ASPFMulti-Position Air Handlerwith Energy-Saving Motor1½ to 5 TonsStandard Features Suitable for use with refrigerants R-410A and R-22 All-aluminum evaporator coil Check flowrater expansion device for cooling and heatpump applications EEM multi-speed motor Enhances the performance of yourGoodman brand air conditioner or heat pump Multi-position — upflow, downflow or horizontal Built-in coil has horizontal, vertical, and downflowdrain pans with secondary drain connections Complies with the Factory-Sealed Air HandlingCredit as listed in the 2001 Florida Building Code,Chapter 13, Section 610.2.A.2.1 AHRI Certified; ETL ListedCabinet Features Fully insulated, painted steel cabinet with attractiveArchitectural Gray finish Built-in filter rack for 1” filter (filter not included) Low-voltage cabinet connections Power supply on top Low-voltage entry on top or side Factory sealed to achieve 2% or less leakage rateat 1.0” water gauge external duct static pressure* Complete warranty details available from your local dealer or at www.goodmanmfg.com. To receive the 10-Year Parts Limited Warranty, online registration must becompleted within 60 days of installation. Online registration is not required inCalifornia or Québec.SS-GASPFwww.goodmanmfg.com5/11Supersedes 4/11

Product BrandASingle-pieceAir HandlerEngineering *Major/ Minor Revisions* Not used for inventory managementUnit ApplicationCCeiling Mount PSC MotorDDownflow PSC MotorEMulti-Position Variable-Speed MotorRMulti-Position PSC MotorSMulti-Position EEM MotorW Wall Mount PSC MotorCabinet FinishUUnpaintedPPaintedNUncasedExpansion DeviceFFlowraterTExpansion Valve2AA11,12Refrigerant ChargeNo Digit R-22 only6 R-410A or R-22Electrical1 208/240 V, 1 Phase, 60 HzNominal Capacity Range @ 13 SEERMulti-Position & Downflow Applications1729 1½ to 2½ Tons (for Export Systems)1830 1½-3½ Tons3642 3-3½ TonsCeiling Mount & Wall Mount Applications(Nominal Cooling Capacity/ Electric Heat kW)1805 1½ Tons Cooling/ 5 kW Electric Heat2405 2 Tons Cooling/ 5 kW Electric Heat3608 3 Tons Cooling/ 8 kW Electric Heatwww.goodmanmfg.comSS-GASPF

Product ASPF313716*ASPF426016*Cooling (BTU/h)18,000 - 30,00030,000 - 36,00030,000 - 36,00042,000 - 60,000CFM (High/ Low)1,085 / 6501,350 / 6001,350 / 6002,000 / ”10⅝”10⅝”10¹¹/₁₆”Coil Drain Connection ”Suction¾”⅞”⅞”⅞”208 / 230208 / 230208 / 230208 / 230Electric Heat Capacity (kW)5, 8, 103, 5, 6, 8, 10, 15, 20, 213, 5, 6, 8, 10, 15, 20, 2110, 15, 20, 21Min Circuit Ampacity3.6 / 3.63.8 / 3.83.9 / 3.96.6 / 6.615 / 15 amps15 / 15 amps15 / 15 amps15 / 15 amps197 / 253197 / 253197 / 253197 / 2532.9 / ½3.0 / ¾3.1 / ¾5.1 / ¾125176176195Nominal RatingsBlowerDiameterService ValveElectrical DataVoltageMax. Overcurrent DeviceMin. / Max VACBlower Motor FLA/ HPShip Weight (lbs)SS-GASPFwww.goodmanmfg.com3

Product odmanmfg.comSS-GASPF

Product SpecificationsAirflow 16*CFM deliverd against External Static PressureMotorSpeed Tap0.1”0.2”0.3”0.4”0.5”Low (T1)700670650595510Med-Low (T2)820785765745705Medium (T3)920900850840815Med-High (T4)1,0751,0551,015975960High (T5)1,1301,1151,0851,0401,000Low (T1)1,060865600515420Med-Low (T2)1,105910795745690Medium (T3)1,1651,0701,020960915Med-High (T4)1,2851,2401,1951,1401,100High (T5)1,4351,3951,3501,3151,265Low (T1)1,060865600515420Med-Low (T2)1,105910795745690Medium (T3)1,1651,0701,020960915Med-High (T4)1,2851,2401,1951,1401,100High (T5)1,4351,3951,3501,3151,265Low (T1)1,4451,2751,175940855Med-Low (T2)1,5451,4051,3251,2601,145Medium (T3)1,6601,6101,5551,4901,415Med-High (T4)1,9051,8701,8101,7501,695High (T5)2,1152,0702,0001,9651,915Notes: Assumes dry coil with filter in place; SCFM correction for wet coil 4% All ASPF models are shipped from the factory with the speed tap set on T4.SS-GASPFwww.goodmanmfg.com5

Product Specifications ASPF****B*/D* Wiring Diagram FLFLFLFLHTR2 TLFLHTR1 TLHTR1 TLBKRDHTR2 TLFLRDPLM11BKRDHTR3 TLFLPLMHTR3 TLBKBK2BKHTR2 TLFLHTR1 TLPLMBKHTR1 TLFLFLBK YLHTR4 7BK8BK E (1) ELEMENT ROWSL2L1TWO (2) ELEMENT ROWSL2L1L2THREE (3) ELEMENT ROWSL1L2L1L2FOUR (4) ELEMENT ROWSNOTE: WHEN INSTALLING HEATER KIT, ENSURE SPEED TAP DOES NOT EXCEED MINIMUM BLOWER SPEED (MBS) SPECIFIED FOR THE AIRHANDLER/HEATERKIT COMBINATION ON THIS UNIT'S S&R PLATE. AFTER INSTALLING OPTIONAL HEAT KIT, MARK AN "X" IN THEPROVIDED ABOVE.MARK ACCORDING TO NUMBER OF HEATER ELEMENT ROWS INSTALLED. NO MARK INDICATES NO HEAT KIT INSTALLED.TERMINAL BLOCK SHOWNFOR 50HZ MODELS ONLYSEE NOTE 2R C G W1 W2 Y1 Y2 O DH 1 2 3 4 5 L2L1EQUIPMENT GROUNDUSE COPPER OR ALUMINUM WIRE208/240 PLM 21 PLMEMRDGRBR1 PLFC L GNPLFSEENOTE 4WHBL123424V55SEE NOTE 1TR3RD2FUSEHOLDERWHPUCRBK 4RD2513RDC123524V4COLOR CODEBK BLACKGR GREENRD REDPU PURPLEYL YELLOW BR BROWNBL BLUEWH WHITEBLBLBL12345BLRDWH PUFUSEHOLDERCOPPER OR ALUMINUMPOWER SUPPLY(SEE RATING PLATE)USE MIN. 75 C FIELD WIREEMC L GNBKCOMPONENT CODEOR BR YL12345RDEMCR C G W1 W2 Y1 Y2 O DH 1 2 3 4 5240BLRD4 PLFSEE NOTE 1TRGR54CRRDBKWH621BLIF REPLACEMENT OF THE ORIGINAL WIRESSUPPLIED WITH THIS ASSEMBLY IS NECESSARY,USE WIRE THAT CONFORMS TO THENATIONAL ELECTRIC CODE.EMTBRCREBTDRWIRING CODEFACTORY WIRINGHIGH VOLTAGELOW VOLTAGEFIELD WIRINGHIGH VOLTAGELOW VOLTAGEEVAPORATOR MOTORTRTERMINAL BOARDPLFRELAYPLMFLCONTROL RELAYTLELECTRONIC BLOWER TIMEHTRDELAY RELAYTRANSFORMERFEMALE PLUG CONNECTORMALE PLUG CONNECTORFUSE LINKTHERMAL LIMITHEAT ELEMENTSNotes:1) Red wires to be on transformer terminal "3" for 240 volts and on terminal "2" for 208 volts.2) See composite wiring diagrams in installation instructionsfor proper low voltage wiring connections.3) Confirm speed tap selected is appropriate for application. If speed tap needsto be changed, connect purple wire from terminal 4 of CR relay to appropriate tapat TB4) Brown and white wires are used with Heat Kits only.0140A00037REV B Wiring is subject to change. Alwaysrefer to the wiring diagram or theunit for the most up-to-date wiring. WarningHigh Voltage: Disconnect all power before servicing or installing this unit. Multiple powersources may be present. Failure to do so may cause property damage, personal injury, or death. 6 www.goodmanmfg.com SS-GASPF

Product Specifications ASPF****C*/E* Wiring Diagram Warning Wiring is subject to change. Alwaysrefer to the wiring diagram or theunit for the most up-to-date wiring. High Voltage: Disconnect all power before servicing or installing this unit. Multiple powersources may be present. Failure to do so may cause property damage, personal injury, or death. SS-GASPF www.goodmanmfg.com7

Product SpecificationsAccessoriesHeat Kit SelectionSingle Point Kit **ASPF183016*XXXX¹X¹X²HKR-03*HKR-05*, HKR-05C*HKR-06*HKR-08*, HKR-08C*HKR-10*, HKR-10C*HKR-15C*HKR-20C*HKR-21C* HKR3-15* XXXX¹X¹ModelSPW-01HKR-15CHKR-20CHKR-21CXXX** Must be installed along with any of the abovecompatible heat kits. This kit will fit any ASPF airhandler as long as a compatible heat kit is installedin the unit.FiltersX¹X¹Revision level that may or may not be designatedCircuit breaker option Heat kit requires three-phase power supplyAir handler must be on speed tap 2, 3, 4, or 5Air handler must be on speed tap 4 or 5.ASPFFilter #QtyRequired183030364260FIL-36-42FIL 48-61FIL 48-61111Expansion Valve Kits for Air Conditioningand Heat Pump ApplicationsKit ant20% Bleed Valve20% Bleed ValveNon-bleed ValveNon-bleed ValveNon-bleed ValveNon-bleed ValveNon-bleed ValveNon-bleed ValveNon-bleed ValveNon-bleed ValveAC OnlyAC OnlyAC OnlyAC OnlyAC or HPAC or HPAC or HPAC or HPAC or HPAC or ain Pan Insulation KitsDownflow ApplicationsChassis SizeSmall (15½”)Medium (19½”)Large (22”)Tonnage:Outdoor Unit1½ - 3 Ton3½ - 5 Ton1½ - 3 Ton3½ - 5 Ton1½ - 2 Ton2½ - 3 Ton3½ - 5 Ton1½ - 2 Ton2½ - 3 Ton3½ - 5 TonHorizontal ApplicationsInsulation KitDPI18-30/20DPI36-42/20DPI48-60/20Note: Each kit contains enough material to modify 20 coilsChassis SizeSmall (15½”)Medium (19½”)Large (22”)Insulation KitDPIH18-32DPIH36-42DPIH48-61Note: Each kit contains enough material to modify 20 coilsGoodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs withoutnotice or without incurring obligations. 2010 Goodman Manufacturing Company, L.P. Houston, Texas Printed in the USA.8www.goodmanmfg.comSS-GASPF

All-aluminum evaporator coil Check flowrater expansion device for cooling and heat pump applications EEM multi-speed motor Enhances the performance of your Goodman brand air conditioner or heat pump Multi-position — upflow, downflow or horizontal Built-in coil has horizontal, vertical, and downflow