CODE ANALYSISPROJECT LOCATION: PUEBLO, COLORADO1365 Garden of the Gods Rd., Suite 130Colorado Springs, CO 80907 719.630.3350 www.bpce.comAPPLICABLE CODES:2015 IBC2015 IMC2015 IPC2015 IFGC2015 IECC2014 NEC2015 IFCEXISTING BUILDING:FIRST FLOOR:SECOND FLOOR:THIRD FLOOR:16,087 SF14,958 SF19,503 SFGENERAL INFORMATION:THE EXISTING BUILDING IS NOT FULLY SPRINKLED.THE SCOPE OF THIS PROJECT IS ONLY TO UPGRADETHE HVAC SYSTEMS AS THEY APPLY TO THEEXISTING BUILDING SPACES. THE FUNCTION OFBUILDING SPACES REMAINS UNCHANGED. NOARCHITECTURAL MODIFICATIONS TO ROOM LAYOUTSOR FUNCTIONS ARE INTENDED AS PART OF THISPROJECT.CSU PUEBLO - ADMINISTRATION DATACENTER COOLING UPGRADE2200 BONFORTE BOULEVARDPUEBLO, CO 81001ADMINISTRATION #111 DATACENTER COOLING UPGRADECONSTRUCTIONDOCUMENTSJULY 31, 20182200 BONFORTE BOULEVARD PUEBLO, CO 81001CSU-PUEBLO PROJECT NUMBER P-14013Project Sheet ListSheetNumberSheet TitleG-001COVER SHEETG-002GENERAL CONSTRUCTION NOTESG-101LEVEL 1 ARCHITECTURAL PLANG-102LEVEL 2 ARCHITECTURAL PLANG-103LEVEL 3 ARCHITECTURAL PLANP-001PLUMBING LEGENDPD-101PLUMBING DEMOLITIONPL-101PLUMBING WASTE & VENT PLANM-001MECHANICAL LEGENDMD-101MECHANICAL DEMOLITION PLANMP-101LEVEL 1 MECHANICAL PIPING PLANMP-102LEVEL 2 MECHANICAL PIPING PLANMP-103LEVEL 3 MECHANICAL PIPING PLANM-701MECHANICAL SCHEDULESE-001ELECTRICAL LEGENDED-101ELECTRICAL DEMOLITIONEP-101ELECTRICAL POWER PLANE-501ELECTRICAL DETAILSE-601ELECTRICAL ONE-LINE DIAGRAM - EXISTINGE-602ELECTRICAL ONE-LINE DIAGRAM - NEWE-701ELECTRICAL SCHEDULESCOVERSHEETG-001

1365 Garden of the Gods Rd., Suite 130Colorado Springs, CO 80907 719.630.3350 www.bpce.comCSU PUEBLO - ADMINISTRATION DATACENTER COOLING UPGRADE2200 BONFORTE BOULEVARDPUEBLO, CO 81001CONSTRUCTIONDOCUMENTSJULY 31, 2018GENERAL CONSTRUCTIONNOTESG-002

SHEET KEYED NOTES1.COORDINATE EQUIPMENT MOVE INDICATED IN PHASE 1 WITHCSU PUEBLO IT PERSONNEL. COORDINATE EQUIPMENTSHUTDOWN WITH OWNER'S REPRESENTATIVE AND COMPLYWITH THEIR REQUIREMENTS.2.EXISTING DATA CENTER EQUIPMENT SHALL REMAIN.3.REMOVE PORTION OF ACCESS FLOOR AS SHOWN.GENERAL NOTESA.B.REPLACE PORTION OF ACCESS FLOOR SYSTEM NOT REQUIREDTO REMAIN IN PLACE BECAUSE OF EXISTING EQUIPMENT ANDCASEWORK TO REMAIN WITH NEW ACCESS FLOOR SYSTEM.REPLACE SUPPORT PEDESTALS AT EDGE OF ACCESS FLOORSYSTEM TO REMAIN WITH NEW PEDESTALS. SHORE UPEXISTING FLOOR WHILE PEDESTALS ARE BEING REPLACED.CLEAN EDGE OF EXISTING FLOOR PANELS TO REMAIN TOALLOW FOR TIGHT FIT TO NEW PANELS. CUT OPENINGS IN NEWFLOOR TILES AT FLOOR PENETRATIONS. FIELD VERIFYLOCATIONS OF FLOOR PENETRATIONS.1365 Garden of the Gods Rd., Suite 130Colorado Springs, CO 80907 719.630.3350 www.bpce.comTHE MAIN POINT OF CONTACT FOR FLOORING SYSTEMMODIFICATIONS SHALL BE THE FOLLOWING:JUSTON VOGTCRITICAL FACILITIES TECHNOLOGY6380 West 54th AvenueSuite 100Arvada, CO 80002jvogt@cftrm.com(303) 944-7578C.NEW FLOORING SYSTEMS SHALL BE INSTALLED IN THREEPHASES.a. PHASE 1 - TO INCLUDE OPEN AREAS, UNDER CASEWORK,UNDER EXISTING SOUTH CABINETS.b. PHASE 2 - TO INCLUDE UNDER RACK ROW #1.c. PHASE 3 - TO INCLUDE AT EXISTING CRAC UNIT AND UNDERFIRE PROTECTION TANKS.D.PNL L1BNEW RAISED FLOORING SHALL BE AS MANUFACTURED BYHAWORTH.a. FLOOR PANELS SHALL BE 1” THICK, CONCRETE FILLEDWITH 1/16” LAMINATE.b. FLOORING INSTALLATION SHALL BE LOAD RATED FOR 1,500POUNDS.103 B118Lc. FLOORING SYSTEM SHALL BE STATIC DISSIPATIVE.MEN'SRESTROOMUP114118 K115118 JXFMRlocationd. FLOORING SYSTEM SHALL UTILIZE A STRINGER SYSTEM.111 P111 M111 NMECH112111 C111 B111UP2200 BONFORTE BOULEVARDPUEBLO, CO 81001f. PEDESTALS SHALL BE 18” HIGH.E.RAISED FLOORING SYSTEM SHALL BE PROVIDED BY THEFOLLOWING:KRIS KREFT - OPERATIONS MANAGERBettinger West Interiors1865 West Union Avenue111 S116PHASE 23PHASE 32116 A111 K111 J111 EF.Bettinger West Interiors SHALL BE RESPONSIBLE FOR ALLDEMOLITION OF THE EXISTING RAISED FLOORING SYSTEM.DEMOLITION SHALL BE COORDINATED WITH CRITICAL FACILITIESTECHNOLOGY.G.Bettinger West Interiors SHALL BE RESPONSIBLE FOR ALL RAISEDFLOORING SYSTEM CUTOUTS FOR UTILITIES AND EXISTINGPENETRATIONS.H.SELECTED PIECES OF EXISTING EQUIPMENT TO BE LIFTED BYCRITICAL FACILITIES TECHNOLOGY SUBCONTRACTOR FORINSTALLATION OF NEW FLOORING SYSTEM. EQUIPMENT TOREMAIN OPERATIONAL DURING LIFTING PROCESS. ANYEQUIPMENT ATTACHED TO EXISTING FLOORING SHALL BEDISCONNECTED AND RE-CONNECTED BY CRITICAL FACILITIESTECHNOLOGY.I.THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FORREMOVING AND RE-INSTALLING THE EXISTING CASEWORK FORFLOORING INSTALLATION. COORDINATE WITH CRITICALFACILITIES TECHNOLOGY.J.THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FORREMOVING THE EXISTING COVE BASE AND PROVIDING NEWRUBBER COVE BASE. COORDINATE TYPE AND COLOR WITHOWNER.K.WESTERN STATES SHALL BE RESPONSIBLE FOR THE REMOVALAND RE-INSTALLATION OF EXISTING FIRE PROTECTION TANKSFOR NEW FLOORING INSTALLATION. COORDINATE WITHCRITICAL FACILITIES TECHNOLOGY.L.THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FORREMOVING ANY EXISTING AIR BARRIERS UNDER THE RAISEDFLOOR.M.THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FORGENERAL CLEANING AND VACUUMING OF FLOOR BELOW RAISEDFLOOR.N.ANY OUTAGE TIME SHALL BE CLOSELY COORDINATED WITHCRITICAL FACILITIES TECHNOLOGY AND COLORADO STATEUNIVERSITY - PUEBLO.O.ALL DEMOLISHED FLOOR PEDESTALS ARE TO BE REMOVEDFROM THE SITE BY THE GENERAL CONTRACTOR.P.ALL EXISTING LIKE KIND FLOOR TILES ARE TO BE SALVAGED TOCSU. ALL OTHERS ARE TO BE REMOVED FROM THE SITE BY THEGENERAL CONTRACTOR.Q.PROVIDE .125" THICK, 4" COVE RUBBER BASE WITH MATTEFINISH. COLOR TO MATCH BASE BEING REMOVED. BASE TO BEFROM ROLL STOCK NOT SECTIONS. DO NOT INSTALL ANY BASESHORTER THAN 24". PROVIDE PREMOLDED EXTERNALCORNERS. INTERNAL CORNERS MAY BE JOB FORMED. INSTALLEDGE/TRANSITION STRIP AT ANY UNPROTECTED OR EXPOSEDFLOOR EDGES WHERE FLOORING TERMINATES ORTRANSITIONS.111 GPHASE 132118C1173111 F111 RDATACENTER118 A118 BSheridan, CO 80110.BETTINGER WEST INTERIORS SHALL BE CONTRACTED TOCRITICAL FACILITIES TECHNOLOGY.1118 FUnit A111 DWOMEN'SRESTROOM104SCOPE OF WORKA1011022A10210118 De. FLOORING SYSTEM SHALL BE GROUNDED AT A MINIMUM OFFOUR LOCATIONS.CSU PUEBLO - ADMINISTRATION DATACENTER COOLING UPGRADE101LEVEL 1 ARCHITECTURAL PLAN1/8" 1'-0"04'8'SCALE: 1/8" 1'-0"16'CONSTRUCTIONDOCUMENTSJULY 31, 2018LEVEL 1 ARCHITECTURALPLANG-101

GENERAL NOTESA.PROVIDE .125" THICK, 4" COVE RUBBER BASE WITH MATTEFINISH. COLOR TO MATCH BASE BEING REMOVED. BASE TO BEFROM ROLL STOCK NOT SECTIONS. DO NOT INSTALL ANY BASESHORTER THAN 24". PROVIDE PREMOLDED EXTERNALCORNERS. INTERNAL CORNERS MAY BE JOB FORMED. INSTALLEDGE/TRANSITION STRIP AT ANY UNPROTECTED OR EXPOSEDFLOOR EDGES WHERE FLOORING TERMINATES ORTRANSITIONS.1365 Garden of the Gods Rd., Suite 130Colorado Springs, CO 80907 719.630.3350 www.bpce.comSHEET KEYED NOTES1.5/8" GYP. BD. ON 3-1/2" 25 GA. METAL STUDS AT 16" OC W/ASSOCIATED TOP AND BOTTOM TRACKS.212 E212CSU PUEBLO - ADMINISTRATION DATACENTER COOLING UPGRADE205201 C2200 BONFORTE BOULEVARDPUEBLO, CO 81001212G210D212 J212206201 D210C212 H213210B1209 D210 A207 B201207207 C207 D209209 CCONSTRUCTIONDOCUMENTS209 AJULY 31, 2018209 B201 ALEVEL 2 ARCHITECTURALPLANLEVEL 2 ARCHITECTURAL PLAN1/8" 1'-0"04'8'SCALE: 1/8" 1'-0"16'G-102

GENERAL NOTESA.PROVIDE .125" THICK, 4" COVE RUBBER BASE WITH MATTEFINISH. COLOR TO MATCH BASE BEING REMOVED. BASE TO BEFROM ROLL STOCK NOT SECTIONS. DO NOT INSTALL ANY BASESHORTER THAN 24". PROVIDE PREMOLDED EXTERNALCORNERS. INTERNAL CORNERS MAY BE JOB FORMED. INSTALLEDGE/TRANSITION STRIP AT ANY UNPROTECTED OR EXPOSEDFLOOR EDGES WHERE FLOORING TERMINATES ORTRANSITIONS.1365 Garden of the Gods Rd., Suite 130Colorado Springs, CO 80907 719.630.3350 www.bpce.comSHEET KEYED NOTES1.314315315 A303 ACSU PUEBLO - ADMINISTRATION DATACENTER COOLING UPGRADE310 C3105/8" GYP. BD. ON 3-1/2" 25 GA. METAL STUDS AT 16" OC W/ASSOCIATED TOP AND BOTTOM TRACKS.2200 BONFORTE BOULEVARDPUEBLO, CO 81001302B310 D0310 A31301 I316CONSTRUCTIONDOCUMENTS3181301 H324 A301 K325323322319324320 A320 D0C323 A301 J325 BJULY 31, 2018320325 A320 B32301 F316 A301 E313324 B319 ALEVEL 3 ARCHITECTURALPLANLEVEL 3 ARCHITECTURAL PLAN1/8" 1'-0"04'8'SCALE: 1/8" 1'-0"16'G-103

PLUMBING SYMBOL LEGENDVALVE SYMBOLSMEDICAL GAS SYMBOLSSECTION SYMBOLPIPING SYMBOLS1365 Garden of the Gods Rd., Suite 130Colorado Springs, CO 80907 719.630.3350 www.bpce.comDETAIL SYMBOLSECTION, ELEVATION, AND DETAIL TITLESPROCESS GASESCSU PUEBLO - ADMINISTRATION DATACENTER COOLING UPGRADEFIXTURE & EQUIPMENT SYMBOLSCHEMATIC SYMBOLSSITE UTILITY SYMBOLSABBREVIATIONS2200 BONFORTE BOULEVARDPUEBLO, CO 81001CONSTRUCTIONDOCUMENTSJULY 31, 2018PLUMBING LEGENDNOTE: NOT ALL ABBREVIATIONS OR SYMBOLS APPLY TO THIS PROJECTP-001

GENERAL NOTES1.THE CONTRACTOR SHALL COORDINATE THE SHUTDOWN OFEXISTING BUILDING SERVICES FOR NEW CONNECTIONS WITHOWNER'S AUTHORIZED REPRESENTATIVE, AND SHALLCONFORM TO THEIR REQUIREMENTS.2.THESE DRAWINGS REFLECT INFORMATION ON EXISTINGBUILDING SERVICES GATHERED BY SITE INSPECTION,DISCUSSIONS WITH MAINTENANCE PERSONNEL, AND PREVIOUSCONSTRUCTION DRAWINGS. IT IS POSSIBLE THAT THE EXACTLOCATION, ARRANGEMENT, AND SIZES OF DUCTWORK AND PIPELINES IN THE EXISTING BUILDING MAY BE DIFFERENT FROMTHAT SHOWN ON THESE DRAWINGS. CONTRACTOR ISCAUTIONED TO INVESTIGATE EXISTING BUILDING CONDITIONSPRIOR TO SUBMITTING THEIR BIDS AND PERFORM ALLREQUIRED FIELD MEASUREMENTS PRIOR TO FABRICATING NEWDUCTWORK, PIPING, AND OTHER COMPONENTS AND DEVICES.1365 Garden of the Gods Rd., Suite 130Colorado Springs, CO 80907 719.630.3350 www.bpce.comSHEET KEYED NOTES1.REMOVE COMPLETE CONDENSATE DRAIN SYSTEM FROMEXISTING CRAC UNIT TO BE REMOVED.CSU PUEBLO - ADMINISTRATION DATACENTER COOLING UPGRADE2200 BONFORTE BOULEVARDPUEBLO, CO 81001109108107CONSTRUCTIONDOCUMENTSPNL L1BJULY 31, 2018MEN'SRESTROOM114115XFMRlocation111 P111 B111 MUP111111 NMECH112111 C111 DWOMEN'SRESTROOM111 E111 F111 S116111 R1(D)117116 A111 KDATACENTER111 G111 JPLUMBING DEMOLITIONPLUMBING DEMOLITION1/8" 1'-0"04'8'SCALE: 1/8" 1'-0"16'PD-101

PLUMBING FIXTURE SPECIFICATIONSP1SHEET KEYED NOTESNON FREEZE WALL HYDRANTTYPE:MFG:AUTOMATIC DRAINING, BRASS BODY VALVE, FREEZE-PROOF, INTEGRAL VACUUM BREAKER,CHROME PLATED BOX AND DOOR WITH LOOSE KEY, 3/4" INLET AND 3/4" GARDEN HOSE OUTLET,VERIFY WALL THICKNESS BEFORE OPENING.1.CONNECT 3/4" CONDENSATE DRAIN TO DISCHARGE OFEQUIPMENT'S INTEGRAL CONDENSATE PUMP, ROUTE UP ASHIGH AS POSSIBLE IN CEILING SPACE AND THEN AS SHOWN.2.ROUTE 1" CONDENSATE DRAIN ADJACENT TO EXISTING AIRHANDLER CONDENSATE DRAIN TO REDUCE IMPACT TO ACCESS.ROUTE DOWN TO FLOOR DRAIN AND SPILL OPEN INTO FLOORDRAIN IN MECHANICAL ROOM. CONTRACTOR TO FIELD VERIFYEXACT LOCATION AND REQUIREMENTS.WOODFORD NO. B65305B306 AGENERAL NOTES3.FIRE PROTECTION CONTRACTOR SHALL REMOVE AND REPLACEFM-200 SYSTEM.4.CONNECT NEW 3/4" DCW TO EXISTING 3/4" MAIN, PROVIDESHUT-OFF VALVE, AND ROUTE AS SHOWN. ROUTE UP INTOMECHANICAL PENTHOUSE AND CONNECT TO P1.5.MECHANICAL EQUIPMENT SHOWN FOR REFERENCE ONLY,REFER TO MECHANICAL SHEETS.6.INSTALL P1 IN PENTHOUSE WALL ABOVE INTAKE LOUVERS,MINIMUM OF 3'-0" ABOVE FINISHED ROOF LEVEL, FIELD VERIFYEXACT LOCATION. COORDINATE LENGTH OF NON-FREEZE WALLHYDRANT STEM WITH THICKNESS OF MECHANICAL PENTHOUSEWALL PRIOR TO ORDERING OR COMMENCING ANY WORK.7.DASHED LINE INDICATES APPROXIMATE LOCATION OFMECHANICAL PENTHOUSE WALLS ABOVE, FIELD VERIFY.8.COORDINATE LOCATION OF P1 SUCH THAT A 50'-0" HOSE WILLREACH ALL SIDES OF ALL NEW MECHANICAL EQUIPMENT ONROOF.306 B306 D1.THE CONTRACTOR SHALL COORDINATE THE SHUTDOWN OFEXISTING BUILDING SERVICES FOR NEW CONNECTIONS WITHOWNER'S AUTHORIZED REPRESENTATIVE, AND SHALLCONFORM TO THEIR REQUIREMENTS.2.THESE DRAWINGS REFLECT INFORMATION ON EXISTINGBUILDING SERVICES GATHERED BY SITE INSPECTION,DISCUSSIONS WITH MAINTENANCE PERSONNEL, AND PREVIOUSCONSTRUCTION DRAWINGS. IT IS POSSIBLE THAT THE EXACTLOCATION, ARRANGEMENT, AND SIZES OF DUCTWORK AND PIPELINES IN THE EXISTING BUILDING MAY BE DIFFERENT FROMTHAT SHOWN ON THESE DRAWINGS. CONTRACTOR ISCAUTIONED TO INVESTIGATE EXISTING BUILDING CONDITIONSPRIOR TO SUBMITTING THEIR BIDS AND PERFORM ALLREQUIRED FIELD MEASUREMENTS PRIOR TO FABRICATING NEWDUCTWORK, PIPING, AND OTHER COMPONENTS AND DEVICES.309309 B309 A306 E309 A109108306306 C309 C309307CONSTRUCTIONDOCUMENTSPNL L1B314313CO2CRAC-11" CND116CO111 FCRAC-2116 A111 K111 J1CO5DATACENTER111 R(E) 3/4" DCW4324 A3/4" CND1171(E) 3/4" DCW35310 A5111 E111 SCU-1 5(ON ROOF)63/4" DCW111 D1" CNDP1316MECH112111323JULY 31, 2018310 D5CU-2(ON ROOF)318OU-1(ON ROOF)50'-0"58322320319111 G324320 AIU-1323 A320 D324 BC111 NUP3107320111 M111 C310 D310 C331010 BB111 B315WOMEN'SRESTROOM111 P316 A115XFMRlocation315 AMEN'SRESTROOM114CSU PUEBLO - ADMINISTRATION DATACENTER COOLING UPGRADE2200 BONFORTE BOULEVARDPUEBLO, CO 81001306 F1071365 Garden of the Gods Rd., Suite 130Colorado Springs, CO 80907 719.630.3350 www.bpce.com320 B319 APLUMBING PLANSPLUMBING FIRST FLOOR WASTE & VENT PLAN1/8" 1'-0"PLUMBING THIRD FLOOR PRESSURE PIPING PLAN04'8'SCALE: 1/8" 1'-0"16'1/8" 1'-0"04'8'SCALE: 1/8" 1'-0"16'PL-101

MECHANICAL SYMBOL LEGENDDUCTWORK SYMBOLSVALVE SYMBOLSFITTING SYMBOLS1365 Garden of the Gods Rd., Suite 130Colorado Springs, CO 80907 719.630.3350 www.bpce.comAPPSPSCSU PUEBLO - ADMINISTRATION DATACENTER COOLING UPGRADE2200 BONFORTE BOULEVARDPUEBLO, CO 81001FPSTSCONSTRUCTIONDOCUMENTSJULY 31, 2018PIPING SYMBOLSSECTION SYMBOLDETAIL SYMBOLSECTION AND DETAIL TITLESEQUIPMENT SYMBOLSMECHANICAL LEGENDNOTE: NOT ALL ABBREVIATIONS ORSYMBOLS APPLY TO THIS PROJECTM-001

GENERAL NOTES105103 G118LUP114118 K115XFMRlocation111 P1365 Garden of the Gods Rd., Suite 130Colorado Springs, CO 80907 719.630.3350 www.bpce.com1.REMOVE EXISTING CRAC UNIT AND ALL ASSOCIATEDCONTROLS, REFRIGERANT PIPING, ACCESSORIES, ETC. PATCHHOLES IN WALLS, CEILINGS, AND FLOORS TO MATCH EXISTINGCONDITIONS. FIRESTOP ALL HOLES IN RATED ASSEMBLIES.2.REMOVE EXISTING CONDENSING UNIT AND ALL ASSOCIATEDCONTROLS, REFRIGERANT PIPING, ACCESSORIES, ETC. PATCHHOLES IN WALLS, CEILINGS, AND FLOORS TO MATCH EXISTINGCONDITIONS. FIRESTOP ALL HOLES IN RATED ASSEMBLIES.CSU PUEBLO - ADMINISTRATION DATACENTER COOLING UPGRADE2200 BONFORTE BOULEVARDPUEBLO, CO 81001111 DWOMEN'SRESTROOM104THESE DRAWINGS REFLECT INFORMATION ON EXISTINGBUILDING SERVICES GATHERED BY SITE INSPECTION,DISCUSSIONS WITH MAINTENANCE PERSONNEL, AND PREVIOUSCONSTRUCTION DRAWINGS. IT IS POSSIBLE THAT THE EXACTLOCATION, ARRANGEMENT, AND SIZES OF DUCTWORK AND PIPELINES IN THE EXISTING BUILDING MAY BE DIFFERENT FROMTHAT SHOWN ON THESE DRAWINGS. CONTRACTOR ISCAUTIONED TO INVESTIGATE EXISTING BUILDING CONDITIONSPRIOR TO SUBMITTING THEIR BIDS AND PERFORM ALLREQUIRED FIELD MEASUREMENTS PRIOR TO FABRICATING NEWDUCTWORK, PIPING, AND OTHER COMPONENTS AND DEVICES.UP111111 NMECH112111 C111 B111 M2.SHEET KEYED NOTESPNL L1BMEN'SRESTROOMTHE CONTRACTOR SHALL COORDINATE THE SHUTDOWN OFEXISTING BUILDING SERVICES FOR NEW CONNECTIONS WITHOWNER'S AUTHORIZED REPRESENTATIVE, AND SHALLCONFORM TO THEIR REQUIREMENTS.1091081071.111 E111 F111 S116111 R118 A1(D)116 A111 KDATACENTER111 G111 JJULY 31, 2018A117101102A118 BCONSTRUCTIONDOCUMENTS1012(D)MECHANICAL DEMOLITIONPLANMECHANICAL DEMOLITION PLAN1/8" 1'-0"04'8'SCALE: 1/8" 1'-0"16'MD-101

GENERAL NOTES105103 G103 HPNL L1B118L103 BMEN'S RESTROOMXFMRlocation114118 K111 M111 NMECH112115118 J111 P111 B111 CUP111111 D111 S111 E4.FIRESTOP ALL PIPE PENETRATIONS OF RATED WALLS ANDFLOORS.1.5/8" RL AND 7/8" RS FROM CRAC-1 UP TO FLOOR ABOVE,PENETRATE 2ND LEVEL FLOOR SLAB IN VOID SPACE BETWEENSTRUCTURAL RIBS. REFER TO MP-102 FOR LEVEL 2STRUCTURAL FRAMING.2.5/8" RL AND 7/8" RS FROM CRAC-2 UP TO FLOOR ABOVE,PENETRATE 2ND LEVEL FLOOR SLAB IN VOID SPACE BETWEENSTRUCTURAL RIBS. REFER TO MP-102 FOR LEVEL 2STRUCTURAL FRAMING.3.3/8" RL AND 5/8" RS FROM IU-3 UP TO FLOOR ABOVE, PENETRATE2ND LEVEL FLOOR SLAB IN VOID SPACE BETWEEN STRUCTURALRIBS. REFER TO MP-102 FOR LEVEL 2 STRUCTURAL FRAMING.CSU PUEBLO - ADMINISTRATION DATACENTER COOLING UPGRADECONSTRUCTIONDOCUMENTS5/8" RL7/8" RS116CRAC-23/8" RL5/8" RS118 B116 AC117111 K111 J111 RDATA CENTER111 GJULY 31, 20188IU-111A1011022A10210118 DINSTALL REFRIGERANT PIPING IN ACCORDANCE WITHMANUFACTURER'S INSTALLATION INSTRUCTIONS.3CRAC-1118 A3.1365 Garden of the Gods Rd., Suite 130Colorado Springs, CO 80907 719.630.3350 www.bpce.com21111 F118 FTHESE DRAWINGS REFLECT INFORMATION ON EXISTINGBUILDING SERVICES GATHERED BY SITE INSPECTION,DISCUSSIONS WITH MAINTENANCE PERSONNEL, AND PREVIOUSCONSTRUCTION DRAWINGS. IT IS POSSIBLE THAT THE EXACTLOCATION, ARRANGEMENT, AND SIZES OF DUCTWORK AND PIPELINES IN THE EXISTING BUILDING MAY BE DIFFERENT FROMTHAT SHOWN ON THESE DRAWINGS. CONTRACTOR ISCAUTIONED TO INVESTIGATE EXISTING BUILDING CONDITIONSPRIOR TO SUBMITTING THEIR BIDS AND PERFORM ALLREQUIRED FIELD MEASUREMENTS PRIOR TO FABRICATING NEWDUCTWORK, PIPING, AND OTHER COMPONENTS AND DEVICES.32200 BONFORTE BOULEVARDPUEBLO, CO 81001WOMEN'S RESTROOM1042.SHEET KEYED NOTESPNL T1A,"TEP"UPTHE CONTRACTOR SHALL COORDINATE THE SHUTDOWN OFEXISTING BUILDING SERVICES FOR NEW CONNECTIONS WITHOWNER'S AUTHORIZED REPRESENTATIVE, AND SHALLCONFORM TO THEIR REQUIREMENTS.1091081071.101LEVEL 1 MECHANICAL PIPINGPLANLEVEL 1 MECHANICAL PIPING PLAN1/8" 1'-0"04'8'SCALE: 1/8" 1'-0"16'MP-101

GENERAL NOTES204A202 D202 C203212 A212 B211 A212 D212 C1.THE CONTRACTOR SHALL COORDINATE THE SHUTDOWN OFEXISTING BUILDING SERVICES FOR NEW CONNECTIONS WITHOWNER'S AUTHORIZED REPRESENTATIVE, AND SHALLCONFORM TO THEIR REQUIREMENTS.2.THESE DRAWINGS REFLECT INFORMATION ON EXISTINGBUILDING SERVICES GATHERED BY SITE INSPECTION,DISCUSSIONS WITH MAINTENANCE PERSONNEL, AND PREVIOUSCONSTRUCTION DRAWINGS. IT IS POSSIBLE THAT THE EXACTLOCATION, ARRANGEMENT, AND SIZES OF DUCTWORK AND PIPELINES IN THE EXISTING BUILDING MAY BE DIFFERENT FROMTHAT SHOWN ON THESE DRAWINGS. CONTRACTOR ISCAUTIONED TO INVESTIGATE EXISTING BUILDING CONDITIONSPRIOR TO SUBMITTING THEIR BIDS AND PERFORM ALLREQUIRED FIELD MEASUREMENTS PRIOR TO FABRICATING NEWDUCTWORK, PIPING, AND OTHER COMPONENTS AND DEVICES.33.INSTALL REFRIGERANT PIPING IN ACCORDANCE WITHMANUFACTURER'S INSTALLATION INSTRUCTIONS.4.FIRESTOP ALL PIPE PENETRATIONS OF RATED WALLS ANDFLOORS.1365 Garden of the Gods Rd., Suite 130Colorado Springs, CO 80907 719.630.3350 www.bpce.comSHEET KEYED NOTES204211NEED5/8" RL AND 7/8" RS FROM CRAC-1 UP FROM BELOW AND UP INCHASE TO FLOOR ABOVE. PENETRATE 3RD LEVEL FLOOR SLABIN VOID SPACE BETWEEN STRUCTURAL RIBS. REFER TO MP-103FOR LEVEL 3 STRUCTURAL FRAMING.2.5/8" RL AND 7/8" RS FROM CRAC-2 UP FROM BELOW AND UP INCHASE TO FLOOR ABOVE. PENETRATE 3RD LEVEL FLOOR SLABIN VOID SPACE BETWEEN STRUCTURAL RIBS. REFER TO MP-103FOR LEVEL 3 STRUCTURAL FRAMING.3.3/8" RL AND 5/8" RS FROM IU-1 UP FROM BELOW AND UP INCHASE TO FLOOR ABOVE. PENETRATE 3RD LEVEL FLOOR SLABIN VOID SPACE BETWEEN STRUCTURAL RIBS. REFER TO MP-103FOR LEVEL 3 STRUCTURAL FRAMING.212 E212201 C1.205212G210D212 JCSU PUEBLO - ADMINISTRATION DATACENTER COOLING UPGRADE2200 BONFORTE BOULEVARDPUEBLO, CO 81001212201 D206210C212 H21321210B209 D210 A207 B201207207 C207 D2093209 A209 CJULY 31, 2018209 BLEVEL 2 MECHANICALPIPING PLANLEVEL 2 MECHANICAL PIPING PLAN1/8" 1'-0"CONSTRUCTIONDOCUMENTS04'8'SCALE: 1/8" 1'-0"16'MP-102

GENERAL NOTES303 F304 B305B305 A306 A306 B306 DTHE CONTRACTOR SHALL COORDINATE THE SHUTDOWN OFEXISTING BUILDING SERVICES FOR NEW CONNECTIONS WITHOWNER'S AUTHORIZED REPRESENTATIVE, AND SHALLCONFORM TO THEIR REQUIREMENTS.2.THESE DRAWINGS REFLECT INFORMATION ON EXISTINGBUILDING SERVICES GATHERED BY SITE INSPECTION,DISCUSSIONS WITH MAINTENANCE PERSONNEL, AND PREVIOUSCONSTRUCTION DRAWINGS. IT IS POSSIBLE THAT THE EXACTLOCATION, ARRANGEMENT, AND SIZES OF DUCTWORK AND PIPELINES IN THE EXISTING BUILDING MAY BE DIFFERENT FROMTHAT SHOWN ON THESE DRAWINGS. CONTRACTOR ISCAUTIONED TO INVESTIGATE EXISTING BUILDING CONDITIONSPRIOR TO SUBMITTING THEIR BIDS AND PERFORM ALLREQUIRED FIELD MEASUREMENTS PRIOR TO FABRICATING NEWDUCTWORK, PIPING, AND OTHER COMPONENTS AND DEVICES.33.INSTALL REFRIGERANT PIPING IN ACCORDANCE WITHMANUFACTURER'S INSTALLATION INSTRUCTIONS.4.FIRESTOP ALL PIPE PENETRATIONS OF RATED WALLS ANDFLOORS.309309 B309 A306 E1.306 F309 A304 A305306306 C307SHEET KEYED NOTES309 C309314315315 A303 A310302CU-1(ON ROOF)310 B310 A56OU-1(ON ROOF)5/8" RL AND 7/8" RS FROM CRAC-1 UP FROM BELOW IN CHASE,OFFSET AS SHOWN IN LEVEL 3 CEILING SPACE, UP THROUGHROOF, AND CONNECT TO CU-1 ON ROOF.2.5/8" RL AND 7/8" RS FROM CRAC-2 UP FROM BELOW IN CHASE,OFFSET AS SHOWN IN LEVEL 3 CEILING SPACE, UP THROUGHROOF, AND CONNECT TO CU-2 ON ROOF.3.3/8" RL AND 5/8" RS FROM IU-1 UP FROM BELOW IN CHASE,OFFSET AS SHOWN IN LEVEL 3 CEILING SPACE, UP THROUGHROOF, AND CONNECT TO OU-1 ON ROOF.4.INSTALL NEW CONDENSING UNIT ON ROOF SKID. REFER TODETAIL 1/M7.01.5.SUPPORT PIPING ON ROOF. REFER TO SPECIFICATIONS ANDDETAIL 2/M7.01.6.ALL EXTERIOR PIPING INSULATION SHALL BE WRAPPED INALUMINUM JACKET PER SPECIFICATIONS.7.REFRIGERANT PIPING UP THROUGH ROOF. REFER TO 3/M7.01FOR PIPING THROUGH ROOF DETAIL.325323322CONSTRUCTIONDOCUMENTS321319JULY 31, 2018323 A325 A324 B320 D0C320 A301 J320 B319 ALEVEL 3 MECHANICALPIPING PLANLEVEL 3 MECHANICAL PIPING PLAN1/8" 1'-0"2200 BONFORTE BOULEVARDPUEBLO, CO 81001320324325 BCSU PUEBLO - ADMINISTRATION DATACENTER COOLING UPGRADE3185/8" RS3/8" RL7324 A4CU-2(ON ROOF)5/8" RL7/8" RS4301 H732301 E316316 A301 I301 K1.5313301 F310 D310 C1365 Garden of the Gods Rd., Suite 130Colorado Springs, CO 80907 719.630.3350 www.bpce.com04'8'SCALE: 1/8" 1'-0"16'MP-103

1365 Garden of the Gods Rd., Suite 130Colorado Springs, CO 80907 719.630.3350 www.bpce.comPIPE CLAMPROOF MOUNTED CONDENSINGUNIT.SEE PLANS FOR PIPE TYPE ANDSIZEDIRECT EXPANSION (DX) COIL ININ-ROW COOLING UNIT.TOP PIPINGROOF SUPPORT ASMANUFACTURED BY C-PORT, CB10,28" LONG OR EQUIVALENT. SEESPEC. FOR SPACING8" MIN.INVERTED P-TRAP.CSU PUEBLO - ADMINISTRATION DATACENTER COOLING UPGRADE2200 BONFORTE BOULEVARDPUEBLO, CO 81001S-TRAP.ROOFELEVATIONP-TRAP.CONDENSERHEAD PRESSURE CONTROLVALVE.CHECK VALVE.HOT GASPRESSURE RELIEF VALVE.ROOF PIPE SUPPORT DETAIL2 ABOVESCALE NONESECTIONCONSTRUCTIONDOCUMENTSSHUT OFF VALVES.PITCH IN DIRECTION OF FLOW.12" PER 10 FEET.JULY 31, 2018COUNTERFLASHING WITH FASTENERS 24" O.C.NOTEFIBER CANT STRIP. SET IN BITUMENSKID SHALL SPAN TWO BEAMS MINIMUM.LIQUIDLOCATE SKIDS FOR SECUREEQUIPMENT SUPPORT.SEE PLANS FOR PIPE SIZE.ROOF INSULATION. SEE ARCH. DWGS.INSTALL SKIDS PERPENDICULAR TOROOF BEAMS.RECEIVERMOP SKID IN PLACE WITH HOT ASPHALT TAR OR ASDIRECTED BY ARCH.ROOF. SEE ARCHITECTURAL DWGS.8"x8" TREATED REDWOOD SKIDFASTENERS AT 8" O.C.BLOCKING. ANCHOR SECURELY TO ROOF DECK,SAME THICKNESS AS ROOF INSULATION.SET SKIDS TO BE LEVEL WHEN INSTALLED ONSLOPING ROOF.BASE FLASHINGFIBER CANT STRIP- SET INBITUMEN.BASE FLASHINGFASTENERS APPROX. 8" O.C.20 GAUGE GALVANIZED SHEET METALCAPFASTENERS APPROX. 24" O.C.RDNOTES:A. ALL LINES SHALL BE TYPE L ACR TUBING IN COMPLIANCE WITHMANUFACTURER IOM.B. FURNISH FACTORY APPROVED SHOP DRAWINGS PRIOR TOINSTALLATION FOR OWNER AND ENGINEER REVIEW.C. TRAP THE VERTICAL DISCHARGE LINE AT EVERY FLOOR TOENSURE PROPER OIL RETURN.D. PIPE SIZING SHOULD CHANGE AFTER P-TRAP BASED ONMANUFACTURER RECOMMENDED PIPING CHARTS IN IOM.E. REFER TO SPECIFICATION 23 23 13 FOR ADDITIONALREQUIREMENTS.SLOPE PIPES AWAY FROM HOOD.SKID DETAIL1 ROOFSCALE NONESHEET METAL OR FLEX-TUBECOLLAR.COIL PIPING SCHEMATIC4 DXSCALE NONESHEET METAL HOOD.INSULATE INSIDE OF METALWORKIN COLD CLIMATES.THRU ROOF DETAIL3 PIPINGSCALE NONEMECHANICAL SCHEDULESAND DETAILSM-701

ELECTRICAL SYMBOL ACPFATCFMSGENGFIG OR WPXFERXFMR1, 2, 3, . . SUBFED PANELAMPS, AMPERE, AMPERAGEABOVE COUNTERALTERNATING CURRENTAMERICANS WITH DISABILITIES ACTABOVE FINISHED FLOORABOVE FINISHED GRADEAVAILABLE INTERRUPTING CURRENTALUMINUMAMERICAN NATIONAL STANDARDS INSTITUTEAUTOMATIC TRANSFER SWITCHAUDIO/VISUALAMERICAN WIRE GAUGECONDUITCIRCUIT BREAKERCLOSED CIRCUIT TELEVISIONCIRCUITCOPPERDIMMINGDIRECT CURRENTDAY-LIGHTINGDIAMETEREMERGENCYENGINE GENERATOREMERGENCY, LIFE SAFETYEMERGENCY, EQUIPMENTELECTRIC WATER COOLEREXISTINGFUTUREFIRE ALARMFIRE ALARM ANNUNCIATORFIRE ALARM CONTROL PANELFIRE ALARM TERMINAL CABINETFACILITY MANAGEMENT SYSTEMGENERATORGROUND FAULT INTERRUPTERGROUND FAULT CIRCUIT INTERRUPTERGROUND FAULT EQUIPMENT PROTECTIONGROUND FAULT ITUTE OF ELECTRICAL AND ELECTRONICSENGINEERSISOLATED GROUNDTHOUSAND CIRCULAR MILSKILOVOLTKILOVOLT AMPSKILOWATTKILOWATT HOUR.LONG TIME, SHORT TIME, INSTANTANEOUS,AND GROUND FAULT PROTECTIONMAXIMUMMOTOR CONTROL CENTERMINIMUMMANHOLEMANUAL TRANSFER SWITCHMEGAVOLT AMPSNOT APPLICABLENORMALLY CLOSEDNATIONAL ELECTRICAL CODENATIONAL ELECTRICAL MANUFACTURERSASSOCIATIONNEUTRALNATIONAL FIRE PROTECTION ASSOCIATIONNOT IN CONTRACTNORMALNORMALLY OPENOVERHEADPOLEPUBLIC ADDRESSPHOTOCELLPHASEPOWER MONITORING AND CONTROL SYSTEMREMOVED/REMOVALROOM CONTROLLERRIGID STEEL CONDUITSURGE PROTECTIVE DEVICESWITCHTEMPORARYTELEVISIONTRANSIENT VOLTAGE SURGE SUPPRESSERTYPICALUNDER COUNTERUNDERGROUNDUNDERGROUND ELECTRICUNDERWRITERS' LABORATORIESUNLESS OTHERWISE NOTEDUNINTERRUPTABLE POWER SUPPLYVOLTS, VOLTAGEVARIABLE FREQUENCY DRIVEWALL MOUNTEDWEATHERPROOF AND GFCIWEATHERPROOFTRANSFERTRANSFORMERREFERENCE TAGSSYMBOLDEFINITIONKEYED NOTE REFERENCEVAV-9 44"A, B, C, SEQUENCE OF PANELS OF THIS TYPE1, 2, 3, . . FLOOR LEVEL(SB SUB-BASEMENT, B BASEMENT, M MEZZANINE,P PENTHOUSE)T TRANSFORMERDB DISTRIBUTION BOARDMSB MAIN SWITCH BOARDMCC MOTOR CONTROL CENTERI ISOLATED PANELBOARDATS AUTOMATIC TRANSFER SWITCHPDU POWER DISTRIBUTION UNITUPS UNINTERRUPTABLE POWER SUPPLYB BUSWAYH HIGH VOLTAGE PANELBOARD (480Y/277V)L LOW VOLTAGE PANELBOARD (208Y/120V)BLANK FOR NORMAL POWERE EMERGENCYEL EMERGENCY-LIFE SAFETY-BRANCHEC EMERGENCY-CRITICAL-BRANCHEQ EMERGENCY-EQUIPMENT-BRANCHDENOTES MOUNTING HEIGHT AFFKITCHEN EQUIPMENT REFERENCE6E4E46AE3 E4E3 E4NORTHSECTION/ELEVATION LETTEROR DETAIL NUMBERDRAWING NUMBER WHEREDETAILEDSECTION/ELEVATION LETTEROR DETAIL NUMBERDRAWING NUMBER WHEREDETAILEDDRAWING NUMBER WHERETAKEN1" 40'-0"40'80' SCALE BAR ORMATCH ARCHITECT'SXXXXXPXPBRANCH CIRCUIT GENERAL INFORMATION:BRANCH CIRCUITS FROM OVERCURRENT PROTECTION (20A) TO FURTHEST DEVICESHALL NOT EXCEED 75 FEET FOR #12AWG COPPER AND 150 FEET FOR #10AWGCOPPER; MEASURED ALONG CONDUCTORS ROUTING PATH. BRANCH CIRCUITSEXCEEDING 150 FEET WILL BE SIZED SO THAT VOLTAGE DROP DOES NOT EXCEED 5%.SYMBOLDESCRIPTIONCONDUCTOR IDENTIFICATION SYMBOLS. REFER TOPLANS FOR COMBINATION USE. CONDUCTORIDENTIFICATION MOSTLY USED IN HOMERUNLOCATION, BUT CAN ALSO BE USED IN BRANCHCIRCUITING WHERE APPLIED. GROUNDCONDUCTORS WILL BE INSTALLED IN ALL RACEWAYSWHETHER SHOWN OR NOT. GROUND HOT/PHASE NEUTRAL SWITCH LEGLA-1,3LA-5,7,9LA-7LA-13XCEILING MOUNTED EMERGENCY DUPLEXRECEPTACLEXDOUBLE DUPLEX (QUADPLEX) RECEPTACLESPLIT DUPLEX RECEPTACLE. TOP HALF SWITCHEDWITH BOTTOM HALF CONTINUALLY HOT.EMERGENCY DOUBLE DUPLEX (QUADPLEX)RECEPTACLEXSPECIAL PURPOSE RECEPTACLE. NEMACONFIGURATION AND AMPERAGE AS NOTED ONPLANSTVSS RECEPTACLE/TV BOX COMBO PASS &SEYMOUR #TV1WTVSS*JCODE SIZE PULLBOX (OR AS SIZED ON PLAN)PPUSHBUTTON (EMERGENCY POWER OFF - EPO)WALLCEILINGCEILING30/3R30/1DATA RACEWAYVOICE/DATA COMBINATION RACEWAY30/3RFIRE ALARM RACEWAY0/1DESCRIPTION1/30/3RMAIN SWITCHBOARD. DASHED LINES INDICATE CLEARANCES.5UPS-ADOUBLE HEAD, POLE MOUNTED LUMINAIREXXDRY TYPE TRANSFORMER (15kVA OR ABOVE), WITH EQUIPMENT TAG(TAG INSIDE OR OUTSIDE, DEPENDING ON SIZE). IN MOST CASES,ACTUAL SIZE SHOWN ON PLANS (ELECTRICAL ROOMS).DRY TYPE TRANSFORMER (LESS THAN 15kVA), WITH NO EQUIPMENT TAG.SIZE, TYPE AND LOCATION NOTED ON PLANS.VARIABLE FREQUENCY DRIVEATS-1GGROUND BARDEMOLITIONSYMBOLREXDESCRIPTIONDASHED SYMBOL INDICATES EXISTINGDEVICE OR EQUIPMENT TO BE REMOVEDREMOVE EXISTING RACEWAY IN ALL ACCESSIBLEAREAS. CAPPED AND ABANDONED IF INUNACCESSIBLE AREASOLID SYMBOL, LIGHTER IN COLORINDICATES EXISTING DEVICE OR EQUIPMENTTO REMAINNOTESXXUTSX 60",UONWALLVARIESSEEPLANSVSVARIESSEEPLANSVS BFHORN NOTIFICATIONSSPEAKER NOTIFICATIONCCHIME NOTIFICATIONCOMBINATION SPEAKER AND CHIMENOTIFICATIONSPEAKER/HORN WITH STROBE LIGHTOSVARIESSEEPLANSDLVARIESSYMBOLTHERMOSTATWALL 44"UON300400ENCLOSED CIRCUIT BREAKER. AMPERAGE/ NEMAENCLOSURE RATING, 3 POLE UON 80"UONPHOTOELECTRIC SMOKE DETECTORIONIZATION SMOKE DETECTORIR/FCOMBINATION RATE OF RISE / FIXEDTEMPERATUREFFIXED TEMERATURE; TEMPERATURE ASNOTED ON PLANS OR SPECIFICATIONSCEILINGSURFACECEILINGOR WALLVARIESUNDERFLOORSEEPLANSATDUCTSEEPLANSRATE OF RISE ONLYBEAM TRANSMITTERBTBRUNDER FLOOR SMOKE DETECTOREXTERIORASDETAILEDDUCT DETECTORFIRE/SMOKE DAMPERPSPRESSURE SWITCHTSTAMPER SWITCHFSFLOW SWITCHPIVPOST INDICATOR VALVEWALL 44"UONMMAGNETIC DOOR HOLDERRCONTROL RELAYMONITOR MODULEMMNON-FUSED DISCONNECT SWITCH. AMPERAGE/NEMA ENCLOSURE RATING, 3 POLE UONFUSED DISCONNECT SWITCH. AMPERAGE/ NEMAENCLOSURE RATING, 3 POLE UONMOTOR STARTER. STARTER SIZE INDICATEDBY NUMBER/NEMA ENCLOSURE RATING,SINGLE SPEED UONCOMBINATION FUSIBLE DISCONNECT SWITCHAND MOTOR STARTER. NEMA STARTERSIZE/AMPERAGE/NEMA ENCLOSURE RATING, 3POLE UONMOTOR. NUMBER INDICATES HORSEPOWERRATING FOR 1HP AND LARGER300400DRAWOUT CIRCUIT BREAKERTRIP SETTINGFRAME SIZEMEDIUM VOLTAGE DRAWOUTCIRCUIT BREAKERTRIP SETTINGFRAME 300AOVERHEAD UTILITY AND OR SYSTEM DISTRIBUTION.3Ø THREE PHASE1Ø SINGLE PHASEP ELECTRICAL PRIMARYS ELECTRICAL SECONDARYT TELECOMMUNICATIONTV TELEVISIONE EMERGENCY POWERATSC AUTOMATIC TRANSFER SWITCH CONTROLN NEWEX EXISTINGUNDERGROUND UTILITY AND OR SYSTEM DISTRIBUTION.UTILITY OR FACILITY TRANSFORMERGFUSE. "300A" DENOTES AMPERAGERATINGGROUND FAULT PROTECTIONSHUNT TRIP OPERATORSTVARIESSEEPLANS2 PORT VOICE\DATA OUTLETWALL 18"UON2 PORT VOICE\DATA OUTLET, STUB A 1" CONDUIT6" INTO CEILING SPACEWALL 18"UONAC2 PORT VOICE\DATA OUTLET ABOVE COUNTER TOPWALL 44"UONWTELEPHONE OUTLET WALL MOUNTEDWALL 44"UONWALL 84"UONWALL 108UONWALLSEEP

d.new raised flooring shall be as manufactured by haworth. a.floor panels shall be 1" thick, concrete filled with 1/16" laminate. b.flooring installation shall be load rated for 1,500 pounds. c.flooring system shall be static dissipative. d.flooring system shall utilize a stringer system.