Fisher GX 3 Way Control Valve And Actuator System

Transcription

Product BulletinGX 3-Way Valve and Actuator51.1:GX 3-WayAugust 2017D103305X012Fisher GX 3-WayControl Valve and Actuator SystemThe Fisher GX 3-Way is a compact, state-of-the-artcontrol valve and actuator system, designed toaccurately control water, oils, steam, and otherindustrial fluids. The robust GX 3-way valve package isperfectly suited to address the space limitations of theOEM industry.The GX 3-Way is rugged, reliable, and easy to select.The internal valve trim is designed to ensure longservice life and avoiding unnecessary maintenance.The same construction may be used for bothconverging and diverging applications.The GX 3-Way meets the requirements of both EN andASME standards. It is available with a completeaccessory package, including the FIELDVUE DVC2000and FIELDVUE DVC6200 integrated digital valvecontrollers.The GX 3-Way trim characteristics are designed foraccurate temperature control in heat exchangerapplications.nSide-Port Common (SPC)--The side flange is thecommon pipe connection for general converging(flow-mixing) and diverging (flow-splitting) service(see figure 4). Utilizes an unbalanced plug design.nBottom-Port Common (BPC)--A balanced designused for high pressure drop applications. Thebottom flange is the common pipe connection forboth converging and diverging service (see figures 8and 10).nHigh-Temperature Side-Port Common (SPC)-- Theside flange is the common pipe connection forgeneral converging (flow-mixing) and diverging(flow-splitting) service (see figure 2). Utilizes anunbalanced plug design, a stem extension, a yokeextension, and includes ENVIRO-SEAL graphiteULF packing (figure 14) and a hard-faced seat ring.www.Fisher.comW9557Fisher GX 3-Way Control Valve, Actuator, and FIELDVUEDVC2000 Digital Valve ControllerGE49204X0176Fisher GX 3-Way High-Temperature Control Valve andActuator

Product BulletinGX 3-Way Valve and Actuator51.1:GX 3-WayAugust 2017D103305X012Figure 1. Fisher GX 3-Way Control Valve Assembly with Port-Guided Contoured Plug (Side Port Common)COMPACT FIELD-REVERSIBLEMULTI-SPRING ACTUATORINTEGRATED POSITIONERMOUNTINGNAMUR POSITIONERMOUNTING CAPABILITYCLAMPED BONNET DESIGNONE-PIECE SCREWEDPACKING FOLLOWERSTANDARD ENVIRO-SEAL PACKINGW9578-1Figure 2. Fisher GX 3-Way High-Temperature Control Valve Assembly with Port-Guided Contoured Plug (Side PortCommon)COMPACT FIELD-REVERSIBLEMULTI-SPRING ACTUATORINTEGRATED POSITIONERMOUNTINGNAMUR POSITIONERMOUNTING CAPABILITYSTEM EXTENSIONYOKE EXTENSIONCLAMPED BONNET DESIGNONE-PIECE SCREWEDPACKING FOLLOWERSTANDARD ENVIRO-SEAL GRAPHITE ULF PACKINGGRAPHITE SEAL RINGX0094-1HARD-FACED SEAT AND GUIDESURFACES ON SEAT RING2

Product BulletinGX 3-Way Valve and Actuator51.1:GX 3-WayAugust 2017D103305X012FeaturesnEasy to size and selectnNo actuator sizing required--selection isautomaticnnAvailable with integrated, easy-to-calibrateDVC2000 or DVC6200 digital valve controllernValve body sizes DN 25 to DN 100(NPS 1 through 4)nPressure Classes PN 10-40,CL150 and 300nHigh capacity designnValve body flow passage optimized for flowstabilitynShutoff capabilities: Class IV metal to metalnISO 5210 F7 mounting available for use withelectric actuatorsEngineered for easy maintenancenMaximum part commonality across sizesnReplaceable trimnLow lifetime costsnRobust, low-profile designContentsFeatures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Principle of Operation . . . . . . . . . . . . . . . . . . . . . . . . 10GX 3-Way Control Valve Specificationsand Materials of Construction . . . . . . . . . . . . . . . 11The GX 3-Way Diaphragm Actuator . . . . . . . . . . . . . 14Valve-Actuator Dimensions and Weights . . . . . . . . .GX 3-Way Actuator Accessories . . . . . . . . . . . . . . . .The FIELDVUE DVC2000 Digital Valve Controller . .Optional Positioners and Instruments . . . . . . . . . . .171919203

Product BulletinGX 3-Way Valve and Actuator51.1:GX 3-WayAugust 2017D103305X012Figure 3. Fisher GX 3-Way and FIELDVUE DVC2000 Digital Valve ControllerLINKAGE-LESS POSITIONFEEDBACKINTEGRAL PNEUMATICPASSAGEWAYSDVC2000COVERPUSH-BUTTON INSTRUMENTSETUPOptimized valve and actuator system. Productsimplicity and ease of selection form the foundation ofthe GX 3-Way. Mounted with a digital or analogpositioner, the GX 3-Way provides high performancecontrol across a wide range of process applications.Compact actuator design. The multi-spring GX 3-Wayactuator is a compact robust design. The GX 3-Waydesign has been optimized to eliminate complicated3-way actuator sizing procedures - once the valve bodyand port size are selected, the actuator size is fixed.Reliable Actuator Performance. Special actuatordiaphragm material helps reduce common problemssuch as air oxidation, thermal aging, low temperatureembrittlement, and loss of retention (see table 6). Thedouble-sided diaphragm within the actuator helpseliminate mechanical wear-induced failure.Modular design. The design architecture has beenoptimized to maximize the use of common partsacross sizes. The actuator stem and stem connectorare used across all GX 3-Way sizes.4Low lifetime costs. Reduced product complexity, lowparts count, and part commonality all contribute toreduced inventory and maintenance costs.Stable flow control. The flow cavity of the GX 3-Wayvalve body has been engineered to provide stable flowand reduce process variability. This linear stability forboth converging and diverging flow is perfectly suitedfor temperature and pH control applications.Emission Requirements— ENVIRO-SEAL packingsystems provide an improved stem seal to helpprevent the loss of valuable or hazardous process fluid.The GX 3-Way comes standard with ENVIRO-SEAL PTFEpacking. ENVIRO-SEAL graphite ULF packing is alsoavailable for all sizes and is standard on hightemperature constructions.Easy maintenance. The simple screwed seat-ring andone-piece plug and stem design provide easymaintenance. Design simplicity and partscommonality contribute to reduced spares inventory.The integrated DVC2000 and DVC6200 digital valvecontrollers allow easy instrument removal, without a

GX 3-Way Valve and ActuatorD103305X012requirement for tubing disconnection or replacement(fail-down construction).Digital valve controller. The GX 3-Way is available withthe DVC2000 digital valve controller. The DVC2000 iseasy to use, compact, and designed for easymounting. It converts a 4-20 mA input signal into apneumatic output signal, which feeds the control valveactuator. Instrument setup is performed with a pushbutton and LCD interface. This interface is protectedfrom the environment within a sealed enclosure. Theinterface supports multiple languages, includingGerman, French, Italian, Spanish, Chinese, Japanese,Portuguese, Russian, Polish, Czech, Arabic, andEnglish.Intrinsic safety and non-incendive construction isavailable to CSA, FM, ATEX, and IEC standards. Anoptional module provides integrated limit switchesand a position transmitter.Integrated mounting. The DVC2000 and DVC6200digital valve controllers integrally mount to the GX3-Way actuator, eliminating the need for mountingbrackets. The DVC2000 transmits a pneumatic signalProduct Bulletin51.1:GX 3-WayAugust 2017to the actuator casing via an air passage in the yokeleg, causing the valve to stroke (see figure 12). Thiseliminates the need for positioner-to-actuator tubingin the fail-down configuration.The DVC2000 and DVC6200 mounting interfaces areidentical on both sides of the actuator yoke for valvebody sizes DN 25 through DN 100 (NPS 1 through 4).This symmetrical design allows the DVC2000 to beeasily moved from one side of the valve to the otherwithout the need to rotate the actuator.Linkage-less feedback. The DVC2000 and DVC6200digital valve controllers offer as standard anon-contacting valve position feedback system. This isa true linkage-less design, which uses no levers and notouching parts between the valve stem and thepositioner.Additional Accessory selection. The GX 3-Way isavailable with a variety of digital or analog positionersbesides the DVC2000 or DVC6200, as well as solenoidand limit switches. The actuator is also compatiblewith the IEC 60534-6-1 (NAMUR) positioner mountingstandard.5

Product BulletinGX 3-Way Valve and Actuator51.1:GX 3-WayAugust 2017D103305X012Flow Directions -- Side Port Common ConstructionsFigure 4. Side Port Common Construction Details for Diverging ConstructionsDIVERGINGBONNETO-RINGLEFT PORT(COMMON PORT)VALVE PLUGRIGHT PORTSEAT RINGW9580-1BOTTOM PORTFigure 5. Fisher GX 3-Way Flow Directions for Side Port Common Diverging ConstructionsDIVERGINGPLUG DOWN (0% TRAVEL)INLETDIVERGINGPLUG UP (100% TRAVEL)INLETINLETALL FLOW PASSESTHROUGH FROM LEFT TORIGHT-HAND PORT6DIVERGINGPLUG MID TRAVEL (50% TRAVEL)FLOW IS DIVERTED EQUALLYBETWEEN BOTTOM ANDRIGHT-HAND PORTALL FLOW PASSESTHROUGH FROM LEFT TOBOTTOM PORT

Product BulletinGX 3-Way Valve and Actuator51.1:GX 3-WayAugust 2017D103305X012Figure 6. Side Port Common Construction Details for Converging ConstructionsCONVERGINGBONNETO-RINGLEFT PORT(COMMON PORT)VALVE PLUGRIGHT PORTSEAT RINGW9580-1BOTTOM PORTFigure 7. Fisher GX 3-Way Flow Directions for Side Port Common Converging ConstructionsCONVERGINGPLUG DOWN (0% TRAVEL)CONVERGINGPLUG MID TRAVEL (50% TRAVEL)INLETINLETINLETBOTTOM PORT FLOW IS SHUT OFF. ALL RIGHT-HAND FLOWEXITS LEFT-HAND PORTCONVERGINGPLUG UP (100% TRAVEL)FLOW IS MIXED EQUALLY FROMBOTTOM AND RIGHT-HANDPORTSINLETRIGHT-HAND FLOW IS SHUTOFF.ALL BOTTOM PORT FLOW EXITSTHROUGH LEFT-HAND PORT7

Product BulletinGX 3-Way Valve and Actuator51.1:GX 3-WayAugust 2017D103305X012Flow Directions -- Bottom Port Common ConstructionsFigure 8. Bottom Port Common Construction Details for Diverging ConstructionsDIVERGINGBONNETVALVE PLUGLEFT PORTO-RINGSEAL RINGBACKUP RINGLOWERSEAT / CAGERIGHT PORTW9579-1BOTTOM PORT (COMMON PORT)Figure 9. Fisher GX 3-Way Flow Directions for Bottom Port Common Diverging ConstructionsDIVERGINGPLUG DOWN (0% TRAVEL)INLETALL FLOW EXITINGRIGHT-HAND PORT8DIVERGINGPLUG MID TRAVEL (50% TRAVEL)INLETFLOW IS DIVERTED EQUALLYBETWEEN BOTH SIDE PORTSDIVERGINGPLUG UP (100% TRAVEL)INLETALL FLOW IS EXITING THELEFT-HAND PORT

Product BulletinGX 3-Way Valve and Actuator51.1:GX 3-WayAugust 2017D103305X012Figure 10. Bottom Port Common Construction Details for Converging ConstructionsCONVERGINGBONNETVALVE PLUGSEAL RINGBACKUP RINGO-RINGLEFT PORTLOWERSEAT / CAGERIGHT PORTW9579-1BOTTOM PORT (COMMON PORT)Figure 11. Fisher GX 3-Way Flow Directions for Bottom Port Common Converging ConstructionsCONVERGINGPLUG DOWN (0% TRAVEL)CONVERGINGPLUG MID TRAVEL (50% TRAVEL)INLETLEFT-HAND FLOW IS SHUT OFF. ALL RIGHT-HAND FLOWEXITS THROUGH THE BOTTOMINLETCONVERGINGPLUG UP (100% TRAVEL)INLETFLOW IS MIXED EQUALLY FROMBOTH SIDE PORTSINLETRIGHT-HAND FLOW IS SHUTOFF.ALL LEFT-HAND FLOW EXITSTHROUGH THE BOTTOM PORT9

Product BulletinGX 3-Way Valve and Actuator51.1:GX 3-WayAugust 2017D103305X012Principle of Operation - GX 3-Way ActuatorFigure 12. Fisher GX 3-Way Principle of Operation -- Actuator Fail PositionAIR SUPPLYAIR VENTAIR VENTAIR SUPPLYFAIL-DOWN (REVERSE-ACTING)(STANDARD CONFIGURATION)FAIL-UP (DIRECT-ACTING)(OPTIONAL CONFIGURATION)E0896-3Integrated Air Supply. When mounted with theDVC2000 digital valve controller, the GX 3-Way usesan integrated actuator air supply system. In thefail-down configuration, air is supplied to the lower10actuator casing via a port on the actuator yoke face -no tubing is required. In the fail-up configuration, air issupplied to the upper casing via tubing.

Product BulletinGX 3-Way Valve and Actuator51.1:GX 3-WayAugust 2017D103305X012GX 3-Way Control Valve Specifications and Materials ofConstructionTable 1. Fisher GX 3-Way Valve Specifications(1)SpecificationsENASMEValve Body SizeDN 25, 40, 50, 80, 100NPS 1, 1-1/2, 2, 3, 4Pressure RatingPN 10 / 16 / 25 / 40 per EN 1092-1CL150 / 300 per ASME B16.34Flanged raised face per EN 1092-1Flanged raised face per ASME B16.5Screwed (NPS 1, 1-1/2, and 2)End ConnectionsValve Body MaterialsBonnet Materials1.0619 steelASME SA216 WCC steel1.4409 stainless steelASME SA351 CF3M stainless steel1.4409 stainless steel / CoCr-ASA351 CF3M SST / CoCr-AFace-to-Face DimensionsSee table 10Shutoff per IEC 60534-4and ANSI/FCI 70-2Metal seat - Class IV (standard)SPC High Temperature construction: Metal seat - Class IV for bottom seat, Class II for upper seatFlow DirectionConverging and DivergingFlow CoefficientsSee Fisher Catalog 12TypePlug SizesDescriptionSide Port CommonAll sizesUnbalanced Port-guidedBottom Port CommonAll sizesBalanced Cage-guidedTrim Style1. Stainless steel valve body is recommended for steam service when the high temperature construction is selected.Table 2. Materials (Other Valve Components)ComponentMaterialPacking FollowerS21800 SST screwed followerBody/BonnetBolting and NutsSA193-B7 studs / SA194-2H nuts with NCF2 coating for carbon steel and stainless steel constructionsPackingENVIRO-SEAL Live-loaded PTFE V-ring (standard) with N07718 Belleville springsENVIRO-SEAL Live-loaded Graphite ULF (optional) with N07718 Belleville springs, (standard) on High Temperature construction.Bonnet GasketGraphite laminateCarbon-Filled PTFE Seal RingBottom PortCommon Trim(all sizes)NBR (Standard) -46 to 82 C (-50 to 180 F)Back-up RingsEthylene Propylene [EPDM] (Optional): -46 to 232 C (-50 to 450 F) in steam and hot water;-46 to 121 C (-50 to 250 F) in air (EPDM is not recommended for use in hydrocarbons)FKM Fluorocarbon (Optional): -18 to 204 C (0 to 400 F) (Applicable in a wide variety of solvents, chemicals,and hydrocarbons. Avoid use with steam, ammonia, or hot water over 82 C [180 F])NBR (Standard) -46 to 82 C (-50 to 180 F)O-ring(not used withGX 3-Way HighTemperature)Ethylene Propylene [EPDM] (Optional): -46 to 232 C (-50 to 450 F) in steam and hot water;-46 to 121 C (-50 to 250 F) in air (EPDM is not recommended for use in hydrocarbons)FKM Fluorocarbon (Optional): -18 to 204 C (0 to 400 F) (Applicable in a wide variety of solvents, chemicals, and hydrocarbons.Avoid use with steam, ammonia, or hot water over 82 C [180 F])Seal Ring(GX 3-Way HighTemperature)Graphite (FMS 17F27) -46 to 371 C (-50 to 700 F)Stem Extension(GX 3-Way HighTemperature)Stainless steel11

Product BulletinGX 3-Way Valve and Actuator51.1:GX 3-WayAugust 2017D103305X012Table 3. Trim Materials (all sizes)Valve BodyConstructionTrim TypeStemPlugUpper SeatLower Seat/Cage(1)Carbon steel (1.0619 /WCC)Bottom Port CommonS31603 strain hardenedCF3M Chrome-platedCF3M/CoCr-ACF3MSide Port CommonS31603 strain hardenedCF3MCF3M/CoCr-ACF3MStainless steel(1.4409 / CF3M)Bottom Port CommonS31603 strain hardenedCF3M Chrome-platedCF3M/CoCr-ACF3MSide Port CommonS31603 strain hardenedCF3MCF3M/CoCr-ACF3M1. HT construction includes CF3M/CoCr-A lower seating. Seat and guide surfaces are hard-faced.Table 4. Allowable Temperature Ranges for Valve Body, Bonnet and Trim(1)TEMPERATUREVALVE BODY / BONNETMATERIAL1.0619/SA216 WCCSteelBONNET STYLEENVIRO-SEALPACKINGGASKETCTRIM STYLEFMinMaxMinMax-29232-20450StandardPTFE orGraphite ULFGraphite laminateBottom Port Common,Side Port Common1.4409/SA351 CF3M SSTStandardPTFE orGraphite ULFGraphite laminateBottom Port Common,Side Port Common-46232-504501.0619/SA216 WCCSteelHT ConstructionGraphite ULFGraphite laminateSide Port Common-29371-207001.4409/SA351 CF3M SSTHT ConstructionGraphite ULFGraphite laminateSide Port Common-46371-507001. Bonnet O-ring and back-up ring materials used on BPC trim may be limited by temperature and application.Figure 13. Material Pressure/Temperature Curves12

GX 3-Way Valve and ActuatorD103305X012Product Bulletin51.1:GX 3-WayAugust 2017Figure 14. Fisher GX 3-Way PackingBELLEVILLESPRING PACKPACKING SPACERANTI-EXTRUSIONWASHERPACKING SETANTI-EXTRUSIONWASHERPACKINGBOX RINGE0897STANDARD BONNET WITH ENVIRO-SEAL LIVE-LOADED PTFE PACKING SETDN 25 through DN 100 (NPS 1 through 4)BELLEVILLESPRING PACKPACKING SPACERPACKINGRINGSPACKINGBOX RINGGE38594 ULFSTANDARD BONNET WITH OPTIONAL ENVIRO-SEAL LIVE-LOADED GRAPHITE ULFPACKING SET (STANDARD ON HIGH TEMPERATURE CONSTRUCTION)DN 25 through DN 100 (NPS 1 through 4)13

Product BulletinGX 3-Way Valve and Actuator51.1:GX 3-WayAugust 2017D103305X012The GX 3-Way DiaphragmActuatorThe GX 3-Way uses a multi-spring, pneumaticdiaphragm actuator (see figure 15). It is capable of airsupply pressures up to 5.0 barg (72 psig), allowingvalve shutoff at high pressure drops (see table 8).Figure 15. Fisher GX 3-Way ActuatorThe GX 3-Way product selection system automaticallymatches the actuator to the valve, eliminating theneed for complex actuator sizing procedures.The multiple spring design provides the preload,eliminating the need for bench set adjustment. Theactuator is available in fail-down and fail-upconfigurations.The GX 3-Way actuator can be used for throttling oron-off service.The GX 3-Way is available with the integratedDVC2000 digital valve controller. Other digital andanalog positioners are available, as well as optionalsolenoids and limit switches.W8487-3Table 5. Actuator SpecificationsDescriptionPneumatic spring-return diaphragm actuatorOperating PrincipleFail-down (standard configuration)Fail-up (optional configuration)Operating Pressure RangesSee tables 8 and 9Ambient Temperature-46 to 82 C (-50 to 180 F)Pressure Connection (Fail-Up Construction)G 1/4 internal casing connectionFinishPowder coat polyesterTable 6. Materials of Construction14PartMaterialUpper and Lower CasingsAISI 1010 stamped carbon steelSpringsSteelDiaphragmNBR and nylonDiaphragm PlateAISI 1010 stamped carbon steelYoke and Yoke Extension on High Temperature ConstructionCarbon steelCasing FastenersA2-70 stainless steel bolts and nutsActuator RodStainless steelStem ConnectorCF3MStem Connector FastenersSA193-B7 bolts with NCF2 coatingStem BushingHigh-density polyethylene (HDPE)Stem SealNBR

Product BulletinGX 3-Way Valve and Actuator51.1:GX 3-WayAugust 2017D103305X012Actuator SelectionWith the GX 3-Way, actuator selection has never beeneasier. Once the valve size has been determined, theactuator is automatically selected.The following tables provide the maximum allowablepressure drops for the GX 3-Way. See table 8 for SidePort Common construction and table 9 for BottomPort Common construction. For optimal performance,the GX 3-Way should be operated with a FIELDVUEdigital valve controller.GX ISO 5210 ElectricActuator MountingElectric actuator mounting is available for anymanufacturing models that comply with ISO 5210,Flange type F7. The mounting offering includes a GXyoke, actuator rod adaptor, spacer, and bolting.Thrust limitations apply when sizing electric actuators(see table 7).Mounting offering can be engineered if not alreadyavailable for a selected actuator. For additionalinformation, contact your Emerson sales office or LocalBusiness Partner.Table 7. Fisher GX 3-Way Maximum Allowable Thrust for use with ISO 5210 Electric Actuators(THRUST LIMITATIONS APPLY IN BOTH TRAVEL DIRECTIONS)STEM DIAMETERTRAVELmmmmDN25-DN40(NPS 1 to 1-1/2)1019DN50 (NPS 2)14DN80-DN100(NPS 3 to 4)14VALVE SIZESTEM MATERIALMAXIMUM 4000315015

Product BulletinGX 3-Way Valve and Actuator51.1:GX 3-WayAugust 2017D103305X012Table 8. Maximum Allowable Pressure Drop (Side Port erating 1ULFMAX DP @Maximum SupplyPressureFAIL-UPOperating PressureMAX DP @Maximum SupplyPressure21.7 bar @ 5.0 bar3bar19.73.44bar20.24bar20.25bar20.216.2 bar @ 5.0 bar14.214.314.314.314.3 bar @ 5.0 bar14.014.0 bar @ 5.0 bar14.014.014.014.014.0 bar @ 5.0 bar14.014.014.0 bar @ 5.0 bar14.014.014.014.014.0 bar @ 5.0 bar21.721.721.721.7 bar @ 5.0 bar19.720.220.220.220.2 bar @ 5.0 bar12.216.216.216.216.2 bar @ 5.0 bar14.214.314.314.314.3 bar @ 5.0 barPTFE14.014.014.014.014.0 bar @ 5.0 bar14.014.014.014.014.0 bar @ 5.0 barULF14.014.014.014.014.0 bar @ 5.0 bar14.014.014.014.014.0 bar @ 5.0 barPTFE29.048.448.4---48.4 bar @ 4.0 bar35.444.944.9---44.9 bar @ 4.0 barULF25.845.545.5---45.5 bar @ 4.0 bar32.641.741.7---41.7 bar @ 4.0 barPTFE30.030.030.0---30.0 bar @ 4.0 bar30.030.030.0---30.0 bar @ 4.0 barULF30.030.030.0---30.0 bar @ 4.0 bar30.030.030.0---30.0 bar @ 4.0 barPTFE10.519.024.2---24.2 bar @ 4.0 bar12.020.224.2---24.2 bar @ 4.0 barULF9.217.723.0---23.0 bar @ 4.0 bar10.719.022.9---22.9 bar @ 4.0 barPTFE16.016.016.0---16.0 bar @ 4.0 bar16.016.016.0---16.0 bar @ 4.0 barULF16.016.016.0---16.0 bar @ 4.0 bar16.016.016.0---16.0 bar @ 4.0 barPTFE6.311.314.7---14.7 bar @ 4.0 bar7.212.214.4---14.4 bar @ 4.0 barULF5.510.513.9---13.9 bar @ 4.0 bar6.511.513.6---13.6 bar @ 4.0 barPTFE10.010.010.0---10.0 bar @ 4.0 bar10.010.010.0---10.0 bar @ 4.0 barULF10.010.010.0---10.0 bar @ 4.0 bar10.010.010.0---10.0 bar @ 4.0 bar20.2 bar @ 5.0 barTable 9. Maximum Allowable Pressure Drop (Bottom Port Operating 0ULFMAX DP @Maximum SupplyPressureFAIL-UPOperating PressureMAX DP @Maximum SupplyPressure51.7 bar @ 5.0 bar3bar36.23.44bar36.24bar36.25bar36.251.7 bar @ 5.0 bar25.625.625.625.625.6 bar @ 5.0 bar28.028.0 bar @ 5.0 bar28.028.028.028.028.0 bar @ 5.0 bar28.028.028.0 bar @ 5.0 bar28.028.028.028.028.0 bar @ 5.0 bar38.751.751.751.7 bar @ 5.0 bar27.927.927.927.927.9 bar @ 5.0 bar16.830.547.951.751.7 bar @ 5.0 bar19.719.719.719.719.7 bar @ 5.0 barPTFE22.022.022.022.022.0 bar @ 5.0 bar22.022.022.022.022.0 bar @ 5.0 barULF22.022.022.022.022.0 bar @ 5.0 bar22.022.022.022.022.0 bar @ 5.0 barPTFE35.251.751.7---51.7 bar @ 4.0 bar51.751.751.7---51.7 bar @ 4.0 barULF31.451.751.7---51.7 bar @ 4.0 bar50.750.750.7---50.7 bar @ 4.0 barPTFE30.030.030.0---30.0 bar @ 4.0 bar30.030.030.0---30.0 bar @ 4.0 barULF30.030.030.0---30.0 bar @ 4.0 bar30.030.030.0---30.0 bar @ 4.0 barPTFE19.535.251.7---51.7 bar @ 4.0 bar45.045.045.0---45.0 bar @ 4.0 barULF17.132.851.7---51.7 bar @ 4.0 bar42.642.642.6---42.6 bar @ 4.0 barPTFE25.025.025.0---25.0 bar @ 4.0 bar25.025.025.0---25.0 bar @ 4.0 barULF25.025.025.0---25.0 bar @ 4.0 bar25.025.025.0---25.0 bar @ 4.0 barPTFE19.535.251.7---51.7 bar @ 4.0 bar45.045.045.0---45.0 bar @ 4.0 barULF17.132.851.7---51.7 bar @ 4.0 bar42.642.642.6---42.6 bar @ 4.0 barPTFE25.025.025.0---25.0 bar @ 4.0 bar25.025.025.0---25.0 bar @ 4.0 barULF25.025.025.0---25.0 bar @ 4.0 bar25.025.025.0---25.0 bar @ 4.0 bar36.2 bar @ 5.0 bar

Product BulletinGX 3-Way Valve and Actuator51.1:GX 3-WayAugust 2017D103305X012Valve-Actuator Dimensions and WeightsTable 10. Fisher GX 3-Way Dimensions and Weights (Standard and High Temperature Constructions)PORT DIAVALVESIZETYPEUpperLowermmmmDN 25/NPS 1BPC2936SPC3636DN 40/NPS1-1/2BPC3946SPC3636DN 50/NPS 2BPC6170SPC4646DN 80/NPS 3BPC7890SPC7070DN 100/NPS 4BPCSPC78909090ABCTRAVELPN10 PN40CL150CL300PN10 8368352368184176184119ACTUATORSIZETable 11. Fisher GX 3-Way Dimensions and WeightsD (Actuator Height)VALVE SIZEEF (AR)Std ConstructionHigh TemperatureConstructionCasing DiaRemoval Height(1)TOTAL WEIGHTStd ConstructionHigh TemperatureConstructionmmmmmmmmkgkgDN 25/ NPS 13134182701152630DN 40/ NPS 1-1/23134222701152832DN 50/ NPS 23424854301206674DN 80/ NPS 339558543014597112DN 100/ NPS 43955854301451231381. Clearance required for removing actuator from installed valve body.Figure 16. Fisher GX 3-Way Dimensions (also see tables 10 and 11)ARAREEDDFFFCCBBA/2GE54802ASTANDARD CONSTRUCTIONA/2AHIGH TEMPERATURE CONSTRUCTION17

Product BulletinGX 3-Way Valve and Actuator51.1:GX 3-WayAugust 2017D103305X012Table 12. Fisher GX 3-Way Electric Actuator Mounting Dimensions and WeightsGVALVE SIZETOTAL WEIGHT,GX ELECTRIC ACTUATOR MOUNTING ASSEMBLYHISO 5210Electric Actuator YokeHeightmmKYoke DiameterStd ConstructionHigh TemperatureConstructionmmmmkgkgDN 25/ NPS 1202170921721DN 40/ NPS 1-1/2202170921923DN 50/ NPS 2202170922937DN 80/ NPS 3222170925772DN 100/ NPS 4226170928398Figure 17. Fisher GX 3-Way Electric Actuator Mounting Dimensions (also see table 12)HKGGE54756 218

Product BulletinGX 3-Way Valve and Actuator51.1:GX 3-WayAugust 2017D103305X012Table 13. Positioner Selection GuidelinesDigital 4)TypeP/P(3)X3660Flameproof / ExplosionProof(4)Non- Incendive(4)XXXXXX1. Digital I/P - microprocessor based electro-pneumatic with HART communication.2. I/P - electro-pneumatic3. P/P - pneumatic4. Refer to Fisher bulletin 9.2:001 (D103222X012) for instrument hazardous area classification details.GX 3-Way ActuatorAccessoriesFigure 18. FIELDVUE DVC2000Digital Valve ControllerThe GX 3-Way is available with a variety of pneumatic(P/P), electro-pneumatic (I/P), and digital valvepositioners, as well as limit switches and solenoids.Table 13 provides the basic features of the positionersoffered with the GX 3-Way actuator.The FIELDVUE DVC2000Digital Valve ControllerThe DVC2000 digital valve controller (figure 18) issimple to use, compact, and designed for the GX3-Way control valve. It converts a 4-20mA input signalinto a pneumatic output signal, which feeds thecontrol valve actuator. Instrument setup is performedwith a pushbutton and LCD interface. This interface isprotected from the environment within an IP66enclosure. Multiple languages are supported with thelocal interface including German, French, Italian,Spanish, Chinese, Japanese, Portuguese, Russian,Polish, Czech, Arabic, and English. Additionally, HARTrcommunication is supported over the 4-20mA loopwiring.The DVC2000 is designed to be integrally mounted tothe GX 3-Way actuator, avoiding the need formounting brackets. The DVC2000 mounts directly toan interface pad on the actuator yoke leg with a secure3-point mounting. An internal passage inside the yokeleg transmits the pneumatic signal to the actuatorcasing, eliminating the need for external tubing (in thefail-down configuration).W8755The high-performance linkage-less position feedbacksystem eliminates physical contact between the valvestem and the digital valve controller or instrument.There are no wearing parts so cycle life is maximized.Additionally, the elimination of levers and linkagesreduces the number of mounting parts and themounting complexity. Digital valve controller orinstrument replacement and maintenance is simplifiedbecause the feedback parts stay connected to theactuator.The DVC2000 is available with an optional modulewhich includes two (2) integral limit switches and astem position transmitter. The limit switches areconfigurable for open and closed valve indication. Theposition transmitter provides a 4-20mA signal for valveposition feedback verification. As an integralcomponent to the instrument, this option moduleavoids the need for difficult-to-mount externalswitches and transmitters.Designed to meet intrinsic safety and non-incendiverequirements, this instrument delivers scalablefunctionality and high performance in a small package.19

Product BulletinGX 3-Way Valve and Actuator51.1:GX 3-WayAugust 2017Optional Positioners andInstrumentsD103305X012Figure 19. FIELDVUE DVC6200Digital Valve Controller3660 and 3661 Valve PositionersThe 3660 pneumatic and 3661 electro-pneumaticpositioners are rugged, accurate, and feature lowsteady-state air consumption. Designed to meetintrinsic safety requirements, these positioners offersimple functionality in a small package. (See table 13.)W9713DVC6200 Digital Valve ControllerThe DVC6200 digital valve controller is acommunicating, microprocessor-basedcurrent-to-pneumatic instrument. Using HART orFOUNDATIONt fieldbus communication protocol,access to critical instrument, valve, and processconditions is provided. When used with ValveLinktsoftware, valve diagnostic tests can be run while thevalve is in service to advise you of the performance ofthe entire control valve assembly. Designed to meet abroad range of hazardous area classifications, thisinstrument offers maximum functionality to improveyour process performance. (See figure 19 and table13.)Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenanceof any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.Fisher, FIELDVUE, ENVIRO-SEAL, and ValveLink are marks owned by one of the companies in the Emerson Automation Solutions business unit of EmersonElectric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks arethe property of their respective owners.The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are notto be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales aregoverned by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of suchproducts at any time without notice.Emerson Automation SolutionsMarshalltown, Iowa 50158 USASorocaba, 18087 BrazilChatham, Kent ME4 4QZ UKDubai, United Arab EmiratesSingapore 128461 Singaporewww.Fisher.comE202008, 2017 Fisher Controls International LLC. All rights reserved.

extension, and includes ENVIRO-SEAL graphite ULF packing (figure 14) and a hard-faced seat ring. Fisher GX 3-Way High-Temperature Control Valve and Actuator W9557 GE49204 X0176 Fisher GX 3-Way Control Valve, Actuator, and FIELDVUE DVC2000 Digital Valve Controller GX 3-Way Valve and Actuator D103305X012 Pr