Hitachi Programmable Controller is a registered trademark of Hitachi, Ltd. Microsoft and Windows are either registered trademarks or trademarks of Microsoft Corporation in the United States and/or other countries. Other company and product names mentioned in this document may be the trademarks of their respective owners.Safety precautions To ensure the safe use of this product, read the following documents before using the product: the Read me, the Usage Guide, and the manual. Use this product in an environment that meets the requirements described in the catalog, the Usage Guide, and the manual. Do not use theproduct in an environment that is exposed to high temperature, high humidity, dust, corrosive gas, vibration, or shock. Failure to follow thisinstruction might result in fire, failure of the product, electric shock, or malfunction. For safety, the product must be installed and wired in accordance with the Usage Guide and the manual. Wiring must be performed by an expert inelectrical work, electrical wiring, etc. Measures must be taken to ensure that foreign objects do not get into the product. Restrictions (such as those pertaining to the purpose and location of use) apply to the some of the products mentioned in this catalog, and someproducts might require periodic inspections. For details, contact us or a Hitachi sales representative. This product is manufactured under strict quality controls. However, safety mechanisms must be installed to prevent serious accidents if theproduct is to be used in important equipment where a product failure might result in death, or in equipment where a product failure might lead tosignificant loss.Precautions for use This catalog gives an overview of the features of the product but does not include restrictions on the use of the product. Before using the product,read the Usage Guide and product manual to check the restrictions. Hitachi shall not be liable for any damages incurred for reasons that cannot be attributed to us; any damage to opportunity or loss of profits incurredby our customers due to the failure of this product; any damages arising out of special circumstances (foreseen or unforeseen); any secondarydamages, accident warranties, damage to products other than our products, or warranties for any other work. Use S10VE only for purposes where there is no risk of a serious accident occurring even if S10VE fails or malfunctions. In addition, in the event of afailure or malfunction, establish backup and fail-safe operations separate from S10VE. S10VE is a general-purpose product intended for use in general industries. It is not intended for use for special purposes that require strict safety,high reliability, or especially high quality. Hitachi shall not assume any liability if the product is used for special purposes.Special purposes include the following: Purposes that require strict safetyExamples: Power-generation control equipment (such as that for nuclear, thermal, or hydroelectric power), combustion equipment, air and spaceequipment, railway equipment, elevators and escalators, recreational equipment, medical equipment, safety equipment, on-board equipment, shipequipment, traffic signal equipment, and other equipment that might pose a danger to human life or physical safety Purposes that require high reliabilityExamples: Systems that supply gas, water, electricity, etc.; systems that operate continuously (24 hours a day); settlement systems; and otherpurposes related to the handling of rights and assets Purposes that require use of the product in harsh conditions or environmentsExamples: Outdoor environments, and environments susceptible to chemical contamination, electromagnetic interference, or constant vibrationand shock However, S10VE can be used even for the aforementioned purposes on the condition that the purpose of use is specifically limited, thecustomer assumes responsibility for ensuring redundancy, and especially high quality is not required. Please contact us for details. The specifications in this catalog may be changed without notice to improve the product. Due to printing conditions, the color of the product inthis catalog might differ from that of the actual product. In some cases, the LED displays in the images in this catalog might differ from the actual displays. All images in this catalog were taken for the purpose of the catalog and might differ from actual usage. If you plan to export this product, please check all foreign export-related laws and regulations, such as Japan’s Foreign Exchange and ForeignTrade Act and the U.S. Export Administration Regulations, and carry out all required procedures. If you have any questions, please contact aHitachi sales representative.For details and inquiries about products, refer to the following. Product site and web inquirieshttps://www.hitachi.com/s10/Industry & Distribution Business Unit, Hitachi, Ltd.PF-041022(4)2021.10Printed in Japan

Continued compatibility with the S10 series,with improved reliability, maintainability, andcomputing performance:A programmable controller that provides advancedsupport for manufacturing and social infrastructuresConnectivity: Ethernet and Controller-Level NetworkMaximum number of nodesEthernet :For PADT 5 nodesFL-net :2 nodesOD.RING:2 nodesComputerEthernet Improved reliability by way of a built-in function (error correction code) that automaticallycorrects soft errors Includes a single CPU module that runs programs coded in ladder logic, HI-FLOW, and CExistingExistingmaintenance workFL-net (Ver. 3.01, class 1-compliant) Max. 254 units、IEEE802.3-compliant Continued compatibility with S10V, enabling the migration of S10V program assets and ensuringnetwork connectivity Features of S10VE01Optical double ring(OD.RING)Max. 64 units、Max. 4 km between PLCs、total length 60 kmSoft-Error AutomaticCorrection FunctionLadder logic, HI-FLOW,and C programming languagesSoft errors can be caused by, amongother things, the malfunction of memorychips due to cosmic rays. S10VE'sprogram memory and internal registersinclude error correction code (ECC) thatautomatically corrects such errors,thereby allowing operations to continue.*The number of error bits that can becorrected depends on the memory area.A single CPU module can concurrentlyprocess programs coded in ladder logic,HI-FLOW, and C. You can also runprograms linked to other programs.Elimination of the battery forprogramsMigration of S10V programassetsConnectivity with existingsystemsNon-volatile memory is now used tostore programs, and the powerretention battery (to protect againstpower outages) has been eliminated.(Note that, if the watch function isused, you will need to periodicallyreplace the watch's battery.)S10V programs coded in ladder logicand HI-FLOW can be migrated toS10VE by using the PADT* converterfunction. (For details, see the guide onreplacement.)S10VE can be connected to S10V viaFL-net, optical double ring (OD.RING),or Ethernet. (For details, see the guideon replacement.)The CPU module is equipped with twoEthernet ports, allowing it tocommunicate with another computeror device in addition to the PADT.You can also add ET.NET modules toincrease the total number of ports toup to six ports.Improved performance (by1.6 times) and increasedEasy replacement of thecommunication moduleCPU indicatorWith a memory size of 479K bits or129 K words, S10VE boasts aladder-bit calculation speed that is 1.6times faster than that of S10V, and aladder program capacity that is 5times that of S10V.The parameters set for thecommunication module are stored inthe CPU, eliminating the need toreconfigure the parameters even if thecommunication module fails andneeds to be replaced.An indicator on the CPU moduledisplays the operating status. Even ifyou are not using the PADT, you caneasily perform maintenance, guided bythe errors and alarms displayed by theindicator.* PADT: Programming and Debugging ToolEthernetTwo standard Ethernet portsOptical double ring (OD.RING) Eliminated the power retention battery for programs, thereby reducing the amount of requiredFL-net(Ver. 3.01, class 1-compliant) Equipped with two standard Ethernet ports for enhanced connectivity with computersConnectivity: Remote I/O and Device-Level NetworkJ.NET (compatible with OPCN-1)Remote I/OD.NET (DeviceNet-compliant)HSC-1000I/OMax. 12units 100I/OS10VE CPUSlaveMax. 2 lines per CPUMax. 300 m per lineHSC-1000I/OMax.Max.Max.Max.2 lines8 lines500 m156 x. 64nodes perlineMax. 31units perlineHSC-1000I/OMax. 2 lines per moduleMax. 8 lines per CPUMax. 1000 m per linemoduleCPUline (trunk line)line (drop line)02

Mounting Configuration DiagramSpecificationsProgramming languageCPU mountbase(required)PADTPADTCPU power RI/O-IF CPUsupplymodule modulemodule(required)(required)512 k stepsLadder logicSoftware for PADTBASE SET/S10VE (required)Programming capacity(with ECC function)HI-FLOW dows (C-language developmentpersonal computerenvironment)Slots for I/O and communication modules (Max.7 slots)C-language compiler for SH(Optional modules specifically for S10VEand HSC-1000 series I/O modules can be installed.)Optional modules specifically for S10VE and HSC-1000 series I/O modulesI/O points8 M bytesHI-FLOW37 Mbytes(Number of tasks: Max. 224)CWhen using remote I/OMax. 2,048 pointsWhen using J.NETMax. 8,192 points479,357 pointsBitRegister capacity129,720 wordsWordLadder logicprocessing speedBasic order (AND)Word operation (ADD)9.4 ns per instruction18.75 ns per instructionEthernetPADT interfaceIncluded (ladder logic and HI-FLOW)Function that rewrites programs while they runRetention in the event of apower outageOperation in the event of apower outageProgram memoryNon-volatile memory (battery-less)RegisterPower retention register includedOperation continues by using the clock s batteriesf power outages: 5 years (25 C)ClockInstallation Environment RequirementsI/O on communication communication communication communication modulesmodulesmodulesmodulesmodulesmodules(1or 7 units)(1or 2 units)(1or 2 units)(1or 4 units)(1or 4 units)(1or 2 units)ItemAmbient temperature during operation(during storage)HumidityRemote I/O modules of the HSC-1000and HSC-2100 series can be connected.DustI/O mount base (required)HSC-1000 series remote I/O moduleI/O mount base (required)HSC-2100 series remote I/O moduleCorrosive gasResistance to momentary power outagesElevation during operationVibration resistanceI/O slots (8 slots)Shock resistanceI/O power RI/O dules(1or 8 units)Specifications0 to 55 C(-20 to 75 C)10 to 90% RH(with no condensation)Federal Standard 209D, class 1,000,000JEITA IT-1004B, class BAirbeilty to operate normally without detecting power outages of 10 ms orless I/O mount base (required)1,000 m or lessCompliance with JIS C60028-2-6Frequency: 10 to 150 Hz; acceleration: 10 m/s2in X, Y, and Z directions; sweep time: 8 minutes; number ofsweep cycles: 20 cyclesCompliance with to JIS C60068-2-27Peak acceleration: 147 m/s2Half-sine pulse: 3 times in each of the X, Y, and Z directionsI/O slots (8 slots)I/O power RI/O dules(1or 8 units)03( ):number of units that can be installed04

Model List: S10VEProduct nameItemCPUpower supplyModule(required)S10VE CPUEthernetDeviceNetNumber ofunits that canbe mountedSpecificationsTB20: 20-point terminal block, TB40: 40-point terminal block, CN40: 40P connector, CN34: 34P connector, Common: Common unitTypeCPU power supply CPU RI/O-IF 3 slotsHSC-1770 CPU power supply CPU RI/O-IF 7 slotsAC 100 to 110 VCPU power supply(AC/DC)LQV4101AC 100 V/120 V -15% to 10%, 144 VA, 50/60 Hz 5 HzDC 100 V/110 V -15% to 30%, 132 WAC 100 to 120 VCPULQP6001Ladder program capacity: 512 K steps, basic instructionexecution time: 9.4 ns, with two built-in Ethernet ports1Remote I/O master station, number of RI/O ports: 2, CPU STOP/RUNcontact input, RI/O STOP contact input, PCSOK contact outputLQE260-E1 to 2100BASE-TX, TCP/IP UDP/IP, 2 channels*1: It cannot be used for PADT connection or NX(Autonomous Decentralized System) use.LQE510-E1 to 2Optical double ring method, maximum distance between stations: 4 kmLQE702-E1 to 2FL-net Ver. 3.01, class 1-compliant, 100BASE-TXDC 48VLQE540-E1 to 4OPCN-1-compliant master station,1 Mbps (240 m) to 125 kbps (1 km)DC 100V1 to 4DeviceNet-compliant, choice of master, slave, peer,self-powered 125 kbps/250 kbps/500 kbpsRI/O-IFET.NETJ.NETD.NETLQE950LQE770-EDigital inputDC 12 to 24 VRelay contactAC 100 to 220 V /DC 12 to 24 V / 48 V /DC 100 to 110VModel List: HSC-1000ItemI/O mount baseModuleI/O powersupplyStationProduct nameModelNumber ofunits that canbe mountedSpecificationsI/O mount base (8 slots) HSC-1081 Number of I/O slots: 8 slotsI/O mount base (4 slots) HSC-1041 Number of I/O slots: 4 slotsI/O mount base (2 slots) HSC-1021 Number of I/O slots: 2 slotsI/O power supply (AC)LQV0001AC 100 V/120 V -15% to 10%, 80 VA, 50/60 Hz 5 HzI/O power supply(AC/DC)LQV1001AC 100 V/120 V -15% to 10%, 80 VA, 50/60 Hz 5 HzDC 100 V/110 V -15% to 20%, 50 WRI/O stationLQS0101Remote I/O slave stationD.STATIONLQS0701DeviceNet-compliant slave stationModel List: HSC-2100ItemI/O mount baseModuleProduct nameModelNumber ofunits that canbe mountedSpecificationsI/O mount base (8 slots) HSC-2108 Number of I/O slots: 8 slotsI/O mount base (4 slots) HSC-2104 Number of I/O slots: 4 slotsI/O mount base (2 slots) HSC-2102 Number of I/O slots: 2 slotsI/O powersupplyI/O power supply(AC/DC)LWV4611StationRI/O stationLWS4101Remote I/O stationCPU clock meterinputAnalog voltage/current outputModel List: Parts to Be Periodically ReplacedProduct nameTransistor (sink output)DC 12 to 24 VAnalog voltage/current inputAC100 V/120 V -15% to 10%, 135 VA50/60 Hz 5 HzDC100 V/110 V -20% to 30%, 65 WItemDigital outputMixed digitalinput/outputNumber ofunits that canbe mountedSpecifications1 per CPUThis battery is mounted on the CPU module and allowsthe clock to continue running even during a power outage.Standard replacement cycle: 5 yearsPulse-counter(UP & DOWN / UP)PointsRated input/output ModuleOptical double ring U mount baseCPU mount baseRemote I/OinterfaceModel List: HSC-1000 Series I/O ModulesInput: DC 12 to 24 VOutput: Transistor (sink output)DC 12 to 24 VHSC-1000 seriesModelTerminalCommon16 points (with latch)LQX110Terminal block8 points16 pointsLQX130Terminal block8 points16 pointsLQX200Terminal block8 points16 points (for high speed)LQX201Terminal block8 points16 points (with latch)LQX210Terminal block8 points32 pointsLQX300CN4032 points32 pointsLQX310CN3432 points64 pointsLQX350CN40 232 points16 pointsLQX220Terminal block8 points16 pointsLQX240Terminal block8 points16 points (with latch)LQX250Terminal block8 points16 points (a contact)LQY100Terminal block8 points8 points (a contact)LQY140Terminal block6 pointsLQY160Terminal blockEach pointindependent16 pointsLQY200Terminal block16 points32 pointsLQY300CN4032 points32 pointsLQY310CN3432 points64 pointsLQY350CN40 232 points32 inputs and 32 outputsLQZ300CN40 232 points(a contact, b contact)DC 5 V / 10 V / 1 to 5 V4 pointsLQA000Terminal blockEach pointindependentDC 5 V / 10 V / 1 to 5 V8 pointsLQA050Terminal blockCommon toall pointsDC 5 V / 10 V / 1 to 5 V8 pointsLQA055Terminal blockDC 4 to 20 mA4 pointsLQA100Terminal blockEach pointindependentDC 4 to 20 mA8 pointsLQA150Terminal blockCommon toall pointsDC 4 to 20 mA8 pointsLQA155Terminal blockEach pointindependent-100 to 100 C/-200 to 350 C/-200 to 500 C4 pointsLQA200Terminal blockCommon toall points-50 to 150 C/-200 to 100 C/-100 to 300 C4 pointsLQA201Terminal blockCommon toall pointsDC 5 V / 10 V / 1 to 5 V4 pointsLQA500Terminal blockDC 4 to 20 mA4 pointsLQA600Terminal blockCommon toall pointsCount: 0 to 16,383 /-8,192 to 8,191,Count input: DC 12 to 24 VComparative output: DC 12 to 24 V1 pointsLQC000Terminal blockIndependent06

Model List: HSC-2100 Series I/O ModulesModel List: Software for Windows 7 (64-bit), Windows 10 (64-bit)TB20: 20-point terminal block, TB40: 40-point terminal block, CN40: 40P connector, CN34: 34P connector, Common: Common unitTypeRated input/outputModelTerminalCommon16 pointsLWI650TB208 points32 pointsLWI600TB408 points16 pointsLWI450TB208 points32 pointsLWI400TB408 pointsDC 48 V16 pointsLWI460TB208 pointsDC 100 V16 pointsLWI470TB208 points32 points (a contact)LWO400TB408 points16 points (a contact)LWO450TB208 points16 points (a contact)LWO460TB40Each point independent8 points (c contact)LWO090TB40Each point independent16 pointsLWO650TB2016 points32 pointsLWO600TB4016 points32 pointsLWO610TB4016 pointsDC 5 V4 pointsLWA400TB20Each point independentDC 5 V (for high speed)4 pointsLWA401TB20Each point independentDC 10 V4 pointsLWA402TB20Each point independentDC 10 V (for high speed)4 pointsLWA403TB20Each point independentDC 10 V (for high speed)2 pointsLWA404TB20Each point independentDC 5 V (12 bits)4 pointsLWA430TB20Each point independentDC 5 V (14 bits)4 pointsLWA435TB20Each point independentDC 10 V8 pointsLWA500TB40Common to all pointsDC 5 V8 pointsLWA501TB40Common to all points-100 to 300 C4 pointsLWA421TB20Common to all points-50 to 150 C4 pointsLWA422TB20Common to all points-200 to 500 C4 pointsLWA423TB20Common to all pointsDC 5 V4 pointsLWA450TB20Common to all pointsDC 10 V8 pointsLWA550TB40Common to all pointsDC 5 V8 pointsLWA551TB40Common to all pointsDC 4 to 20 mA4 pointsLWA460TB20Common to all pointsDC 4 to 20 mA8 pointsLWA560TB40Common to all pointsCount: 0 to 16,383,Count input: DC 10 to 30 V,Comparative output: DC 24 V1 pointsLWC400TB20IndependentCount: -8,192 to 8,191,Count input: DC 10 to 30 VComparative output: DC 24 V(high-speed version)1 pointsLWC401TB20IndependentAC 100 to 120 VDigital inputDC 12 to 24 VRelay contactAC 100 to 220 V /DC 12 to 24 VDigital outputTransistor (sink output)DC 12 to 24 VTransistor (source output)DC 12 to 24 VAnalog voltage/current inputAnalogresistancethermometer inputAnalog voltage/current outputPulse-counter(UP & DOWN / UP)PointsCount: -8,192 to 8,191,Count input: DC 10 to 30 V,Comparative output: DC 24 V(low-speed version)1 pointsTypeProduct nameModel (*1)RemarkHSC-2100 seriesLWC402TB20Programming andparameter-setting software(required)Set of ladder diagrams, base system,backup restore, and parameter-settingsoftwareBASE SET/S10VE is a set package containing the following.・OD.RING SYSTEM/S10VE・BASE SYSTEM/S10VE・FL.NET SYSTEM/S10VE・CPMS/S10VE・LADDER DIAGRAM SYSTEM/S10VE ・D.NET SYSTEM/S10VE・BACKUP RESTORE SYSTEM/S10VE ・RCTLNET/S10VE・J.NET SYSTEM/S10VEBASE SET/S10VES-7898-50HI-FLOW SYSTEM/S10VES-7898-03HI-FLOW programmingRPDP/S10VES-7898-10C-language program developmentTo use the C programming language,a separate C compiler is required.NXACP/S10VES-7898-11Remote data field, long packet support.(Use in combination with RPDP/S10VE(Model: S-7898-10))To use the C programming language,a separate C compiler is required.NXTOOLS SYSTEM/S10VES-7898-13Execution module for NX parameter setting(NXTools And set of NX/HOST)Product nameTypeAPPLISuperH RISC engineC/C compiler Ver.9S-7350-22PProgramming softwareNX(Autonomous DecentralizedSystem)Model List Recommended SoftwareTypeC compilerUsed with the C-language compilerRPDP/S10VE for SHModel List: Recommended anufactured byHitachi Metals, Ltd.For long distances(300 m or less per line)・CO-EV-SX-1P 0.75SQ・CO-EV-SB-1P 0.3SQManufactured byHitachi Metals, Ltd.For intermediate distances(200 m or less per line)CO-EV-SB-1P 0.18SQManufactured byHitachi Metals, Ltd.CO-SPEV-SB-1P 0.3mm2Manufactured byHitachi Metals, Ltd.See "Recommended Cables" in theOD.RING documentation.Manufactured byHitachi Metals, Ltd.J.NETShielded twisted pair cable (KPEV-SB 2P 0.5 mm2)Manufactured byHitachi Metals, Ltd.D.NETDeviceNet cablesThick cable: UL20276-PSX 1P 18 AWG 1P 14 AWGFine cable: UL20276-PSX 1P 24 AWG 1P 22 AWGManufactured byHitachi Metals, Ltd.FL.NETHUTP-CAT5E-4P XXX (XXX indicates the cable length)Manufactured byHitachi Metals, Ltd.Remote I/OFor short distances(100 m or less per line)OD.RINGIndependent*1: When placing an order, add "J" or "E" to the end of the model number. Add "J" to receive the product along with documentation in Japanese,or "E" to receive the product along with documentation in English. Example: S-7898-50J, S-7898-50E0708

External DimensionsExternal dimensions of the HSC-10008-slot I/O unit(Unit: mm)119174159External dimentions of the S10VE7-slot CPU unitTop viewTop view119100139100139174Side view418437Side view418437Front viewFront view140External dimensions of the HSC-21008-slot I/O unitTop view200269140Side view418437Front viewS10VE CPU unit09HSC-1000 I/O unit(reference)S10V/S10 mini CPU mount baseHSC-2100 I/O unit7 slots3 slots8 slots4 slots2 slots8 slots4 slots2 269269269D17417411911911914014014010

Connectivity: Ethernet and Controller-Level Network Connectivity: Remote I/O and Device-Level Network Computer Existing Existing Ethernet Ethernet FL-net (Ver. 3.01, class 1-compliant) Max. 254 units、IEEE802.3-compliant Optical double ring (OD.RING) Max. 64 units、Max. 4 km between PLCs、 total length 60 km Optical double ring (OD.RING)