Tecomat Foxtrot CFox RFox

Transcription

Tecomat Foxtrot CFox RFoxProduct CatalogAdvanced Automation

Dear customers,dear designers!You get into the hand the new issue ofthe catalog of programmable controllersproduced by Teco a.s. company.This catalog is dedicated to PLC systemTecomat Foxtrot designed for anyapplication in industry, transport,measurement and energy control etc.Foxtrot system is younger and smallerbrother of time-proven big modularsystem Tecomat TC700. But smallerdimensions doesn t mean smallerrange of functionality. On the otherway, you may find in it all functionsof big programmable controllers withIEC EN 61131 standard compatibility,even combined with latesttechnologies known better from IT,telecommunication and internet.In next section you may find datasheets of CFox modules, these area logical extension of Foxtrot systeminto field of intelligent building controland building management systems.They are based on connection viatwo-wires bus with free topologyCIB. CIB – Common Installation Bus isa proprietary bus of Teco a.s. and ispatented.Next section is RFox line, what isa system extension of Tecomat Foxtrotwith wireless input/output modules infrequency band 868 MHz.We are sure that product range in thiscatalog may successfully cover eachautomation project.Teco a.s.

Central modules, peripheral modules and accessories overviewCentral modules XN 110 004 AI/DI, 2 DI/2302 ROPage 10TXN 110 038 DI/HSC, 8 AI/DI4 DO/PWM, 8 ROPage 12TXN 110 044 DI/HSC, 4 DI/AI6 ROPage 14TXN 110 056 AI/DI6 RO, 2 AOPage 16TXN 110 0613 AI/DI, 1 DI/HSC, 1 DI/23010 RO, 2 SSR, 2 AOPage 18TXN 110 0810 AI/DI, 2 AI, 1 DI/2307 RO, 4 SSR, 4 ROPage 20Central modules Foxtrot with LCD and keyboardCP-1014CP-1015CP-1016CP-1018TXN 110 144 DI/HSC, 4 DI/AI6 ROPage 14TXN 110 156 AI/DI6 RO, 2 AOPage 16TXN 110 1613 AI/DI, 1 DI/HSC, 1 DI/23010 RO, 2 SSR, 2 AOPage 18TXN 110 1810 AI/DI, 2 AI, 1 DI/2307 RO, 4 SSR, 4 ROPage 20Expansion I/O modulesInput/output 51PX-7811PX-7812TXN 113 014DI/HSC, 8DITXN 114 01TXN 115 014DI/HSC8 ROPage 26TXN 116 048 AI2 AOPage 27TXN 116 028 AI (TC)2 AOPage 27TXN 116 51TXN 178 117 DITXN 178 124 DI3DOPage 3112 DOPage 25Page 244AOPage 28Communication modules on TCL2 busUC-1203UC-1204Page 31Modules connected via serial 33 phase networkmeasurement /ModbusPage 39NEWTXN 112 03TXN 112 04OpenThermMP-BusPage 32Page 32TXN 105 52RS-485/MM optic fiberPage 33TXN 111 31RFox masterPage 83TXN 111 41Bus master2 CIBPage 47TXN 112 05TXN 111 81GSM gate for SMSRS-232 – MBusPage33Page 38Communication 15MR-0152MR-0161MR-0158MX-0301TXN 101 04RS-232TXN 101 14RS-485TXN 101 24RS-422TXN 101 58M busTXN 103 01WiegandPage 30TXN 101 52Profibus DPSlavePage 30TXN 101 61CANPage 30TXN 101 061 RS-2322 RS-485Page 30TXN 101 15Page 30TXN 101 052 RS-2321 RS-485Page 30Page 30Page 30Page 303 RS-485Page 30AI – analog input, DI – digital input, AI/DI – combined analog/digital input, DI/230 – digital input 230 VAC,DI/HSC – digital input/fast counter, RTD – resistive temperature detector, thermocouples connectionAO – analog outputs, DO – digital outputs, RO – relay outputs, SSR – Solid state relay, OC – open colectorAdvanced Automation

Power suppliesDR-15-24DR-60-24DR-100-24PS2-60/27TXN 070 4027 VDC/2,2 A12 VDC/0,3 APage 96DR-15-24DR-60-24DR-100-2424 VDC/0,63 A24 VDC/2,5 A24 VDC/4,2 APage 97Page 97Page 97Communication Ethernet/GSMSX-1162105FX306FX2UR5i v2ER75i v2RWEPAEasy RouteTXN 111 62Ethernet switch5 TX, 100MbitPage 35105FXEthernet switch4 TX, 1 FX portPage 36306FX2Ethernet switch4 TX, 2 FX portPage 36UR5i v23G/UMTS routerER75i v2GPRS/EDGE routerRWEPAWiFi klient IP67Easy Route4 TX port, WiFi3G routerDisplays, HMI panelsID-18ID-18 - DesignID-28ID-14ID-17TXN 054 42EthernetVGA touch panelPage 40TXN 054 40EthernetVGA touch panelPage 41TXN 054 33bus TCL24 20 characters, 25 keysPage 43TXN 054 37bus TCL2240 64 pixels, 4 DI, 2 ROPage 42NEWTXN 054 39EthernetVGA touch panelPage 41CIB bus system modulesCF-1141C-BS-0001MCIB bus modules on DIN NEWC-DL-0064MC-FC-0024XNEWTXN 111 41Masterbus 2 CIBTXN 133 55Bus separatorbus CIBDTNVEM-1/CIBOvervoltageprotection CIBDTNVE-1/CIBOvervoltageprotection CIBTXN 133 064 AI/DI, 14 DITXN 133 592 DI/AI, 2 RO1 AO/PWMTXN 133 5464x DALITXN 133 393 AI/DI2 RO, 1 AOPage . 47Page . 47Page 48Page 48Page 49Page 50Page 57Page 58CIB bus modules on DIN railC-HM-0308MC-HM M-ILEDC-DM-0402MNEWTXN 133 243 AI/DI6 RO, 2 AOPage 52TXN 133 103 AI, 8 DI11 RO, 2 AOPage 52TXN 133 113 AI, 8 DI19 RO, 2 AOPage 52TXN 133 03TXN 133 45TXN 133 46TXN 133 588 ROPage 516 LED outputsPage 546 LED outputsPage 552 230 V/AC dimmerPage 56CIB modules into installation box, under device 0401SC-DL-0012SC-WG-0503STXN 133 526 DI, 2 AI/DI, 1 AI8 OC PNP/NPNPage 61TXN 133 472 AI/DI, 1 IR, 1 photodiode1 IR transmitterPage 62TXN 133 23TXN 133 533 DI, 2 AI/DI3 OC NPNPage 64NEWTXN 133 292 AI/DIPage 59TXN 133 252 AI/DI1 RO, 1 AOPage 59TXN 133 265 AI/DI4 AOPage 6012 DALIPage 63

CIB modules into installation box, under device coverC-OR-0202BC-VT-0102BTXN 133 022 AI/DI2 ROPage 65TXN 133 551 AI/DI2 fans (7 – 15)VPage 66CIB modules for RC-0002RC-RC-0003R LogusRCM2-01NEWTXN 133 302 Buttons2 RTD externalTXN 133 314 Buttons2 RTD externalTXN 133 191 RTD internal1 RTD externalPage 75Page 75Page 79TXN 1332 AI/DI, 1 IR,1 fotodiode1 IR transmitterPage 80TXN 133 333 Buttons1 RTD externalLCDPage 81TXN 133 373 Buttons, 1 temperature1 humiditybacklit LCDPageTXN 131 571 rotational button1 RTD externalLCDPage 82CIB modules for interioron 0201F-ETXN 133 12Concentration CO2TXN 133 13Concentration VOCTXN 133 14Smoke concentrationTXN 133 15Relative humidityPage 83Page 83Page 83Page 83TXN 133 482 AI/DIValve drivePage 85Modules on CIB bus with IP65 0H-PC-IT-0100H-PC-IT-0100H-AC-RI-0401INEWTXN 133 092 AITXN 133 506 AI/DITXN 133 16.111 AITXN 133 16.121 AITXN 133 16.011 AITXN 133 17.011 AIPage 67Page 68Page 69Page 69Page 69Page 69Modules for wireless network RFoxTXN 133 47.921 temperature1 lightingPage 70Portable R-KF-0500TTXN 111 31Master for64 RFox modulesTXN 132 34AN-0631-01-01.001TXN 132 25TXN 132 08RouterAntenna RFoxAntenna RFox/GSM4 buttons5 buttonsinto socket868 MHzPage 92Page 92Page 88Interior modules for wireless network RFoxR-WS-0200RR-WS-0400RR-IT-0100RR-RC-0001RTXN 132 30TXN 132 31TXN 132 322 buttons4 buttons1 RTDPage 89Page 89Page 89TXN 132 091 RTD,Control buttonPage 90R-AQ-0001RR-AQ-0002RR-AQ-0003RR-AQ-0004RTXN 132 12TXN 132 13TXN 132 13TXN 132 15Concentration CO2 Concentration VOC Smoke concentration Relative humidityPage 97Page 97Page 97Page 97

RFox modules on DIN railfor valveinto installation 01BTXN 132 103 AI, 8 DI11 RO, 2 AOPage 93TXN 132 113 AI, 8 DI19 RO, 2 AOPage 93TXN 132 281 AIValve drivePage 82TXN 132 044 DITXN 132 011 ROPage 96Page 95Accessories (complementary products)Electricity meters, flow meters, water quality sensorsED11.MED11.M1f 230 V/25 AS0 pulse outputED 110.D0ED 310.DROpto probeWater meter ¾“AV23pHRedoxED 110.D0.14E302-001f 230 V/32 AS0ED 310.DR.14E304-003f 230 V/64 AS0, RS-485TXN 149 013/4" BONEGA-T-E/20223.7704.000SPH-1-S6SRX-1-PT-S6EN 62056-21RS-2322.5 m3/hourPulse output2.40m3/min1 flow, 1 temperaturepHRedoxMeteostations, sensors of condensation, humidity, inundation and levelMeteostationCondensationHumidity at flat spaceHumidity at gutterInundationWater levelLevel meterGIOM 3000Direction and speedof wind, air pressure,humidity, temperatureEthernetSHS A1ESF 524 001ESD 524 003DSCLS-23S-11HLM-25S-I-1000condensationHumidity at flat spaceHumidity at gutterconductivitycapacitivehydrostatic 150 kΩRTDcontact1 OC4 – 20 mATemperature RTD 1000OutsidePt1000StrapPt1000for HVACPt1000for sumpSK8NTC 12k-2PSSK2PA-2SSSK8S-2PSTXN 134 01.01P11PAP15PAP11PAP13PATemperature sensors for rtenC-IT-0200R-ZakTXN 133 20C-IT-0200R-ZakTXN 133 20C-IT-0200R-ZakTXN 133 20C-IT-0200R-ZakTXN 133 20C-IT-0200R-ZakTXN 133 20C-IT-0200R-ZakTXN 133 20C-IT-0200R-ZakTXN 133 20C-IT-0200R-ZakTXN 133 20Advanced Automation

Accessories – heatingAccessories - LightingValve drive 230 VValve drive 24 VValve drive 0 – 10 VBallast DALIBallast 1 – 10 VAlpha AA 2004/230Alpha AA 4004/24 VAlpha AA 5004 0 – 10 VEL 1 XX siFluorescent tubes T8, T5EL 1 XX scFluorescent tubes T8, T5Acessories – access systemRFID card readerRFID card readerCard reader with keyboardsAXR-100WiegandPage 63SSA-R1100WiegandPage 63SSA-R2000 VWiegandPage 63Accessories – security systems, electronic guard system detectorsMotion detectorMotion and glassbreak detectorGlass breakdetectorDoor contactGate contactIndoor sireneJS-20 LARGOPage 106JS-25 COMBOPage 106GBS-210 VIVOPage 106SA-200APage 106SA-204Page 106SA-913Page 106Accessories – security systems, electronic guard system detectorsPrestige QDPrestige PWPrestige DTPrestige Orbit DTPrestige External TDTriredImpaq Glass Break031 30300Quad PIR sensor42 detection zones2 contactsPage 64031 30700034 30100Dual MW PIR42 detection zones2 contactsPage 64031 32101Outdoor dualPIR MW2 contactsPage 64031 32000031 74600Outdoor triple PIRmotion detector2 contacts032 00700Acoustic glass breakdetection2 contacts24 detection zones2 contactsPage 64Outdoor dual PIR2 contactsPage 64Accessories – security systems, electronic fire system detectorsEXODUS OH/4W231 05100Dual, smokeand temperature1 contactPage 646EXODUS RR/4WEXODUS FT64/4W231 05200231 05300Max. temperature 64 C1 contactPage 64Temperature increase1 contactPage 64EXODUS FT9O/4WGS-133SD-282STSD-282STSmoke and hightemperature1 contact231 05400GS-133Max. temperature 90 CFlammable gases1 contactPage 641 contactPage 106Advanced Automationwww.tecomat.cz Teco a.s., Havlíčkova 260, 280 58, Kolín 4, Česká republika teco@tecomat.cz www.tecomat.com

FoxtrotPLC Basic modulesFoxtrotPLC Expansion modulesFoxtrotCommunication modulesDisplaysOperator panelsCFoxSensors and actuators for CIBCommon Installation BusRFoxWireless sensors and actuatorsPower suppliesAccessoriesSensors, detectors etc.www.tecomat.cz Teco a.s., Havlíčkova 260, 280 58, Kolín 4, Česká republika teco@tecomat.cz www.tecomat.comAdvanced Automation7

PLC FoxtrotCentral module communication lines schemaTCL2CIBRS-232I/OEthernet 10/100I/OMass storageSD/SDHC/MMCOptional interfaceRS-232RS-422RS-485RS-485/Profibus2 DMX512M-busCANParallel I/OModules connected to the system are mentioned in other parts of the catalog.8Advanced Automationwww.tecomat.cz Teco a.s., Havlíčkova 260, 280 58, Kolín 4, Česká republika teco@tecomat.cz www.tecomat.com

PLC FoxtrotBasic P-1006CP-1008CP-1016CP-1018www.tecomat.cz Teco a.s., Havlíčkova 260, 280 58, Kolín 4, Česká republika teco@tecomat.cz www.tecomat.comAdvanced Automation9

PLC Tecomat Foxtrot – basic modulesCentral module for building automation projects with CFox and RFox modulesTypeCP-1000DI2 DI/230 VACBasic featuresRO2 ROAI4 AI/DI Outstanding integration of control system with latest IT technologies and telecommunication technologies. Central module with 4 universal inputs, 2 inputs 230 V ACand 2 relays outputs. Universal inputs may be configured as analog inputsfor connecting temperature sensors Pt1000, Ni1000 or NTCtermistor 12 kΩ or as potential-free digital inputs. Digital inputs 230 V AC for connecting MRC (Mass RemoteControl) signal and 230 V AC network monitoring. Standard relay outputs 250 V AC/3 A. Extension of I/O up to 10 peripheral modules on serial busTCL2 (345 kbit/s). Expandable memory with SD/SDHC/MMC cards, built-in filesystem FAT32. Built-in clocks and calendar. Central module contains 2 CIB bus masters. It enables connectup to 64 inputs and outputs modules CFox in any combination and in any mechanical design. On terminals CIB and CIB– there is a powered bus. Number of CIB branches is expandable up to 10 via upto 4 optional masters CF-1141 connected on TCL2 bus, enabling up to 320 modules CFox. Optional connection up to 4 RFox masters RF-1131 via TCL2on radio channel 868 MHz. External masters of CIB bus CF-1141 and wireless system RFoxRF-1131 may be combined up to total number 4 masters on1 central module. There is built-in serial channel RS-232 for connection GSMmodems for direct communication with mobile phones,sending SMS messages etc or for general purpose.AOComm2 CIB, 1 TCL21 Ethernet 10/100,1 RS-232,1 optionalCP-1000 Next channel CH2 enables connection of optional communication interface submodule or inputs/outputs. Other 6 channels can be added using communication channels SC-1101or SC-1102. Programming and communications (LAN, WiFi, WAN, internet)via ethernet (100 Mbit/s), adjustable fixed IP adress or assigned by DHCP. Support of standard protocols Modbus RTU/TCP (masterand slave) and BACnet (slave). Built-in web server, free user programmable web pages storedon memory card (XML technology is used). Enables to create web page of any connected controlledobject. Possibility to use as programmable converter of communication protocols. Possibility to use as independent programmable dataloggerfor any measured or internal values with time stamp. Compact dimensions and form factor fit for standard electroinstallation switchboards assembled on DIN rail. Central module is powered from 24 V DC power supply.If 27.2 V power supply is used, it is possible to connect Pbaccumulators and keep the system in operation during powerfail for time depending on capacity of used accumulators. For automation control in buildings and residential housesfor common and complex tasks with needs to integrate withother systems mostly via communication interfaces. Central module may be free programmed in Mosaic softwareor parametrized in parametrization software FoxTool.Related productsSubmodules with tion example10www.tecomat.cz Teco a.s., Havlíčkova 260, 280 02, Kolín 4, Czech Republic teco@tecomat.cz www.tecomat.comAdvanced Automation

Function Digital inputsSerial portsSystem I/O busCommunication over expansionmodule on TCL2 busInstallation bus1 100/10 Mbit/s; TCP/IP, UDP,HTTP; SMTP ; MODBUS/TCP,BACnet, IEC 60870-5-1041 RS232;1 optional slot, optionalInterface (see submodulesMR-0xxx)1 TCL2 (RS485, 345 kbit/s)CIB, RFox, MPbus, OpenthermInput voltage for log. 0 (UL)Input voltage for log. 1 (UH)Input current for log. 1 (IH)Delay 0 – 1/1 – 02 CIB (19.2 kbit/s)(Common installation bus)Galvanic isolationInput voltage for log.0 (UL):Input voltage for log.1 (UH):Input current for log.1 (IH):Delay 0 – 1/1 – 0:Features of CPUCPUPLC Instruction cycleReal Time Clock (RTC)Backup period of RAM and RTCUser program memoryProgram memory backupInternal data memory (DataBox)Archive memory for the projectresource filesMemory card slotMemory for variablesUniversal inputs32 bit RISC processor0.2 ms/1k instructionsYes500 h without battery20 000 h with battery192 64 kBYes0.5 MB2 MBYes, MMC/SD, SDHC64 kB/32 kB remanent(DI0/AI0-DI3/AI3)Number inputsConfigurable inputs4Resistance measurement. Binaryinput (See separate table).minus (AGND)NoCommon wireGalvanic isolationFunkcion Analog inputs (AI0–AI3)ResolutionConversion timeMeasurement repeatingProtection type12 bittype 50 μs/1 inputtype 650 μsintegrated, overvoltageDigital inputs 230 V ACRelay outputsNo. of outputs groupsGalvanic isolationType of contact/type of outputSwitched voltageSwitched currentShort-term output overloadTime of close/open the contactThreshold limits of switched loadsfor resistive loadFoxtrotCommunicationEthernet;supported protocols(DI0-DI3)min. 2.3 V, max. 12 Vmin. 0 V, max. 1 Vtyp. – 1.7 mA1 ms/1 ms(HDO, IN 230 VAC)Yes, 4 kVmax. 120 V ACmin. 200 V ACtyp. 5 mA10 ms/10 msCP-1000(DO0–DO1)2 (1 1)Yes (outputs each other)NO relay, unprotected outputmin. 5 V; max. 250 Vmin. 10 mA; max. 3 Amax. 4 Atyp. 10 ms/4 msmax. 3 A at 30 V DCor 230 V ACfor inductive load DC13max. 1 A at 30 V DCfor inductive load AC15max. 3 A at 230 V ACSwitching frequency without load max. 300 switchings/min.Switching frequency with ratedmax. 20 switchings/min.loadMechanical/Electrical lifetimemin. 5 mil./100 000 cyclesat max. loadShort-circuit protectionNoSpike suppressor of inductive load External. (RC unit, varistor, diode)Insulation voltage3750 V AC (more details seedocumentation of TXV 004 11)Measurement rangesResistance Temperature Detectors (RTD)Input impedanceInput rangeMax. error at 25 CAllowed overloadSensor disconnectiondetection 4 kΩPt1000 1.385 (–90 up to 270 C)Pt1000 1.391 (–90 up to 2700 C)Ni1000 1.617 (–60 up to 155 C)Ni1000 1.500 (–60 up to 155 C)NTC 12k (–40 up to 125 C)KTY81-121 (–55 up to 125 C)resistance transmitter 0 up to 2000 Ωresistance transmitter 0 up to 200 kΩ 0.5 % of full range 10 % for range 0 up to 200 kΩ–20 up to 35 V(between AI and AGND)Yes, in status wordDimensions and weightOperating conditionsOperating temperatureStorage temperatureElectric strengthIP Degree of protection IEC 529Overvoltage categoryPollution degreeIEC EN 60664–1:2004Working positionInstallationConnectionsConductors cross-section–20 . 55 C–25 . 70 Caccording EN 60950IP 20II1verticalon DIN railScrew connectorsmax. 2.5 mm2DimensionsWeight158 92 63 mm250 gPower supplyPower supply voltage (SELV)Allowed rangeMax. power consumptionGalvanic isolationMemory backup 24 V DC–15% 25% (20.4 – 30 V DC)75 WNo, only relay outputs, HDO, IN 230VAC and CH2Built-in Li-Ion accumulator(500 hours)Holder for lithium battery CR2032(20 000 hours)Order numberTXN 110 00CP-1000, CPU, ETH100/10, 2 CIB, 1 RS232, 1 SCH, 4 AI/DI, 2 DI 230 VAC, 2 RO, prg. Mosaic/FoxToolwww.tecomat.cz Teco a.s., Havlíčkova 260, 280 58, Kolín 4, Czech Republic teco@tecomat.cz www.tecomat.comAdvanced Automation11

PLC Tecomat Foxtrot – basic modulesTypeCP-1003DIRO7 RO/3 A1 RO/10 A4 DO/PWM8 DI/HSCBasic features Programmable controller (PLC) according to IEC 61131standard with 32 I/O on basic module and with increasednumber of 20 extension modules up to 272 I/O in total. Built-in ethernet port 100 MBit and serial port RS-485 with option to expand with up to 3 other serial ports directly in basicmodule. Powerfull central module with practical configurationof 32 integrated inputs and outputs. 2 4 digital inputs with selectable voltage level and withalternative function of fast counters up to 100 kHz. 8 universal inputs selectable as analog or digital ones. Optional voltage, current and resistance range. 4 analog outputs with voltage range 10 V and resolution12 bit. 4 extra fast semiconductor digital outputs with optional function frequency output, pulse wide modulation (PWM), directcontrol of DC motors or direct control of stepper motors upto frequency 100 kHz. 8 relay outputs. 1 of them has possibility to switch10 A/230 V AC. 7 outputs switch up to 3 A. Expandable memory with SD/SDHC/MMC cards, built-in filesystem FAT32.Connection exampleAI8 DI/AIAO4 AOCommEthernet 10/100,2 TCL2, 1 RS485 Built-in clocks and calendar. Extension of I/O number with next up to 20 extension modules on 2 serial buses TCL2 (345 kbit/s). Option to create network of more PLC Tecomat in ethernetnetwork on RS-485 bus. Free programmable according to IEC 61131-3 standard. On-line programming during operation. Programming and communication via ethernet (100 Mbit/s),adjustable fixed IP address or DHCP. Up to 4 serial channels, one RS-485 is in basic configuration, others with optional interface from range MR 01xx(up to 345 kbit/s), adjustable UART. Other 6 optional channelscan be added using communication modules SC-1101 orSC-1102. Built-in PROFIBUS DP Master up to 180 kbit/s. Built-in WEB server, free web page designing, storing webpages at memory card (XML technology). Enables to create web page of any connected controlledobject. May be used also as programmable converter of communication technologies. May be used as independent programmable dataloggerfor any measured or internal values with time sign. Compact dimensions fit for standard electroinstallationswitch boxes, assembly on DIN rail.CP-1003Related productsSubmodules with inputs/outputsCommunicationsubmodulesMR-01xxCPU characteristicsCPUPLC cycle timeReal Time Clock RTCBack up RAM and RTCUser program and table memoryBack up memory programInternal memory – DataBoxMemory for program archivingSlot for memory cardsMemory for variablesNo. of IEC timers/countersCommunication32 bit RISC processor0.2ms/1k instructionsYes500 h/20 000 h without/with battery384 64 kBYes0.5 MB2 MBYes, SDHC/SD/MMC192 kB/48 kB remanent4096/8192Binary/counter inputs DI8-DI11, DI12-DI15Binary/Counter inputsOptional input functionsCommon wireGalvanic isolationTreshold level at inputInput voltage for. 0Input voltage for. 1Input resistance for. 1Delay 0– 1/1– 0124 24 counter or 2 IRC (encoder) upto 100 kHzminus (GNDA, GNDB)Yes, by groupsYes, 5 – 24. Adjustable by ref. voltageat input VDIA, resp. VDIBMax. 0,25 UDIMin. 0,6 UDITyp. 4.5 kΩ2μs/2μsEthernetSupported protocolsSerial channelsSystem I/O busCommunication via expansionmodule on TCL2 busBus for electroinstallation1 10/100Base TTCP/IP, UDP, http, SMTP, ModbusTCP, BACnet1 RS-485 (CH1) a 1 free slot CH2for submodule (see MR-01xx)2 TCL2 (RS-485, 345 kbit/s)CIB, RFox, MP-BUS, OpenThermOnly with external master CF-1141Analog/digital inputs DI0/AI0-DI7/AI7No. of inputs groupsOptional input functionCommon wireGalvanic isolationResolutionTime of transactionMeasurement repeatingProtection type8 1 Digital input Voltage range: 0 – 2 V, 0 – 10 V Current range: 0 – 20 mA, 4 – 20 mA Resistance range: 0 – 2 kΩ,0 – 200 kΩ NTC, 12k, KTY81 – 121,Ni1000, Pt1000Minus (AGND)Yes, from the rest of module, AI isconnected only with AO12 bit80 μs/1 input480 μsIntegrated, overvoltagewww.tecomat.cz Teco a.s., Havlíčkova 260, 280 02, Kolín 4, Czech Republic teco@tecomat.cz www.tecomat.comAdvanced Automation

4Yes, transistor output, isolatedfrom the rest of moduleOutput typePush-Pull – couple transistorsswitching into VCC and GND.May be grouped by two andcreate 2 full bridge.Optional output functionsFrequency output, PWMoutput, DC motor control. Withconnecting motor into bridgebetween 2 outputs the speedand direction can be controlled.Common wireminus (GND)Switched voltage10 – 32 V DCSwitched current permanent/pulse Max. 2,7 A/4 AResidual current at switching off12 mATime of switch on/off1.6μs/0.6μsSwitching speedMax. 100 kHzFoxtrotDigital transistor outputs DO8-DO11No. of inputsGalvanic isolationAnalog outputs AO0-AO3No. of outputsGalvanic isolationCommon wireResolutionOutput range/currentTime of conversion4Yes, AO is connected only with AIMinus AGND12 bit 10 V/max. 10 mA10μsCP-1003Relay outputs DO0-DO7Number of outputs7 3 A (DO0-DO6), 1 10 A (DO7) divided in 4groupsGalvanic isolationYes (also among groups)Type of contact/outputNO relay, unprotected outputSwitched voltageMin. 5 V, max. 250 V ACSwitched currentMin. 10 mA; max. 3 A (DO7-10 A)Short term output overloadMax. 4 A (DO7-10 A)Common wire currentMax. 15 ATime to close/open the contactTyp. 10 ms/4 msSwitching frequecy without the load Max. 300 switchings/min, 60 switchings/min (DO7)Switching frequecy with rated load Max. 20 switchings/min, 6 switchings/min (DO7)Mechanical/Electrical lifetimeMin. 5 mil/100 000 cyclesat max. loadShort-circuit protectionNoSpike suppressor of inductive load External. (RC unit, varistor, diode)Isolation voltage3750 V ACOperating conditions CP-1003Operating temperatureStoring temperatureElectric strengthDegree of protection IP (IEC 529)Overvoltage categoryDegree of pollution accordingČSN EN60664-1;2004Operation positionInstallationConnectionWire diameter–20 . 55 C–25 . 70 Caccording EN 60950IP20II1Verticalinto switching board on DIN railscrew terminalsDI, AI, AO, DO0, CH2 – 1.5 mm2,Others max. 2.5 mm2Dimensions and weight CP-1003DimensionsWeight158 92 63 mm (9M)250 gPower supply CP-1003Nominal voltage – (SELV)ToleranceMax. input powerInternal protectionGalvanic isolationBack up memory 24 V DC–15% . 25%; 20.4.30 V DC,10 WYesInputs and outputs yes,communication noBuilt-in Li-Ion accumulator (500hours). Holder for lithium battery.Order numberTXN 110 03CP-1003; CPU, ETH100/10, 1 RS485, 1 SCH, 8 AI/DI, 8 DI/HSC, 4 AO, 8 RO, 4 DO, 2 TCL2www.tecomat.cz Teco a.s., Havlíčkova 260, 280 58, Kolín 4, Czech Republic teco@tecomat.cz www.tecomat.comAdvanced Automation13

PLC Tecomat Foxtrot – basic modulesBasic module with 14 I/O (max. 21 I/O) with counter inputsTypeDI8 DIof which 4 DI/AI,and 4 DI/HSCCP-1004CP-1014RO6 ROAIAOCommEthernet 10/100, RS-232,1 optional interface,1 TCL2, 1 CIB, RFoxoptionalBasic featuresCP-1004 Programmable controller (PLC) according to IEC EN 61131standard. Outstanding integration of control system with latest ITand telecommunication technologies. Powerfull central module with integrated mostly binaryinputs and relay outputs (I/O). Type CP-1014 with built-in display 4 20 characters and 6 userkeys, other features the same with CP-1004. Available codepages: CP1250 (Central European), CP1251 (Cyrillic), CP1252(Western European), CP1253 (Greek). CP 1255 (Hebrew). 4 inputs may be configured as High speed counters (HSC)and 4 as voltage analog inputs. Optional slot can be inserted by additional 7 DIor 4 DI/3 DO on submodules PX-781x. Memory expandable by SD/SDHC/MMC cards, built-in filesystem compatible with FAT32. Built-in clocks and calendar. No. of I/O is expandable up to 134 I/O, resp. up to 10 moduleson high speed internal serial bus TCL2 (345 kbps). Other I/O can be expanded also by 2 wire installation bus CIB(19.2 kbps). More PLC Tecomat can be networked by Ethernet LAN or byRS-485 bus.Connection AI2CIB1 CIB LINEB1DI5AI1 24V24 V DCA9DI4AI0TCL2-GNDTC LINEA8DI3A7DI2A6DI1A5DI0A4GNDA3TxDA2RTSA1TCL2 24 V0VDIGITAL/SPECIAL INPUTS Free programmable PLC according IEC EN 61131-3. On-line programming during operation. Programming and data communication (in LAN, WiFi, WAN,Internet) is available on Ethernet port (100 Mbps) with fixed IPaddress or DHCP. Up to 10 serial ports: one RS-232, other 3 with optionalinterface (up to 345 kbps), configurable UART. Other 6 withadditional communication modules SC-1101 and SC-1102. Built-in PROFIBUS DP Master, Modbus RTU/TCP slave,IEC 60870-5-104 as payed application profile. Built-in BACnet slave on Ethernet port. Built-in web server, free creation of user internal web sitestored on memory card (XML technology). Enables to create web page of any connected controlledobject. May be used as programmable converter of communicationprotocols. May be used as independent programmable dataloggerfor any measured or internal values. Compact form-factor for DIN rail mounting (6 modules width)for standard circuit breaker cabinets. Removable connectors instead of fixed terminals.ETHERNETCP-1004MODENo. of counting inputsInput Frequency/Pulse widthDelay 0 – 1/1 – 0RangeModesD4D5DO5D3DO4D2DO3D1COM2C9DO2-TxRx TxDC8DO1C7TxRx-RxD--C6DO0C5TxRx CTS-C4TxRx-BT BT-C3DIGITAL OUTPUTSCOM1C2RTSGND 5VGND 5VC1D6D7D8D9230 VAC 24 V0V8 14 (DI0–DI3)4 (DI4–DI7)minus (GND)No0 V DC; (–5 5 V DC) 24 V DC; ( 15 30 V DC)typ. 5 mA5 μs/5 μs (DI0–DI3)5 ms/5 ms (DI4–DI7)Submodules with inputs/outputsDIGITAL/ANALOG INPUTSERRORCH2 OPTIONAL SUBMODULE (e.g. RS-232, RS-485)Related productsDigital inputs (DI0–DI7)No. of inputs groupsOption: High speed counterOption: Analog inputsCommon wireGalvanic isolationInput voltage for log. 0 (UL)Input voltage for log. 1 (UH)Input current for log. 1 (IH)Delay 0 – 1/1 – 0:High speed countersRUNCP-101424 VDC SELVAnalog inputsNumber of inputsCommon wireGalvanic isolationResolution/RangeConversion timeMax. error at 25 C(DI0–DI3)45 kHz/20 000 edges/secmin. 50 μs5 μsmax. 32 bit;0 4 294 967 295One, two way counter, encoder,pulse and period 4minus (GND)No10 bit/0 – 10 V350 μs/1 input 3 % of full rangeFeatures of CPUCPUPLC Instruction cycleReal Time Clock (RTC)Backup period of RAM and RTCUser program memoryProgram memory backupInternal data memory (DataBox)Archive memory for the projectresource filesMemory card slotMemory for variablesNo. of IEC timers/counters1432 bit RISC procesor0.2 ms/1 k instructionsYes500 h without battery, 20 000 hwith battery192 64 kBYes0.5 MB2 MBYes, MMC/SD, SDHC64 kB/32 kB Remanent4096/8192CommunicationEthernet;supported protocolsSerial portsSystem I/O busCommunication over expansionmodule na TCL2Installation bus1 10/100 BaseT;TCP/IP, UDP, HTTP; SMTP; MODBUSTCP, BACnet, IEC 60870-5-1041 RS-232;1 free slot for optionalinterface (see submodulesMR-0xxx)1 TCL2 (RS-485, 345 kbit/s)CIB, RFox, MP-Bus, OpenTherm1 CIB(Common installation bus19.2 kbit/s)www.tecomat.cz Teco a.s., Havlíčkova 260, 280 02, Kolín 4, Czech Republic teco@tecomat.cz www.tecomat.comAdvanced Automation

FoxtrotRelay outputs(DO0–DO5)No. of outputs groupsGalvanic isolationType of contact/type of outputSwitched voltageSwitched currentShort-term output overloadCurrent through joint terminalTime of close/open the contactThreshold limits of switched loadsfor resistive loadfor inductive load DC13for inductive load AC15Switching frequency without loadSwitching frequency with ratedloadMechanical/Electrical lifetimeat max. loadShort-circuit protectionSpike suppressor of inductive loadInsulation voltage3

TXN 133 09 TXN 133 50 TXN 133 16.11 TXN 133 16.12 TXN 133 16.01 TXN 133 17.01 TXN 133 47.92 2 AI 6 AI/DI 1 AI 1 AI 1 AI 1 AI 1 temperature 1 lighting Page 67 Page 68 Page 69 Page 69 Page 69 Page 69 Page 70 Modules for wireless network RFox Portable mobiles RF-1131 R-RT-2305W AN-06 AN-RFox/GSM R-KF-0400T R-KF-0500T