ObstructionLighting Guide

Obstruction Lighting Devicesas Tough as Your EnvironmentFor more than a century, companies have cometo rely on Cooper Crouse-Hinds for value theycan trust to grow their business. By integratinga comprehensive line of electrical productswith expert support, industry insights and localavailability, we improve safety and productivity inthe most demanding industrial and commercialenvironments worldwide. Every product wedevelop and every solution we engineer is clearlyfocused on lowering our customer’s total costof ownership.Our new line of LED Obstruction Lighting is noexception. Designed for long life, high brightness,and energy efficiency, these products will provideyears of cost-effective and maintenance-freeoperation. Cooper Crouse-Hinds LED obstructionlights, beacons, and visual signals contain themost advanced solid state technology packagedin a corrosive and weather-tight housing, meetingthe most rigorous safety standards for the mostdemanding environments.Cooper Crouse-Hinds is a globalleader across the industrial,commercial and residential marketsbecause of a strategic focus thatcombines the highest quality andreliability with technical support tominimize downtime, reduce repairincidence, and spur growth. In aworldwide marketplace, CooperCrouse-Hinds provides solutionsand products that are certifiedto meet local standards. When itcomes to quality, engineering andservice, however, our commitmentto continuous reinvention sets aglobal standard.2

Introduction & Table of ContentsIntroduction to Obstruction Lighting GuidelinesAny structure that exceeds 200' above ground level generally needsto be marked (lighted) according to FAA/ICAO Regulations. There aremany factors that can affect obstruction marking requirements, such asweather, terrain, proximity to airports, etc. The information presentedin the following pages of this catalog is intended to provide basicguidance for structure marking.The FAA and ICAO guidelines presented herein describe minimumrequirements for various structure heights and descriptions ofequipment to be used. Note that for Red Lighting Systems, the towermust be painted in alternating levels of aviation orange and white toprovide maximum daytime visibility (red lights are for nighttime only).In the case of white or dual lighting systems, the need for painting thetower is eliminated.Height is only one important consideration when choosing how astructure is to be marked. The products presented in this catalogsupport the obstruction lighting requirements set forth by the FAA/FCC and ICAO. For industrial applications, professional assistancewill be required, for example in the case of aviation lighting for industrial facilities. Let your salesrepresentative or Cooper Crouse-Hinds Customer Service (866-764-5454) help you determine which isthe best lighting solution for your unique application.Table of ContentsIntroduction to Obstruction Lighting Guidelines.3FAA and ICAO Configurations.4-11LED Technology.12-13Obstruction Lights (L-810).14-25LED General UseLED Class I, Div. 2LED ATEXVisual Signals.26-33LED General UseLED Class I, Div. 2LED ATEXBeacons L-864.34-39LED General Use Medium Intensity RedLED Class I, Div. 2 Medium Intensity RedXenon Medium Intensity RedBeacons L-864/L-865.40-41LED Dual Medium Intensity Red/WhiteXenon Dual Medium Intensity Red/WhiteBeacons L-865/L-866.42Xenon Medium Intensity WhiteBeacons L-856/L-857.43-44Xenon High Intensity WhiteXenon Flashheads Medium IntensityXenon Controllers for High IntensityControl Systems.48-52Accessories.53-62Index.63-64Xxxxx xxxx3

FAA & ICAO ConfigurationsFaaICAOFaa Lighting System ConfigurationIcao Lighting System ConfigurationTYPE ARed Lighting SystemTYPE BHigh Intensity WhiteTYPE CHigh Intensity White/Medium Intensity WhiteBeacon on appurtenance over 40' tallTYPE DMedium Intensity WhiteTYPE EDual Lighting System/RedMedium Intensity WhiteTYPE FDual Lighting System Red High Intensity White(Dual Beacon on appurtenance over 40' tall)FAA Equipment ClassificationL-810Steady-Burning RedObstruction LightL-856High Intensity Flashing White Obstruction Light(40 FPM)L-857High Intensity Flashing White Obstruction Light(60 FPM)L-864Flashing Red Obstruction Light (20-40 FPM)L-865Medium Intensity Flashing White ObstructionLight (40 FPM)L-864/L-865Dual: Flashing Red Obstruction LightMedium Intensity Flashing White ObstructionLight (40 FPM)L-866Medium Intensity Flashing White ObstructionLight (60 FPM)L-885Red Catenary (60 FPM)FPM Flashes Per Minute4Type ALow Intensity, Red SteadyMedium Intensity, White FlashingHigh Intensity, White FlashingType BLow Intensity, Red SteadyMedium Intensity, Red FlashingHigh Intensity, White FlashingType CLow Intensity (Mobile), Yellow/Blue FlashingMedium Intensity, Red Steady

FAA ConfigurationsFAA Red Lighting Type A†—Painted Tower/Red Lights for Night1751' – 2200' *CONFIGURATION KEYL-864 Flashing BeaconL-810 Obstruction Light1401' – 1750' *1051' – 1400' *701' – 1050' *351' – 700' *151' – 350' *0' – 150' *A-6A-5A-4A-3A-2A-1A-0This illustration is meant to be used as a guideline only. Please refer to FAA Advisory Circular 70/7460-1K* Including any appurtenance†5

FAA ConfigurationsFAA White Lighting Type C† and Type D†—White Lights for Day/White Lights for Night1751' – 2200' **CONFIGURATION KEYL-865 Medium IntensityFlashing BeaconL-856 High IntensityFlashing Beacons1401' – 1750' **1051' – 1400' **701' – 1050' **501' – 700' **351' – 500' *200' – 350' *C-6C-5C-4C-3C-2D-2D-1This illustration is meant to be used as a guideline only. Please refer to FAA Advisory Circular 70/7460-1K* Including any appurtenance** Excluding appurtenance†6

FAA ConfigurationsFAA Dual Lighting Type E† and Type F†—White Lights for Day/Red Lights for Night1751' – 2200' **CONFIGURATION KEYL-864/L-865 MediumIntensity Dual Red/WhiteFlashing BeaconL-864 Flashing BeaconL-856 High IntensityFlashing BeaconsL-810 Obstruction Light1401' – 1750' **1051' – 1400' **701' – 1050' **501' – 700' **351' – 500' *200' – 350' *F-6F-5F-4F-3F-2E-2E-1This illustration is meant to be used as a guideline only. Please refer to FAA Advisory Circular 70/7460-1K* Including any appurtenance** Excluding appurtenance†7

FAA ConfigurationsFAA/FCC Chimney & StackLighting Re quire mentsNOTE:Information is provided to assist in your product selection basedon AC 70/7460-1K and AC 150/5345-43G Advisory Circular.Your application may demand special lighting requirements. LEDFixtures are ideal for solid structure applications.Number of lights per level/structure diameterNOTE:Number of lights per level is the minimumNumber and Types of Lighting Levels/HeightA1A2A3L-864 Flashing RedObstruction mend use of double fixtureswith transfer to spare on failure3/4Feet(meters)150’(46)7/8PTOL-810 *Steady-BurningRed Obstruction Light1/2A4350’(107)700’(213)1050’(320)Type of Lighting and fixture locationA01400’(427)Height of Structure AGL (above ground level)NOTE:Lowest level of lights must be raised above the height of adjacent structures. If your structure is not rep re sent ed, allow us to assistyou with selecting the proper products for your specific structure. Example: For structure “A1” requires one L-864 beacon at top andat ½ tower height mount L-810 sidelights.8

ICAO ConfigurationsICAO Red Lighting†—Painted Tower/Red Lights for Night‡521m – 624m*CONFIGURATION KEYMedium IntensityType B (flashing) orType C (steady) L-864Low IntensityType B (steady) L-810Low Intensity doubleType B (steady) L-810417m – 520m*NOTE: Spacing between levelsmust not exceed 52m. For moreinformation on specific applications,call Technical Support.313m – 416m*209m – 312m*105m – 208m*46m – 104m*0m – 45m*This illustration is meant to be used as a guideline only. Please refer to ICAO (Annex 14)May use low intensity Type B or medium intensity Type B at this level* Including any appurtenance†‡9

ICAO ConfigurationsICAO White Lighting†—White Lights for Day/White Lights for NightCONFIGURATION KEY526m – 630m**Medium IntensityType A — L-865/L-866High IntensityType A — L-856/L-857421m – 525m**316m – 420m**211m – 315m**151m – 210m**106m – 150m*45m – 105m*This illustration is meant to be used as a guideline only. Please refer to ICAO (Annex 14)* Including any appurtenance** Excluding appurtenance†10

ICAO ConfigurationsICAO Dual Lighting†—White Lights for Day/Red Lights for Night521m – 624m**CONFIGURATION KEYMedium Intensity Type Aand Type B—L-864/L-865Medium Intensity Type B(flashing) or Type C (steady)L-856/L-857 or L-864(Use all Type B or all Type C)High Intensity Type AL-856/L-857417m – 520m**Low Intensity Type B—L-810313m – 416m**209m – 312m**151m – 208m**105m – 150m*45m – 104m*This illustration is meant to be used as a guideline only. Please refer to ICAO (Annex 14)* Including any appurtenance** Excluding appurtenance†11

Solid State Lighting for Industrial Locations —LED TechnologyEvolution in Lighting TechnologyAdvances in light emitting diode (LED)technology, including super-bright whitediodes and other performance improvements,are creating new applications and increasedacceptability of LEDs in mainstreamuse. Additionally, challenging customerrequirements in industrial or harsh andhazardous locations including long life, highbrightness, and reliability can be achievedwith currently available LED technology.Once considered only for indication ordecorative purposes, LEDs are nowgaining acceptability in signaling, downlights, floodlights, street lights, and othermainstream uses. When compared toother conventional light sources suchas incandescent, fluorescent or metalhalide, a LED light source can offer longerlife, energy savings, and equal or betterlight characteristics, providing years ofmaintenance free operation with aquantifiable return on investment.Cooper Crouse-Hinds isleading the innovation effortsto make LED technology aviable alternative in luminairesfor use in industrial andhazardous areas.The Solid State LED growthinitiative is one integral part ofa company-wide plan to driveinnovation and technologywithin our business to broadenour solutions to our customers.12

Solid State Lighting for Industrial Locations—LED TechnologyLED – Light Emitting Diode Semiconductor material converts electricity into light asic structure consists of semiconductor, reflector wire bondBand epoxy domeColor of the light is dependent on the semiconductor materialLED photo courtesy of Philips LumiledsLighting CompanyAdvantages of Cooper Crouse-Hinds LED TechnologyLower Cost of OwnershipSolid State LED lighting has become a leading energy efficient technology with the addedbenefit of long service life. This equates to energy savings and reduced maintenance,providing a lower cost of ownership when compared to many conventional light sources.High Intensity and BrightnessHigh brightness and Ultra High brightness LEDs now offer the ability to producecustomized light patterns for illumination. Using customized LED arrays, designers cannow focus on unique fixture designs without relying on a pre-determined lamp source.Low HeatConventional lighting technologies waste a significant portion of energy producingvisible white light. This translates to excessive heat energy. LED technology is efficientat converting electrical energy into light energy while generating very little heat. Inhazardous locations, this relates to a more favorable T-rating.Environmentally FriendlyUnlike conventional light sources such as fluorescent and HID that use mercury togenerate light, LED lighting uses no mercury, thus eliminating the issues surroundingdisposal of hazardous substances. Additionally, LEDs save energy, therefore reducingthe overall impact of fossil fuels on the environment.Reliable and RuggedLEDs contain no fragile filaments or glass. LEDs are solid state devices and are lessaffected by the demands of harsh and hazardous environments. Additionally the life ofthe LED is based on lumen depreciation, not failure. Therefore, LED lighting is designedto maintain a safe lights-on condition throughout the useful life of the luminaire.Easily Programmed or ControlledSolid State lighting offers the ability to integrate control systems for building uniquefeatures into a lighting system. Controls can offer a feature as simple as dimming oron/off to controls of color temperature or monitoring of product condition.13

14

ObstructionLighting15

Obstruction Lights—LED General UseRT SeriesLED OBSTRUCTION LIGHTCertified to: FAA AC NO: 150/5345-43GCompliant to: ICAO (Annex 14 - Fourth Edition,July 2004)Low intensity Type A (10 cd)Low intensity Type B (32 cd)DGAC MexicoVER IF I E Doperating conditionsFeatures/Benefits Available as a single, dual, or retrofit unit Available in 120-240VAC or 12-48VDC Grounding terminals provided Unique optical design (patent pending) Advanced high-flux LED technology Lasts years longer than an incandescent The RT Series is designed to withstand thedynamic conditions experienced in the most severeenvironments around the world. It has been tested intemperatures ranging from -40 to 55 degrees Celsius,direct sunlight, wind blown rain, wind in excess of150mph, high humidity, salt, and fog.materials and finishes eather/corrosion resistant lamp assembly andWhousing elf-contained wiring compartment eliminatesSadditional boxes Threaded 1" and 3/4" bottom hub for mounting Can be operated steady or flashed Uses 95% less energy than incandescent Resistant to shock and vibration IP65 / IP66 / NEMA 4X Cast aluminum base and housing Aviation red UV resistant polycarbonate domeapplicationThe RT Series Obstruction Light utilizes a uniqueoptical, electrical, and mechanical design. The RTSeries is the most universal, compact, and efficientobstruction light in the world. ETL Certified to FAArequirements, the RT Series fixture is also ICAO andTransport Canada compliant. Also available as a singlefixture for direct replacement of incandescent lamp/lens technology. C voltage version is perfect for use with our SOLDSeries of solar systems for a completely maintenancefree obstruction light system with absolutely no energycosts.PATENTS PENDINGNOTE: Ask about our solar powered obstruction lights.16

Obstruction Lights—LED General UsePHOTOMETRIC DATAMECHANICAL DIMENSIONSRetrofit UnitSingle Fixtureac power - ordering informationPart 0-240Obstruction fixture, single120-240VACRedFAARTLDF/120-240Obstruction fixture, double120-240VACRedFAAEOLRTL/120-240Retrofit OB fixture, single120-240VACRedFAAac power - weights and measuresShippingInput PowerContainerWeight(Nominal)Dimensions100-240VAC /- 10%1.25 lbs.6.5 W7.60" x 5.25" x 5.75"Single Unit100-240VAC /- 10%2.00 lbs.6.5 W7.60" x 5.25" x 5.75"Dual Unit100-240VAC /- 10%4.60 lbs.13.0 W18.60" x 12.50" x 6.40"ModelOperating VoltageRetro Unitdc power - ordering informationPart -48Obstruction fixture, single12-48VDCRedFAARTLDF/12-48Obstruction fixture, double12-48VDCRedFAAEOLRTL/12-48Retrofit OB fixture, single12-48VDCRedFAADc power - weights and measuresShippingInput 5 lbs.3.5 W7.60" x 5.25" x 5.75"Single Unit12-48VDC2.00 lbs.3.5 W7.60" x 5.25" x 5.75"Dual Unit12-48VDC4.60 lbs.7.0 W18.60" x 12.50" x 6.40"ModelOperating VoltageRetro Unit17

Obstruction Lights—LED General UseL810 GeNEral USELED OBSTRUCTION LIGHTCertified to: FAA AC NO: 150/5345-43GCompliant to: Canadian Aviation Regulation ICAO (Annex 14)Low intensity Type A (10cd)Low intensity Type B (32cd)VER IF I E DOrdering Information †Features/Benefits Available as a single or dual unitVoltage vailable in 12VDC, 24VDC, 48VDC, 120VAC, andA240VAC versions (50 or 60Hz)120VACOWLFSR/120OWLFDR/120240VACOWLFSR/240 ‡OWLFDR/240 ‡Earth grounding provisions provided12VDCOWLFSR/12OWLFDR/12 nique optically designed lens to enhance LEDUoperation and provide 360 FDR/24 eather/corrosion resistant lamp assemblyWand housingCatalog Numbering SYSTEM elf-contained wiring compartment eliminatesSadditional boxesO ObstructionS Single or D DualW Non Hazardous LocationR Red Threaded 1" and 3/4" bottom hub for mountingL Light Emitting Diode (LED)120, 240 Voltage AC an be operated steady or flashedC(controller not supplied)F FAA Type L81012, 24, 48 Voltage DCResistant to shock and vibration NEMA 4X rated and IP66† Standard product meets both 32cd and 10cd requirements‡ 240VAC lights are also available in 50cd and 10cd only. For 50cd only, remove “F”from catalog number and add “ICAO50CD” to end. For 10cd only remove “F” fromcatalog number and add “ICAO10CD to end. Ex. OWLSR/240 ICAO50CDApplication he Cooper Crouse-Hinds LED ObstructionTlight is a type FAA L810 red obstruction light.Designed for steady burning, this fixture is usedto mark any obstacle that may present hazardsto aircraft navigation.Specifications Dual FixtureState-of-the-art high-flux LED technology Single Fixture perating Temperature: -67 F to 131 FO(-55 C to 55 C)Finish Cast aluminum housing Stainless steel hardware18

Obstruction Lights—LED General UsePHOTOMETRIC DATAMECHANICAL DIMENSIONSL810 Isotropic Intensity Chart60.0-80.0Lens 0-20.01050(9.75") 247.7mmREFVertical 79") 147mmREF-1590 135 180 225 270 315Horizontal Angle (deg)(15.54") 394.6mmREFWeights & MeasurementsPart NumberApprox. Shipping WeightContainer DimensionsSingle Unit7.1 lbs16" x 9" x 8"Dual Unit16.1 lbs22" x 17" x 9"PFElectrical SpecificationsOPERATING VOLTAGEVAWATTS (W)MinTypMaxMinTypMaxAMPS120VAC UNITS.346.5921201321015180.120240VAC UNITS (60Hz).17721982402641115180.120240VAC UNITS (50Hz)––198240264121417–12VDC UNITS (STANDARD)––1012142025292.00024VDC UNITS––2124271722290.92048VDC UNITS––4348531114160.27519

Obstruction Lights—LED Class I, Division 2L810 Class I, division 2LED OBSTRUCTION LIGHTSuitable for Use in Hazardous AreasETL Listed in compliance with UL1598 and UL844for use in Class I, Div 2 Hazardous LocationsCertified to: FAA AC NO: 150/5345-43GCompliant to: ICAO (Annex 14)Type A or Type BVER IF I E DOrdering InformationFeatures/Benefits Available as a single or dual unitVoltageSingle FixtureDual FixtureColor uitable for all Class I, Div 2, Groups A, B, C, DShazardous environments, T4 240OX2LFDR/240Red nique optically designed lens to enhance LEDUoperation and provide 360 visibilityCatalog Numbering SYSTEMUp to 100,000 hours of service life eather/corrosion resistant lamp assemblyWand housingO elf-contained wiring compartment eliminatesSadditional boxesThreaded 1" and 3/4" bottom hub for mounting an be operated steady or flashedC(controller not supplied) Resistant to shock and vibration NEMA 4X rated and IP66 Available in 120VAC and 240VAC (50 or 60Hz) Energy efficient LED technologyX2 H azardous LocationClass I, Div 2R RedL Light EmittingDiode (LED)12, 24, 48 Voltage DCF FAA Type L810 Cast aluminum housing and stainless steel hardware. Electrostatically applied powdercoat of aviation orange paint. he Cooper Crouse-Hinds Obstruction Light isTan LED based Class I, Division 2 certified fixture.Used to mark obstructions on structures inhazardous environments, these fixtures providea valuable solution to facilities in demanding anddangerous environments.Operating Conditions 120, 240 Voltage ACFinishApplication S Single or D DualObstruction he fixture is designed for severe duty conditions andThazardous environments. emperatures ranging from -67 F to 131 F (-55 C toT 55 C). Will withstand wind in excess of 150 mph(240 kph), salt fog.20

Obstruction Lights—LED Class I, Division 2PHOTOMETRIC DATAMECHANICAL DIMENSIONSL810 Isotropic Intensity 0-20.0Lens Assembly105011.21[284.6]REFVertical 4.21[360.8]-5045Dual WireHousingBI-DIRECTIONALWIRE HOUSING-10-1590 135 180 225 270 3155.79 [147]REFHorizontal Angle (deg)15.54 [394.7]Dimensions are in inches (mm)Weights & MeasurementsPart NumberApprox. Shipping WeightContainer DimensionsSingle Unit7.1 lbs16" x 9" x 8"Dual Unit16.1 lbs22" x 17" x 9"PFElectrical SpecificationsOPERATING VOLTAGEVAWATTS (W)MinTypMaxMinTypMax120VAC UNITS0.36592120132101518240VAC UNITS (60Hz)0.272198240264111518240VAC UNITS (50Hz)0.27319824026412131721

Obstruction Lights—LED ATEX CertifiedL810 HazardousLocation Atex CertifiedLED OBSTRUCTION LIGHTSuitable for Use in Hazardous AreasCertified to:I I 3GEx nA IIC T4Compliant to: ICAO (Annex 14)Low IntensityType A or Type BFeatures/Benefits Ordering Information ATEX CERTIFIED PRODUCTI nherent safety capability; low electrical/thermalenergy and high light output nique optically designed lens to enhance LEDUoperation and provide 360 visibilityVoltageSingle FixtureDual 40VACVALSR/240-ATEXVALDR/240-ATEXRed eather/corrosion resistant lamp assemblyWand housingCatalog Numbering SYSTEM elf-contained wiring compartment eliminatesSadditional boxesO Obstruction or V Visual SignalR Red an be operated steady or flashed (controllerCnot supplied)A ATEX Certified120, 240 Voltage ACL Light Emitting Diode (LED)-ATEX Available as a single or dual unitS Single D Dual Resistant to shock and vibration Threaded 1" and 3/4" bottom hub for mounting NEMA 4X rated and IP66 ED technology for extended life andLenergy efficiency Available in 120VAC and 240VAC T4 ratedApplication he Cooper Crouse-Hinds Visual Signal LightTis an LED based ATEX certified fixture. Usedfor visual indication in hazardous environments,providing a valuable solution to the petrochemicalindustry facilities.Operating Conditions Temperaturesranging from -67 F to 131 F (-55 C to 55 C). Willwithstand wind in excess of 150 mph (240 kph), salt fog.Finish Cast aluminum housing and stainless steel hardware. Electrostatically applied powdercoat of aviation orange paint.22

Obstruction Lights—LED ATEX CertifiedPHOTOMETRIC DATAMECHANICAL DIMENSIONSL810 Isotropic Intensity 0-20.0LensAssembly105011.21[284.6]REFVertical 4.21[360.8]Dual WireHousing-5BI-DIRECTIONALWIRE HOUSING-10045-1590 135 180 225 270 31515.54[394.7]5.79 [147]REFHorizontal Angle (deg)Dimensions are in inches (mm)Weights & MeasurementsPart NumberApprox. Shipping WeightContainer DimensionsSingle Unit7.1 lbs16" x 9" x 8"Dual Unit16.1 lbs22" x 17" x 9"PFElectrical SpecificationsOPERATING VOLTAGEVAWATTS (W)MinTypMaxMinTypMax120VAC UNITS0.36592120132101518240VAC UNITS (60Hz)0.272198240264111518240VAC UNITS (50Hz)0.27319824026412131723

Obstruction Lights—Incandescent General UseL810 GENERAL USEInCanDESCENTOBSTRUCTION LIGHTCertified to: FAA AC 150/5345-43Compliant to: FCC Rules and RegulationsCanadian Standards Association (CSA) ICAO (Annex 14)Low Intensity Type A or Type BCanadian Aviation RegulationCAR 621.9 (Transport Canada)REOL SERIESOrdering Information*Features/Benefits TL Certified to FAA (EOL with Red GlobeEand 116W, 130V Lamp(s) only) perates on 120 or 220-240V and 60 or 50HzOfrequency power supply when used withproper voltage lamp Threaded 1" hub for mounting Pre-wired leads Cast aluminum housing with yellow finish Globes with tether and clamp band R IF I E D Red fresnel glass globes for 360 visibility VELens Color:R RedG GreenB Blue ccepts traffic signal lamps with USA medium screwAbase and European E27 baseO-ring globe seal amp life 8,000 hours at 120V and 4,000 hours forL220-240V applicationsApplication Fixture Type:40940 Single, Bottom Entry50033 Single, Side Entry50021 Double, Bottom EntryY YellowC ClearLamp Type:No symbols mean lamp(s) not included116 116W130V10047-3100 or 10047-2993*100 116W230V10047-2145Note: Ground wire included as standard. No -GR suffix isrequired.*For replacement lamps, order 10047-3100. he EOL Series incandescent obstruction light is usedTfor nighttime obstruction marking of tall structuresthat may present hazards to air navigation. The EOL isdesigned for steady burning applications.MECHANICAL DIMENSIONSWeights & Measurements500335002140940ShippingWeight:4.0 lbs1.8 kg10.0 lbs4.5 kg3.0 lbs1.4 kgShippingVolume:0.4 cu ft0.011 cu m0.45 cu ft0.013 cu m0.4 cu ft0.011 cu 1.0(280)Dimensions are in inches (mm)248.8(224)

Obstruction Lights—Incandescent General UseL810 GENERAL USEIncandescentObstruction LightCompliant to: US Military Specification MIL-L-7830USAF ANA StandardsFCC Rules and RegulationsCanadian Standards Association (CSA) ICAO (Annex 14)Low Intensity Type A or Type BCanadian Aviation RegulationCAR 621.9 (Transport Canada)RVAW SERIESOrdering Information*Features/Benefits ompliant to US Military Specification MIL-L-7830 asCwell as USAF ANA Standards Red fresnel glass globes for 360 visibility Threaded bottom 1" hub for mounting Cast aluminum housing with natural finish Threaded globes ccepts traffic signal lamps with USA medium screwAbase and European E27 base perates on 120 or 220-240V and 60 or 50HzOfrequency power supply when used with propervoltage lampGasket for globe seal amp Life 8000 hours at 120V and 4000 hours forL220-240V applicationsOptional wire guards (-GG option)Application Fixture Type:43958 Single43961 Double43950A Double**Lamp Type:No Symbols Mean Lamp(s) Not Included116 116W 120V 10047-1577100 116W 230V 10047-2145Options:GG Wire Globe Guard(s): Factory Installed OnlyGR Ground Wire(s)* Other colored globes are available for non-obstructionlighting applications, (contact factory).** Includes brackets for lowering device.Cooper Crouse-Hinds also offers the complete ObstructionLight Lowering System (contact factory). he VAW Series incandescent obstruction light is usedTfor nighttime obstruction marking of tall structures thatmay present hazards to air navigation. The VAW isdesigned for steady burning applications.MECHANICAL DIMENSIONS439614395815.00(381)5.75(146)Weights & Measurements4396143958ShippingWeight:16.0 lbs1.4 kg8.0 lbs0.7 kgShippingVolume:1.4 cu ft0.04 cu m0.7 cu ft0.02 cu m14.13(359)13.38(340)Dimensions are in inches (mm)Application Note:FAA Advisory Circular 70/7460-1K ‘‘Obstruction Marking and Lighting,’’Chapter 12, paragraph 123.a advises that steady burning red lights shouldconform to FAA AC 150/5345-43 or Military Specification MIL-L-7830.25

26

Visual Signals27

Visual Signals—LED General UseGeneral useLED VISUALSIGNAL LIGHTUL 1598*Features/BenefitsApplication Available as a single or dual unit Available in 120VAC, 240VAC, 12/24/48VDC nique optically designed lens to enhance LEDUoperation and provide 360 visibility tate-of-the-art high-flux LED technology forSextended life and energy efficiency Uses 90% less energy than an incandescent Weather/corrosion resistant lamp assembly and housing Operating Conditions elf-contained wiring compartment eliminatesSadditional boxes Threaded 1" and 3/4" bottom hub for mounting Can be operated steady or flashed Resistant to shock and vibration NEMA 4X rated and IP66 he Cooper Crouse-Hinds Series Multi-Purpose LED Light fulfillsTthe needs of engineers and architects requiring a rugged, weatherproof fixture with color alternatives to the standard red obstructionlights. Available in green, yellow, blue and white, these fixturesare typically used as a continuous source to warn, communicate,or draw attention to an area, machine, or process. Truly the LEDsolution to your lighting challenges. Temperature: -67 F to 131 F (-55 C to 55 C)*UL 1598 pendingOrdering InformationSingle 0VWLDG/120VWLDG/240V