOUR1Set on “C” off delay.RELAY BASEIDECSR2P - 06*Engineer to determine part number based on voltage/amperageand fill in the missing part number represented by *the asterisk.K - 1608/2017

APPROVED MATERIALS (BOM)SPECIAL CONSTRUCTION NOTESITEM5354555657CITY OF LACEY DESCRIPTION60616263*Control System Manufacturing shall use listed parts and install them usingthe Special Construction Notes.FOR FLYGT PUMPSMINICAS IIFOR NON FLYGT PUMPSMTS#MOS-1PGround pin 4. Run blue wire from pin 4 to field terminal. Set on manualreset.TERMINAL BLOCKSSPRECHER SCHUHV7-W4 SERIESSteel Din Rail (NO Aluminum). Stops installed.MAIN CONTROL CABINET ENCLOSUREHOFFMANA727224USSLP-MODwith white steel back plateSet on manual reset.Factory installed Drip Shield and drain holes in the enclosure bottom per (UL3R). No penetrations in the top. Padlocking handle.Accessories to be spot welded: Door stop kit - Bottom, both doors (seemodification services guide). Folding 12" x 12" Shelf - ACSHLF1212SS.Default location: Inside left door.ISOLATION PEDESTAL ENCLOSUREFOR 2 PUMP STATIONHOFFMANFOR 3 PUMP STATIONHOFFMANA30H2412SS6LP3PT with whitesteel back plateA36H3612SS6LP3PT with whitesteel back plateSEE DETAIL SHEET 7-51-E AND 7-54-ESEE DETAIL SHEET 7-51-E AND 7-54-ECABLE SEALAPPLETONPXSS2K SERIESMELTRICD****PUMP POWER RECEPTACLEDE-CONTACTOR TYPE59PART #SEAL FAIL / OVER TEMP RELAYLIQUID POUR RESIN BARRIER58MANUFACTURERENGINEERSPECIFIED PART#(see foot note)Pumps with separate cords for seal fail/over temp also usePN7C 63-034043 receptacle.SEE DETAIL SHEET 7-54-EPUMP CORD CONNECTORDE-CONTACTOR TYPEMELTRICISOLATION PEDESTAL BARRIER“CUSTOM”ISOLATION PEDESTAL HEATERPFANNENBERG17015005007ISOLATION PEDESTAL HYGROSTATSTEGOMFR012INTRINSICALLY SAFE RELAYTURCKIM1-22EX-R*Engineer to determine part number based on voltage/amperageand fill in the missing part number represented by *the asterisk.D**** with NPT HANDLEPumps with separate cords for seal fail/over temp also usePN7C 01-NA013-12 connector. Use with 1/2" NPT poly handle 63-38043.SEE DETAIL SHEET 7-54-EConstructed of aluminum and needs to run the full height of the panel andextend 6 inches towards the door from the back plate.K - 1708/2017

APPROVED MATERIALS (BOM)SPECIAL CONSTRUCTION NOTESITEM646566676869CITY OF LACEY DESCRIPTIONMANUFACTURERPART #BREAKER PANEL BREAKER – 15AEATONCH115BREAKER PANEL BREAKER – 20AEATONCH12050 foot cord needs to be supplied with pendant attached and then cut tolength in the filed.Cord needs to be long enough to reach the wet well from the main controlcabinet.Neatly coil up cord and hag up by using a heavy duty Velcro strap with aeyelet in it to secure to an existing bolt.PUMP JOG PENDANTFOR 2 PUMP STATIONWOODHEAD4022FOR 3 PUMP STATIONWOODHEAD4023ISOLATION PEDESTAL POST BASEB-LINEB281SQ SS4SEE DETAIL SHEET 7-54-EUNISTRUTP2073ASQSSSEE DETAIL SHEET 7-54-EOZ-GEDNEY170-150GSEE DETAIL SHEET 7-56-E1 ½” WEATHER HEADANTENNA CABLINGMust be taped with silicone splicing tape and covered with black vinyl tape.NO HEAT SHRINK.SEE DETAIL SHEET 7-56-ELMR400 with type "N" male LMR400 connector70ANTENNALaird UHF Directional Yagi71727374*Control System Manufacturing shall use listed parts and install them usingthe Special Construction Notes.ENGINEERSPECIFIED PART#(see foot note)ANTENEX4506SEE DETAIL SHEET 7-56-E16’ LIGHT POLE WITH TENNON TOPHAPCORTA16D6B4200BAL/ABGround inside the hand hole.Grout under bottom of pole.SEE DETAIL SHEET 7-56-ELUMINAIRE ARMCREEXA-XSP4PTMNTMount with stainless steel hardware.SEE DETAIL SHEET 7-56-ELED LUMINAIRECREEBXSPBHT3MEB40KUS ULBKJSEE DETAIL SHEET 7-56-ESITRANS P DS III PRESSURE TRANSMITTERSIEMENS7MF4033-1DA10-1NC6-B21DIAPHRAM SURE TRANSMITTER ASSEMBLY*Engineer to determine part number based on voltage/amperageand fill in the missing part number represented by *the asterisk.K - 18Instrument to be calibrated for Full scale output (20 mA) at 100 PSIG.SEE DETAIL SHEET 7-56-EThe diaphragm seal is to be filled with glycol and mounted to the pressuretransmitter as an assembly at the instrumentation shop.08/2017

APPROVED MATERIALS (BOM)SPECIAL CONSTRUCTION NOTESITEM75767778798081828384CITY OF LACEY DESCRIPTIONMANUFACTURERPART #*Control System Manufacturing shall use listed parts and install them usingthe Special Construction Notes.ENGINEERSPECIFIED PART#(see foot note)No splices in the J-box. All wires to be home run to the Main Control Cabinetfield terminals.CHECK VALVE SWITCH ASSEMBLYRECEPTACLEEATONE50RASEE DETAIL SHEET 7-56-ESWITCH BODYEATONE50SASEE DETAIL SHEET 7-56-E5 HEADEATONE50DR1SEE DETAIL SHEET 7-56-ELEVER ARMEATONE50KL537SEE DETAIL SHEET 7-56-EFOR CRISPIN VALVE USE BRACKETCRISPINP0611FRFVI-13-2 andPA111FRFVI-18-2Item 75 & 76 included Crispin valve # BDS0A24RF*1-VI-LM-CHR-SP andCrispin valve # BDS0A24RF*1-VI-LM-CHL-SPNOT USED WITH CRISPIN VALVE“CUSTOM”LIMIT SWITCH MOUNTING BRACKETLIMIT SWITCH POST BASENeeds to be constructed out of 1/4" x 1 1/2" x 8" stainless steel flat bar. Drilland tap holes to mount the limit switch to the flat bar and secure to strut withstrut nuts. SEE DETAIL SHEET 7-57-EB-LINEB280SQ SS4SEE DETAIL SHEET 7-57-EPOWER STRUTP2072ASQSSSEE DETAIL SHEET 7-57-E1” X 1/2” SS REDUCER BUSHINGCROUSE – HINDRBSS31SEE DETAIL SHEET 7-56-ESS CORD GRIPWOODHEADMAX - LOC 1300980070SEE DETAIL SHEET 7-56-ESS CORD GRIP WITH STRAIN RELIEFWOODHEADMAX – LOC 130097 – 034SEE DETAIL SHEET 7-56-EHIGH LEVEL FLOAT (HIGH BALL) MOUNTING BRACKETANCHORSCIENTIFICW-MSSEE DETAIL SHEET 7-56-EHIGH LEVEL FLOAT (HIGH BALL)ANCHORSCIENTIFICROTO-FLOAT N.O. type “S” **footSEE DETAIL SHEET 7-56-EPVC COATED CAPPED ELLOCALLBY35-GApply copper coat to cap threads.SEE DETAIL SHEET 7-56-ELEVEL TRANSDUCERSIEMENSXPS–15 7ML11180EA30*Engineer to determine part number based on voltage/amperageand fill in the missing part number represented by *the asterisk.K - 19Cable will loop through the Isolation Pedestal and home run to LevelControl. Do not remove the sheathing. Seal cable gland directly tosheathing with resin.SEE DETAIL SHEET 7-56-E08/2017

APPROVED MATERIALS (BOM)SPECIAL CONSTRUCTION NOTESITEM8586CITY OF LACEY DESCRIPTIONMANUFACTURERPART #LITTLE JOHN DIGESTERDO2ELJD1001-**AIR SCRUBBERPURE AIRDS300 with Mist & GreaseEliminator*Engineer to determine part number based on voltage/amperageand fill in the missing part number represented by *the asterisk.K - 20*Control System Manufacturing shall use listed parts and install them usingthe Special Construction Notes.ENGINEERSPECIFIED PART#(see foot note)Must be converted to 2 wire control to automatically re - start after a powerfail.SEE DETAIL SHEET 7-56-EMust be converted to 2 wire control to automatically re - start after a powerfail.SEE DETAIL SHEET 7-56-E08/2017

Phenolic Legends1-1/2” X 7-1/2” Red background with white 3/8” letters,text to include: 1 277/480 3ø *** AMPS4-1/2” X 7-1/2” Black background with white 1/4”letters, text to include: 2 SERVICE/METER DISCONNECT1-1/2” X 7-1/2” Black background with white 3/16”letters, text to include: 3 LIFT STATION (address)1-1/2” X 6” Black background with white 1/2” letters,text to include: 4 LIFT STATION (number)1-1/2” X 5” Black background with white 3/8” letters,text to include: 6 BREAKER PANEL1-1/2” X 6” Black background with white 3/8” letters,text to include: 7 PUMP CONTROL PANEL3/4” X 2-1/2” Black background with white 3/8” letters,text to include: 8 PUMP 13/4” X 2-1/2” Black background with white 3/8” letters,text to include: 10 PUMP 31-3/4” X 2” Black background with white 5/32” letters,text to include: 12 CONTROL POWER1-3/4” X 2” Black background with white 5/32” letters,text to include: 13 HIGH WET WELLFEEDS ATS IN CONTROL CABINETFED BY STANDBY GENERATOR(location of generator)1-1/2" X 5” Red background with white 1/4” letters, textto include: 5 DISCONNECT TO THEBREAKER PANELRIGHT OF ENCLOSURE3/4” X 2-1/2” Black background with white 3/8” letters,text to include: 9 PUMP 2OVERRIDE SELECTP11-3/4” X 2” Black background with white 5/32” letters,text to include: 13 HIGH WET WELLOVERRIDE SELECTP1P21-3/4” X 2” Black background with white 5/32” letters,text to include: 14 HIGH WET WELLP21-3/4” X 2” Black background with white 5/32” letters,text to include: 15 HAND-OFF-AUTO3/4” X 3” Black background with white 3/16” letters,phenolic width to match HOA width, text to include: 16 PUMP 11-1/2" X 5” Black background with white 3/8” letters,text to include: 20 ISR PANELLEVEL RESETP33/4” X 3” Black background with white 3/16” letters,phenolic width to match HOA width, text to include: 17 PUMP 23/4” X 3” Black background with white 3/16” letters,phenolic width to match HOA width, text to include: 18 PUMP 31-1/2" X 5” Black background with white 3/8” letters,text to include: 19 LITLLE JOHN1-1/2" X 5” Black background with white 3/8” letters,text to include: 21 ISOLATION PEDESTAL1-1/2" X 5” Red background with white 3/16” letters,text to include: 22 GENERATOR EMERGENCY1-1/2" X 5” Black background with white 3/8” letters,text to include: 23 AIR SCRUBBERSTOP INSIDEK - 2108/2017

Vinyl LabelsEmedco part number SQS116 text to include: 25 Emedco part number SQS9 text to include: 26 Emedco part number SQ3784 text to include: 35 CAUTIONDANGERWARNINGTHIS EQUIPMENTIS SUPPLIED BYMORE THAN ONEPOWER SOURCE480 VOLTSARC FLASH AND SHOCK HAZARDAPPROPRIATE PPE REQUIREDFAILURE TO COMPLY CAN RESULTIN DEATH OR INJURY.White background with 18 point black font, text to include: 27 PHASE MONITOR 28 TVSS 29 F1 F2 F3KTK-R-1/10 30 CB-TVSS 31 XFMR PRIMARY 32 XFMR SECONDARY 33 UPS 34 36 PS-1 37 PS-2 38 PS-3 39 PS-4 40 PS-5 42 LPC 44 CB-LPCDCF-A3 49 DCF-R 50 DCF-PLC 51 DCF-FLD 52 AREA LIGHTWhite background with black font, text to include: (label to include fuse name, type and size) 45 53 DCF-A0 46 DCF–SS1 54 TYPE SIZETYPE SIZEDCF- A1 47 DCF–SS2 55 TYPE SIZETYPE SIZEWhite background with 18 point black font, text to include: 58 CR-5–PULSE 67 CR-6 77 CR-16DCF- A2 48 DCF–SS3 57 TYPE SIZETYPE SIZETYPE SIZETYPE SIZETYPE SIZETYPE SIZEDCF–F7TYPE SIZESPARETYPE SIZE{Mount on back plate} 59 TD-1 60 TD-2 61 TD-3 63 CR-1 64 CR-2 65 CR-3 66 CR-4 68 CR-7 69 CR-8 72 CR-11 73 CR-12 74 CR-13 75 CR-14 76 CR-15ACF–FM 82 ACF–P2 83 ACF–AC1 84 ACF–IS1 85 CB2 96 98 LITTLE JOHN 99 White background with black font, text to include: (label to include fuse name, type and size) 78 86 ACF-PV 79 ACF–P4 87 TYPE SIZETYPE SIZEACF–P1TYPE SIZE 80 ACF-LC 81 94 TYPE SIZETYPE SIZETYPE SIZETYPE SIZETYPE SIZEACF–P3TYPE SIZEACF–P5TYPE SIZEWhite background with 18 point black font, text to include: 90 SEAL FAIL 1 91 SEAL FAIL 2 92 SEAL FAIL 3 100 SS-2 101 SS-3 102 AIR SCRUBBER 95 CB1K - 22CB3SS-108/2017

Vinyl LabelsWhite background with 24 point black font, text to include: 104 CONTROL CABINETFAN & HEATER 105 CHEMICAL FEEDSYSTEM 106 CONTROL CABINETGFCI RECEPTACLE 107 RPBA HEATTAPE 107 RPBA/AIR RELEASEHEAT TAPE 108 ISOLATION PEDESTALHEATER 109 PUMP PANEL 120 VACCONTROL POWER 110 UPS RECEPTACLE 111 OUTSIDE AREALIGHT 112 GENERATOR BATTERYCHARGER 113 GENERATOR BLOCKHEATERRed or yellow background with black 5/32” letters, text to include: 116 WARNING: To prevent ignition of flammables or combustibleatmospheres, disconnect power before servicing.This panel provides intrinsically safe circuit extensions for use inCLASS 1 GROUP D HAZARDOUS LOCATIONS when connected per(Control System Manufacturer) drawing package (number). 117 Apply red tape to the floor of the MAIN CONTROL CABINET to designate intrinsically safe area.(Only intrinsically safe circuits are allowed in this area. No conduit should be closer than 2” to the red line.)White background with 18 point black font, text to include: 118 HIGH BALL 119 PUMP 1 120 PUMP 2 121 PUMP 3 127 EMERGENCEYPOWERPUMP 3White background with black font, text to include: (Sized to fit) 123 PUMP 1 124 PUMP 2 125 128 LOAD BANK 129 BATTERY CHARGER 130 BLOCK HEATER 131 DISCONNECT IS IN THEMAIN CONTROL PANELThis document is supported by UL 898A, WAC 296 – 46B, 2014 NEC, NFPA 90, PSE and the Local Jurisdiction having Authority.It is the contractor’s responsibility to comply with all current codes.January 22, 2018K - 2308/2017

K - 2408/2017

K - 2508/2017

K - 2608/2017

K - 2708/2017

K - 2808/2017

K - 2908/2017

K - 3008/2017

K - 3108/2017

K - 3208/2017

RITTAL: 3239.110 Mount fan on lower right. VENT RITTAL: 3239.200 SS HOOD: RITTAL 3239.080 *Control System Manufacturing shall use listed parts and install them using the Special Construction Notes. Mount intake and exhaust hoods forward in the Main Control Cabinet toward the door, allowing clearance for the Service Entrance Disconnect. Filter