Issue Date:Page:PSS-K656LR-W0XFile:15/25kV600A Deadbreak Elboww/ TestPoint07/17/20171 of 5K656LR-W0XK656LRElbow Connector(with Test Point)Applications:The Elastimold K656LR (with test point) isdesigned to provide fully shielded, dead-frontsubmersible cable connections to high-voltageapparatus. The K656LR can be used through28kV with conductor range from #2 AWG to1250 kcmil for aluminum and copperconductors and insulation diameters from.640’’ to 1.935’’. When used on metallic tapeshield or drain wire cable, an ECS cable sealgrounding device for safety is highlyrecommended.Features:Ratings: For 15kV Voltage Class:Fully rated 15/25kV, 600 Amp Deadbreak Elbow Fully shielded, fully submersible molded rubber housing 100% peroxide-cured construction includes insulationand conductive EPDM materials Can be easily connected or disconnected usingstandard hand tools and equipment in a de-energizedstate Optional accessories allow visible external separation,by-pass, isolation, dead-ending, grounding, and testingas well as adding taps, surge arrestors, and fault currentindicators Non-corrosive, capacitive test pointMeets ANSI/IEEE Standard 386, LatestRevision8.3kV Max Phase-to-Ground – OperatingVoltage14.4kV Max Phase-to-Phase95kV BIL – Impulse Withstand (1.2 x 50microsecond wave)34kV AC – One minute withstand53kV DC – 15 minutes withstand11kV AC – Corona Extinction @ 3pCsensitivity600 Amp – Continuous25kA Sym – 10 Cycles MomentaryFor 28kV Voltage Class:16.2kV Max Phase-to-Ground – OperatingVoltage28kV Max Phase-to-Phase140kV BIL – Impulse Withstand (1.2 x 50microsecond wave)45kV AC – One minute withstand84kV DC – 15 minutes withstand21.5kV AC – Corona Extinction @ 3pCsensitivity600 Amp – Continuous25kA Sym – 10 Cycles Momentary

Issue Date:Page:File:15/25kVw/ TestPoint600A Deadbreak Elbow05/17/20172 of 5PSS-K656LR-W0XK656LR-W0XProduct Selection:CATALOG NUMBER SELECTIONStep 1 (W)Determine the insulation diameter of the cable.Select the insulation letter code that best straddles the insulationdiameter from W table below. Insert code into catalog number.Step 2Choose the proper connector material type and insert it intothe catalog number.Step 3 (X)Choose the proper compression lug code according to theconductor size from the Conductor Code Table. Insert code intocatalog number.Example:The ordering number for a 600 Amp ElbowConnector for a 4/0 compacted, 175 mil wall cablewith an insulation diameter of .830’’ to .910’’ andtest point is K656LR-G0270 plus the sealingkit, based on the shielding type. See next page.For 900A Elbows Use the Part #K676LR-G2270Each kit contains the following:111131111Elbow connector housingAl -Universal compressionlugStudInsulated Plug w/ CapTube, lubricantCable adapterInstallation InstructionInstallation InstructionCrimp 0IS-0320CC-0050

Issue Date:Page:PSS-K656LR-W0XFile:600A Deadbreak Elbow15/25kVUniversal AlCUBi-metalW CodeCable InsulationDiameter in inchesK656LR-W0X025XXX Code-Cable InsulationDiameter in millimetersX CodeK656LRw/ TestPoint05/17/20173 of 5MIN.MAX.MIN.MAX.Symbolfor 20440AWG or 500-Connector 0142004601440

Issue Date:Page:File:600A Deadbreak Elbow15/25kVw/ TestPoint05/17/20174 of 5PSS-K656LR-W0XK656LR-W0XIMPORTANT:For safety purposes, a sealing & grounding kit installed with the 600A dead break isRECOMMENDED. Please choose the sealing and grounding kit below.Jacket ConcentricNeutral Cable200/600ECSFor Jacketed ConcentricNeutral Cables, the sealingkit part number will be:200ECS or add suffix “-S” topart number for cables withnominal O.D. within the rangeof .80”-1.50”600ECS or add suffix “-S” topart number for cables withnominal O.D. within the rangeof 1.28”-2.30”Example:The ordering number for a 600Amp Elbow Connector for a 4/0compacted, jacketed concentricneutral, 175 mil wall cable withan insulation diameter of .830’’ to.910’’ , with test point, andoverall cable diameter is 1.23”and capacitive test point isK656LR-G0270-S.Copper TapeShield Cable200/600ECSG3For Copper Tape ShieldCables, the sealing &grounding kit part number willbe:200ECS or add suffix “-S” topart number for cables withnominal O.D. within the range of.80”-1.50”600ECS or add suffix “-S” topart number for cables withnominal O.D. within the range of1.28”-2.30”Example:The ordering number for a 600 AmpElbow Connector for a 4/0compacted, copper tape shield, 175mil wall cable with an insulationdiameter of .830’’ to .910’’ , with testpoint, and overall cable diameter is1.23” and capacitive test point isK656LR-G0270-S.

Issue Date:Page:PSS-K656LR-W0XFile:15/25kV600A Deadbreak Elboww/ TestPoint05/17/20175 of 5K656LR-W0XUnishieldCable10TL-WFor Unishield Cables, the shieldadapter part number will be:10TL-W, where the “W” letter code willbe determined by the insulationdiameter of the Unishield cable. Pleasesee W Table below for W code. Or addsuffix “-TL” to the part number.Copper TapeShield CableConcentricNeutral CableW Code10TLCable InsulationDiameter 51.5201.5951.6401.6851.875-Cable InsulationDiameter in 34.935.438.640.541.742.847.6Example:The ordering number for a 600Amp Elbow Connector for a 4/0compacted, Unishield,175 milwall cable with an insulationdiameter of .830’’ to .910’’ , withtest point, and overall cablediameter is 1.23” and capacitivetest point is K656LR-G0270-TL.Symbolfor ample:Example:Partial installation example ofK656LR-G0270-SG3 for coppertape shield cables.For full instruction please see IS460.Partial installation example ofK656LR-G0270-S for concentricneutral cables.For full instruction please see IS459.

For 15kV Voltage Class: 8.3kV Max Phase-to-Ground - Operating Voltage 14.4kV Max Phase-to-Phase 95kV BIL - Impulse Withstand (1.2 x 50 microsecond wave) 34kV AC - One minute withstand 53kV DC - 15 minutes withstand 11kV AC - Corona Extinction @ 3pC sensitivity 600 Amp - Continuous 25kA Sym - 10 Cycles Momentary