The Electrician’s Handbook

Transcription

The Electrician’s HandbookNexans Canada Inc., General Market140 Alcatel Parkway, Markham, Ontario, Canada L3R 0Z7Telephone (905) 944-4300 Fax (905) 944-4330www.nexans.com

INTRODUCTIONThe material presented in this handbook has been extractedfrom the Canadian Electrical Code, Part 1, CSA StandardC22.1 – 1998, and other sources.For authoritative reference or ruling please see the CanadianElectrical Code or consult your local inspection authority orCanadian Standards Association at (416) 747-4000.CAUTIONIn case of fire, well-maintained early-warning smoke detectors will give an alarm long before nonmetallic coverings become combustible. However, the Electrical and Electronic ManufacturersAssociation of Canada has suggested that all purchasers of PVC insulated/jacketed products beadvised of the following: Non-metallic coverings of electrical cables can burn and may transmit fire when ignited. Burning non-metallic coverings may emit acid gases which are toxic and may generate densesmoke. Emission of acid gases may corrode metal in the vicinity; e.g., sensitive instruments andreinforcing rods in cement.

TABLE OF 526-3738383839-4647-5555-5859-60Current Ratings – Single Copper Conductors . . . . . . . . . . .Current Ratings – Multi-Copper Conductors . . . . . . . . . . . .Current Ratings – Single Aluminum Conductors . . . . . . . . .Current Ratings – Multi-Aluminum Conductors . . . . . . . . . .Correction Factors applying to Tables 1, 2, 3 and 4 . . . . . . .Correction Factors for Tables 1 and 3 . . . . . . . . . . . . . . . .Ampacity Correction Factors for Tables 2 and 4 . . . . . . . . .Current Rating Factors for Cables in Tray . . . . . . . . . . . . . .Maximum Allowable per cent Conduit Fill . . . . . . . . . . . . . .Maximum Number of Conductors of One Size in TradeSizes of Conduit or Tubing . . . . . . . . . . . . . . . . . . . . . . . .Cross-Sectional Areas of Conduit and Tubing . . . . . . . . . . .Strandings for Building Wire and Cable . . . . . . . . . . . . . . . .Dimensions of Insulated Conductors for CalculatingConduit Fill . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Conditions of Use and Maximum Allowable ConductorTemperature of Wires and Cables other than Flexible Cords,Portable Power Cables and Equipment Wires . . . . . . . . . . .Spacing for Conductors . . . . . . . . . . . . . . . . . . . . . . . . . . .Supporting of Conductors in Vertical Runs of Raceways . . .Space for Conductors in Boxes . . . . . . . . . . . . . . . . . . . . .Corflex DimensionsCorflex Installation InformationACWU DimensionsACWU Installation InformationTable 1Table 2Table 3Table 4Table 5ATable 5BTable 5CTable 5DTable 8Table 6Table 9Table D5Table 10Table 19Table 20Table 21Table -85858687-8889909192-9596Recommended Configurations – Single Conductor Cables in Free AirAmpacity and Configurations – Single Conductor Cables Direct BuriedAmpacity and Configurations – Single Conductor Cables inUnderground DuctsConductors in Cable TraysVoltage DropDistance to Centre of Distribution . . . . . . . . . . . . . . . . . . . . Table D3Splicing and Terminating Aluminum ConductorShielding of Insulated ConductorsGrounding – Portable EquipmentMinimum Size Conductors Metallic Conduit or ElectricalMetallic Tubing for Grounding raceways and Equipment . . . Table 16Minimum Size of Grounding Conductor for AC Systemsor Common Grounding Conductor . . . . . . . . . . . . . . . . . . . Table 17Minimum Size of Grounding Conductor for Services . . . . . . Table 18Uses and Ampacity of Flexible Cord and Equipment Wire . . Table 12Three Phase AC Motors . . . . . . . . . . . . . . . . . . . . . . . . . . Table 44Single Phase AC Motors . . . . . . . . . . . . . . . . . . . . . . . . . . Table 45Alternating and Direct Current FormulaeCSA Wire and Cable StandardsNexans Canada Inc. Product ListingsSI PrefixesMetric ConversionsStranded Bare Copper and Aluminum ConductorsFire Rated Cables FT1 and FT41

TABLE 1(See Rules 4-004, 8-104, 12-2212, 26-000, 26-744, 42-008, 42-016, and Tables 5A, 5B, 19 and D3)ALLOWABLE AMPACITIES FOR SINGLE COPPER CONDUCTORS IN FREE AIR*Based on Ambient Temperature of 30 CAllowable Ampacity†85–90 C‡110 C‡60 C‡75 C‡125 C‡200 C‡SizeAWGkcmilTypeTWTypesRW75,TW75TypesR90, RW90,T90 te(3)SeeNote(3)BareWireCol. 1Col. 2Col. 3Col. 4Col. 5Col. 6Col. 751001351802102402803253704305102

TABLE 1 20—1,165—1,450—1,715Col. 1Col. 2Col. 3Col. 4Col. 5* See Table 5A for the correction factors to beapplied to the values in columns 2 to 7 for ambienttemperatures over 30 C.† The ampacity of single conductor aluminumsheathed cable is based on the type of insulationused on the copper conductor.‡ These are maximum allowable conductortemperatures for single conductors run in free airand may be used in determining the ampacity ofother conductor types in Table 19, which are so runas follows: From Table 19 determine the maximumallowable conductor temperature for that particulartype, then from the above Table determine theampacity under the column of correspondingtemperature rating.§ These ratings are based on the use of 90 Cinsulation on the emerging conductors and forsealing. Where a deviation has been allowed inaccordance with Rule 2-030, mineral-insulatedcable may be used at higher temperatures withoutdecrease in allowable ampacity, provided thatinsulation and sealing material approved for suchhigher temperature is used.Notes:1. The ratings of Table 1 may be applied to aconductor mounted on a plane surface ofmasonry, plaster, wood, or any material having aconductivity not less than 0.4W/(m �Col. 6Col. 72. For correction factors where from 2 to 4conductors are present and in contact, seeTable 58.3. These ampacities are only applicable underspecial circumstances where the use ofinsulated conductors having this temperaturerating are acceptable to the inspectiondepartment.4. Type R90 silicone wire may be used in ambienttemperatures up to 65 C without applying thecorrection factors for ambient temperaturesabove 30 C provided the temperature of theconductor at the terminations does not exceed90 C.3

TABLE 2(See Rules 4-004. 8-104, 12-012, 12-2212, 26-000; 26-744, 42-008, 42-016, and Tables 5A, 5C, 19 and D3)ALLOWABLE AMPACITIES FOR NOT MORE THAN 3 COPPER CONDUCTORS IN RACEWAY OR CABLE*Based on Ambient Temperatures of 30 C60 C‡75 C‡SizeAWGkcmilTypeTWTypesRW75,TW75Col. 1Col. 2Col. ble Ampacity†85–90 C‡110 C‡TypesR90, RW90,T90 NylonPaperMineral-InsulatedCable**Col. 4152030456585105120140155185††210235125 C‡200 C‡SeeNote(1)SeeNote(1)SeeNote(1)Col. 5Col. 6Col. 3404

TABLE 2 5315345390420470525560580600—680—785—840Col. 1Col. 2Col. 3Col. 4Col. 5* See Table 5A for the correction factors to beapplied to the values in columns 2 to 7 for ambienttemperatures over 30 C.† The ampacfty of aluminum-sheathed cable isbased on the type of insulation used on the copperconductors.‡ These are maximum allowable conductor temperatures for 1, 2, or 3 conductors run in a raceway or2 or 3 conductors, run in a cable and may be usedin determining the ampacity of other conductortypes in Table 19, which are so run as follows: FromTable 19 determine the maximum allowable conductor temperature for that particular type; then fromthe above Table determine the ampacity under thecolumn of corresponding temperature rating.** These ratings are based on the use of 90 Cinsulation on the emerging conductors and forsealing. By special permission, mineral-insulatedcable may be used at higher temperatures withoutdecrease in allowable ampacity, provided thatinsulation and sealing material approved for suchhigher temperature is used.†† For 3-wire 120/240 and 120/208 V residentialservices or subservices, the allowable ampacity forsizes No. 6 and No. 2/0 AWG shall be 60 A and 200A respectively. In this case, the 5% adjustment ofRule 8-106(1) cannot be applied.‡‡ See Table 5C for the correction factors to beapplied to the values in Columns 2 to 7 where ———————————————Col. 6Col. 7are more than 3 conductors in a run of raceway orcable.Notes:1. These ampacities are only applicable underspecial circumstances where the use ofinsulated conductors having this temperaturerating are acceptable to the inspectiondepartment2. Type R90 silicone wire may be used in ambienttemperatures up to 65 C without applying thecorrection factors for ambient temperaturesabove 30 C provided the temperature of theconductor at the terminations does not exceed90 C.5

TABLE 3(See Rules 4-004, 8-104, 12-2212, 26-000, 26-744, 42-008 and 42-016 and Tables 5A, 5B, 19 and D3)ALLOWABLE AMPACITIES FOR SINGLE ALUMINUM CONDUCTORS IN FREE AIR*Based on Ambient Temperature of 30 CAllowable Ampacity†85–90 C‡110 C‡60 C‡75 C‡125 C‡200 C‡SizeAWGkcmilTypeTWTypesRW75,TW75TypesR90, RW90,T90 NylonSeeNote(3)SeeNote(3)BareWireCol. 1Col. 2Col. 020304575100115135155180210240280Col. 4Col. 5Col. 6Col. 60801051401651852202552903354006

TABLE 3 Col. 1Col. 2Col. 3Col. 4Col. 5Col. 6Col. 7* See Table 5A for the correction factors to beapplied to the values in columns 2 to 7 for ambienttemperatures over 30 C.† The ampacity of single conductor aluminumsheathed cable is based on the type of insulationused on the aluminum conductor.‡ These are the maximum allowable conductortemperatures for single conductors run in free airand may be used in determining the ampacity ofother conductor types in Table 19, which are so run,as follows: From Table 19 determine the maximumallowable conductor temperature for that particulartype; then from the above Table determine theampacity under the column of correspondingtemperature rating.3. These ampacities are only applicable underspecial circumstances where the use ofinsulated conductors having this temperaturerating are acceptable.Notes:1. The ratings of Table 3 may be applied to aconductor mounted on a plane surface ofmasonry, plaster, wood or any material having aconductivity not less than 0.4 W/(m C).2. For correction factors where from 2 to 4conductors are present and in contact, seeTable 5B.7

TABLE 4(See Rules 4-004, 8-104, 12-2212, 26-000, 26-744, 42-008, 42-016 and Tables 5A, 5C, 19 and D3)ALLOWABLE AMPACITIES FOR NOT MORE THAN 3 ALUMINUM CONDUCTORS IN RACEWAY OR CABLE*Based on Ambient Temperature of 30 CAllowable Ampacity†§85–90 C‡110 C‡60 C‡75 C‡SizeAWGkcmilTypeTWTypesRW75,TW75TypesR90, RW90,T90 NylonPaperCol. 1Col. 2Col. 3Col. 20145165185**125 C‡200 C‡SeeNoteSeeNoteSeeNoteCol. 5Col. 6Col. 16018021024530455575951151301501802002252708

TABLE 4 ————————————Col. 1Col. 2Col. 3Col. 4Col. 5Col. 6Col. 7* See Table 5A for the correction factors to beapplied to the values in columns 2 to 7 for ambienttemperatures over 30 C.† The ampacity of aluminum-sheathed cable isbased on the type of insulation used on the copperconductors.‡ These are maximum allowable conductortemperatures for 1, 2, or 3 conductors run in araceway or 2 or 3 conductors, run in a cable andmay be used in determining the ampacity of otherconductor types in Table 19, which are so run asfollows: From Table 19 determine the maximumallowable conductor temperature for that particulartype; then from the above Table determine theampacity under the column of correspondingtemperature rating.§ SeeTable 5C for the correction factors to beapplied to the values in Columns 2 to 7 where thereare more than 3 conductors in a run of raceway orcable.** For 3-wire 120/240 and 120/208 V residentialservices or subservices, the allowable ampacity forsizes No. 6, No. 2 and No. 4/0 AWG shall be 60 A,100 A, and 200 A respectively. In this case, the 5%adjustment of Rule 8-106(1) cannot be applied.Note.These ampacities are only applicable under specialcircumstances where the use of insulatedconductors having this temperature rating areacceptable.9

TABLE 5A(See Rules 4-004(8), 12-2212 and Tables 1, 2, 3, 4, 57, 58 and D3)CORRECTION FACTORS APPLYING TO TABLES 1, 2, 3 AND 4AMPACITY CORRECTION FACTORS FOR AMBIENT TEMPERATURES ABOVE 30 C(These correction factors apply, column for column, to Tables 1, 2, 3, and 4. The correction factors in column 2 also apply to Table 57)Correction Factor85–90 C110 C60 C75 CAmbientTemperature CTypeTWTypesRW75,TW75TypesR90, RW90,T90 NylonCol. 1Col. 2Col. �———Notes:1. The ampacity of a given conductor type at thesehigher ambient temperatures is obtained bymultiplying the appropriate value from Table 1, 2,125 C200 CSee Note(2)See Note(2)See Note(2)Col. 4Col. 5Col. 6Col. 000.910.870.860.840.800.770.690.593, or 4 by the correction factor for that highertemperature.2. These ampacities are only applicable underspecial circumstances where the use of insulatedconductors having this temperature rating areacceptable.10

TABLE 5B(See Rules 4-004(9) and Tables 1, 3 and D3)CORRECTION FACTORS FOR TABLES 1 AND 3WHERE FROM 2 TO 4 SINGLE CONDUCTORS ARE PRESENT AND IN CONTACTNumber of ConductorsCorrection Factors2340.900.850.80Notes: 1. Where four conductors form a three-phase-with-neutral system, thevalues for three conductors may be used, Where three conductorsform a single-phase, three-wire system, the values for two conductorsmay be used.2. Where more than four conductors are in contact, the ratings forconductors in raceways shall be used.TABLE 5C(See Rules 4-004 and 12-2212 and Tables 2 and 4)AMPACITY CORRECTION FACTORS FOR TABLES 2 AND 4Number of ConductorsAmpacity Correction Factor1–34–67 – 2425 – 4243 and up1.000.800.700.600.5011

TABLE 5D(See Rule 12-2212)CURRENT RATING CORRECTION FACTORS WHERE SPACINGS ARE MAINTAINED(VENTILATED AND LADDER TYPE CABLE TRAYS)Number ofConductorsor 0.890.830.790.760.750.74VerticallyTABLE 8(See Rule 12-1014)MAXIMUM ALLOWABLE PER CENT CONDUIT AND TUBING FILLMaximum Conduit and Tubing Fill, Per CentNumber of Conductors or Multi-conductor Cables1234Over 4Conductors or multi-conductorcables (not lead-sheathed)5331404040Lead-sheathed conductoror multi-conductor cables553040383512

TABLE 6(See Rule 12-1014)MAXIMUM NUMBER OF CONDUCTORS OF ONE SIZE IN TRADE SIZES OF CONDUIT OR TUBING(NOTE: For ampacity derating factors for more than three conductors in raceways, see Rule 4-004)Size of Conduit or Tubing (inches)½¾11¼1½22½33½44½56Conductor Type Conductor SizeAWG 2654498761211981614121020181513252219163732282413

TABLE 6 (continued)Size of Conduit or Tubing (inches)½¾11¼1½22½33½44½56Conductor Type Conductor SizeAWG 720020020014011114

TABLE 6 275544TWU15(continued)

TABLE 6 (continued)Size of Conduit or Tubing (inches)½¾11¼1½22½33½44½56Conductor Type Conductor SizeAWG 111112111143332544436655487765109887151312111016

TABLE 6 3328242049413529TWTW75R90Silicone(Sizes No. 8and ed)

TABLE 6 (continued)Size of Conduit or Tubing (inches)½¾11¼1½22½33½44½56Conductor Type Conductor SizeAWG kcmilTWTW75R90Silicone(Sizes No. 8and 020020018

TABLE 6 1916§ These are the values for RW75XLPE and RW90XLPE without a jacket.** These are the values for Types RW75XLPE and RW90XLPE with a jacket.19

TABLE 9(See Rule 12-1014)CROSS-SECTIONAL AREAS OF CONDUIT AND TUBINGTradeSizeInchesInternalDiameterInchesPer Cent Cross-Sectional Area of Conduit – Square 2142.9703.8204.7846.0008.670Note:The dimensions represent average conditions onlyand variations will be found in dimensions ofconduit and tubing of different manufacture.20

TABLE D5STRANDINGS FOR BUILDING WIRE AND CABLENominalStandardDiam. ofDiam. ofStrandedEach Wire Conductor(inches)(inches)CMAreaNo. ofWires14*12*10*84 1106 53010 38016 51077770.02420.03050.03850.04866432126 24041 74052 63066 36083 6907777190000000000105 600133 100167 800211 600250 000300 000AWGFlexibleExtra FlexibleDiam. ofStrandedConductor(inches)No. ofWiresDiam. ofEach Wire(inches)Diam. 00.07010.5760.63191910.05240.05740.5770.632No. ofWiresDiam. ofEach e sizes are customarily supplied with solid conductors.(continued)21

TABLE D5 (continued)NominalAWGStandardFlexibleDiam. ofDiam. ofStrandedEach Wire Conductor(inches)(inches)Extra FlexibleNo. ofWiresDiam. ofEach Wire(inches)Diam. ofStrandedConductor(inches)No. ofWiresDiam. ofEach Wire(inches)Diam. 1.632CMAreaNo. ofWires350 000400 000450 000500 000550 00037373737610.09730.10400.11030.11620.0950600 000650 000700 000750 000800 000900 0006161616161611 000 0001 250 0001 500 0001 750 0002 000 00061919112712722

TABLE 10(See Rule 12-1014)DIMENSIONS OF INSULATED CONDUCTORS FOR CALCULATING CONDUIT AND TUBING FILLNote 1. Subject to the range of conductors and types of wires for which aluminum conductors are approved.Note 2. The dimensions represent average conditions only and variations will be found in dimensions of conductors of different manufacture.Rubber- (Thermoset) and Thermoplastic-insulated Conductors (0–600 V)SizeAWGkcmilTypes RW75,RW75 EP,RW90 EP,RW75 (XLPE)**,RW90(XLPE)**Types TW, TW75,RW75 (XLPE)§,RW90 (XLPE)§,R90 Silicone,R90 esAreaSquareInches141414(2/64) 0.171(3/64) 2/64) 0.188(3/64) 2.—.—Types TW U,RWU75 (XLPE)§,RWU90 (XLPE)§Types RWU75 EPRWU90 EPType T90 �0.268.—.—0.05640.1530.018423(continued)

TABLE 10 (continued)Rubber (Thermoset) and Thermoplastic-insulated Conductors (0–600 V)SizeAWGkcmilTypes RW75,RW75 EP,RW90 EP,RW75 s8640.3110.3970.452321Types TW, TW75,RW75 (XLPE)§,RW90 (XLPE)§,R90 Silicone,R90 (XLPE)§Types TW U,RWU75 (XLPE)§,RWU90 (XLPE)§Types RWU75 EPRWU90 EPType T90 .83810.92460.7160.7710.8220.40260.46690.530724

TABLE 10 (continued)Rubber (Thermoset) and Thermoplastic-insulated Conductors (0–600 V)SizeAWGkcmilTypes RW75,RW75 EP,RW90 EP,RW75 21Types TW, TW75,RW75 (XLPE)§,RW90 (XLPE)§,R90 Silicone,R90 (XLPE)§Types TW U,RWU75 (XLPE)§,RWU90 (XLPE)§Types RWU75 EPRWU90 30393.6610* These are the dimensions for Types RW75 and R90.† Dimensions of R90 silicone in sizes No. 14 to 10 AWG. Dimensions of R90 silicone in sizes No. 8 AWG and larger are the same as Type TW.§ Dimensions for Types RW75 XLPE, R90 XLPE, RW90 XLPE, RWU75 XLPE, and RWU90 XLPE conductors without a jacket.** Dimensions for Types RW75 XLPE and RW90 XLPE conductors with a jacket.Type T90 10.716325

TABLE 19(See Rules 4-006, 6-300, 12-100, 12-302, 12-602, 12-606, 12-902, 12-904, 12-1606, 12-2104, 12-2204, 16-112, 16-210, 22-200,22-202, 22-204, 22-206, 26-642, 30-312, 30-1004, 30-1102, 32-100, 32-202, 34-216, 38-006, 54-100, 56-104, 60-304, 74-004,78-104, and 80-004, 82-018, and Tables 1, 2, 3, 4, and D1)CONDITIONS OF USE AND MAXIMUM ALLOWABLE CONDUCTOR TEMPERATURE OF WIRES AND CABLES OTHERTHAN FLEXIBLE CORDS, PORTABLE POWER CABLES, AND EQUIPMENT WIRES.MaximumAllowableConductorTemperature CReferenceNotesConditions of UseTrade DesignationCSA Type DesignationFor exposed wiring in dry locations onlyArmoured CableTECK90AC9090904, 10, 124, 10, 12For exposed wiring in dry locations whereexposed to corrosive action, if suitablefor corrosive conditions encounteredArmoured CableTECK90902, 4, 10, 12Nonmetallic Sheathed CableNMD909023Nonmetallic Sheathed CableNMW, NMWU6023For exposed wiring in dry locations wherenot exposed to mechanical injuryFor exposed wiring in dry locations and inCategory 1 and 2 locations, where notexposed to mechanical injury26

TABLE 19 (continued)Conditions of UseFor exposed wiring in dry or damp locationsFor exposed wiring in wet locationsMaximumAllowableConductorTemperature CReferenceNotesTrade DesignationCSA Type DesignationRubber (Thermoset-) Insulated CableR90904, 9, 10, 11, 12Thermoplastic-Insulated CableTW604Nylon JacketedThermoplastic-Insulated CableT90 NYLON*9014Nonmetallic Sheathed CableNMD909018, 23Armoured CableTECK90ACWU9090904, 7, 10, 124, 7, 10, 12Rubber (Thermoset-) Insulated CableRW75RL90, RW9075904, 7, 10, 124, 7, 10, 12Aluminum-Sheathed CableRA75RA90759074, 7, 10, 12Mineral-Insulated CableMI, LWMI901, 7, 21Thermoplastic-Insulated CableTWTW 75*60754, 74, 7Nonmetallic Sheathed CableNMWU607, 8, 23(continued) 27

TABLE 19 (continued)Conditions of UseMaximumAllowableConductorTemperature CReferenceNotesTrade DesignationCSA Type DesignationArmoured CableTECK90904, 10, 12Rubber (Thermoset-) Insulated CableRW75R90, RW9075904, 10, 124, 10, 12Thermoplastic-Insulated CableTW, TWUTWU75607544Neutral-Supported CableNS-1, NSF-275—Nonmetallic Sheathed CableNMWU608, 23Armoured CableTECK90AC9090904, 10, 124, 10, 12For concealed wiring dry and damp locations Nonmetallic Sheathed CableNMD909018, 23For concealed wiring in dry locations and inCategory I and 2 locations where notexposed to mechanical injuryNMW, NMWU6023For exposed wiring whereexposed to the weatherFor concealed wiring dry locations onlyNonmetallic Sheathed Cable28

TABLE 19 (continued)Conditions of UseFor concealed wiring in wet locationsFor use in raceways, except cable trays,in dry or damp locationsFor use in raceways, except cable trays,in wet locationsMaximumAllowableConductorTemperature CReferenceNotesTrade DesignationCSA Type DesignationArmoured CableTECK90ACWU9090904, 7, 10, 124, 7, 10, 12Nonmetallic Sheathed CableNMWU607, 8, 23Aluminum-Sheathed CableRA75RA90759074, 7, 10, 12Mineral-Insulated CableMI, LWMI901, 7, 21Rubber (Thermoset-) Insulated CableR90904, 9, 10, 11, 12Thermoplastic-Insulated CableTW604Nylon JacketedThermoplastic-Insulated CableT90 NYLON*9014Rubber (

ALLOWABLE AMPACITIES FOR SINGLE ALUMINUM CONDUCTORS IN FREE AIR *Based on Ambient Temperature of 30 C Allowable Ampacity† 60 C‡ 75 C‡ 85–90 C‡ 110 C‡ 125 C‡ 200 C‡ Size Types Types See See AWG Type RW75, R90, RW90, Note Note Bare kcmil TW TW75 T90 Nylon (3)