Hubbell Controls Application Guide To ASHRAE 90

Transcription

Hubbell Controls Application Guide to ASHRAE 90.1A S U P P L E M E N TA L G U I D E TO C O D E R E V I S I O N S I M PAC T I N G L I G H T I N G C O N T R O L

Hubbell Lighting’s Commitment to the ASHRAE 90.1 ChallengeHubbell Lightingunderstands the challenge of code compliance and is here to lessen this burden onend-users. On October 2016 ASHRAE 90.1 2016 Energy Standard for Buildings Except Low-Rise ResidentialBuildings was published. This revised standard improves energy efficiency in non-residential buildingsbeyond the previous ASHRAE 90.1 publication however, navigating the updated lighting code can be timeconsuming and confusing.By breaking down the latest changes to ASHRAE 90.1 by application space, Hubbell Lighting is able tosimplify the complexities of code compliance. On the following pages you will find product solutions for eachcontrols type based on application space and code requirements. These controls solutions range from themost basic solutions to the most advanced. The guidelines are focused on recent code revisions and are notintended to replace the complete ASHRAE 90.1 publication.The Hubbell AdvantageFor over 125 years Hubbell Lighting has continued to make the ordinary extraordinary as one of the largestlighting fixture manufacturers in North America. Serving a multitude of markets Hubbell Lighting aims to provideinnovative solutions that provide performance, quality, and ease of use regardless of the application. Supportedby the most prestigious portfolio of brand names Hubbell Lighting has a full range of indoor and outdoorlighting products that supply solutions to commercial, industrial, institutional, and residential markets.TABLE OF CONTENTSONE COMPANY DISTINCT BRANDSAlera Lighting4Hubbell’s Core Capabilities6Classroom / Lecture Hall / Training Room8Conference / Meeting / Multi-Purpose Room10Office 250 Sq. Ft.12Office 250 Sq. Ft.14Corridor16Restroom18Stairwell20Storage Room 1000 Sq. Ft.22NX Distributed Intelligence24PowerHUBB POE Lighting & Control26CX Commercial Lighting System27Occupancy Sensors28GlossaryArchitectural Area LightingBeacon ProductsColumbia LightingCompassDual-LiteHubbell Control SolutionsHealthcare SolutionsHubbell Industrial LightingHubbell Outdoor LightingKim LightingKurt VersenLitecontrolPrescoliteWhiteway

Hubbell Lighting Core Capabilities - Complete SolutionsStay on the leading edge of technology by selecting from Hubbell Lighting’s portfolioof solid-state lighting products.Complete SolutionsFrom beautiful commercial environments to complex industrial applications, Hubbell Lighting provides highperformance solutions across virtually every industry application.Outdoor SiteCanopyWallRecessedReducing MaintenanceEnergy savings is only part of the story.Solid-state LED solutions from HubbellLighting last up to 3 times longer than MetalHalide or Fluorescent sources and up to 60times longer than incandescent sources,dramatically reducing maintenance costs.IndustrialParking GaragePost TopHubbell Lighting ControlsHaving lights on only when needed, helps in reducing utility costs for energy savings and sustainability objectives.Easy installation, intuitive interfaces and web-based commissioning and monitoring make Hubbell Control Solutions(HCS) the logical choice for lighting control.Energy SavingsHubbell Lighting has broken the technology barriers to create cost effective, high performance LED luminaires thatcan save up to 70% in applications, replacing less efficient technologies such as HID or 1000400-Watt Metal Halide4HUBBELL LIGHTINGFluorescent T5 HOLEDREQUIRED RELAMPSvs. LEDIncandescent1,00060Compact Fluorescent10,0006Metal Halide20,0003Linear Fluorescent20,0003LED60,0000Control In ApplicationHubbell LED solutions provide instant restrike performance, that when combinedwith factory integrated controls, reduce energy usage by as much as 80% inapplication. It’s another innovative way we help meet fast evolving codes.Easy Install, Easy MaintenanceHubbell LED luminaires are designed withinstallation and ease of maintenance inmind. Our products offer simple accessto electrical components that will reduceinstallation time and costs while makingmaintenance quick and efficient.DownlightingLIFE IN HOURSLAMP TYPEElectronic TrackingIn the fast evolving LED space, componentperformance upgrades are ongoing. Toprovide best-in-class field support, we’reintegrating electronic tagging technologyacross our product lines, giving us a recordof all the spec details of your luminaire. Yearsafter installation a quick scan will reveal all ofthe critical specification details our teams willneed to provide superior service and support.Environmentally FriendlyWith no mercury, unlike HID or fluorescenttechnologies, Hubbell Lighting LED luminaries requireno lamp recycling and dramatically reduce CO2emissions when replacing legacy technologies.Rebate Program ApprovedUtility rebate programs, where available, usually requireproducts to be Design Lights Consortium (DLC) or ENERGYSTAR qualified. Hubbell Lighting maintains an extensivecollections of DLC and ENERGY STAR qualified productsavailable to reduce project costs and quicken payback.For a complete listing, visit change

Classroom / Lecture Hall / Training RoomCodeProvisionON/OFF CONTROLSMinimumControl TypeRequirementsBasic(Choice of)Intermediate(Choice of)Advanced9.4.1.1(a)Local switchReadily accessible device(s) to controllighting within an enclosed space. OMNI Ceiling Sensor & Override Switch LightHAWK2 Wall Switch Sensor NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & Control9.4.1.1(b, c)and 9.4.1.1(h)Occupancy sensorManual On - AutoOff or AutomaticPartial On - AutoOffPartial On no more the 50% of full lightoutput. Automatically shuts off lightingpower after vacancy of 20 minutes or less OMNI Ceiling Sensor & Override Switch LightHAWK2 Wall Switch Sensor NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & Control9.4.1.1.(d)Bi-level lightingcontrol minimumAt least one intermediate step shall bebetween 30% and 70% (inclusive) of fulllighting power. OMNI Ceiling Sensor & Override Switch LightHAWK2 Wall Switch Sensor NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & ControlMulti-level daylightcontrolSensor to reduce lighting in response toavailable daylight when daylight area is150W or greater. Daylight areas definedin definitions. Control points between 20-40% and 50-70% In addition to off.Primary daylight zones must be controlledseparately from secondary zones. NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & ControlFunctional testingTesting shall ensure that occupantsensors, time switches, programmableschedule controls, and photo sensors arecalibrated, programmed, and functioningproperly. NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & ControlReceptacle controlAutomatically turn OFF at least 50% of thereceptacles in the space. This can eitherbe achieved by switching every alternatereceptacle or 50% of the outlets in eachreceptacle NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & ControlLIGHT LEVELCONTROL9.4.1.1(e, f)9.4.3ADDITIONALCONTROL8.4.2 OMNI Ceiling Sensor & Override SwitchNOTE: Alterations of more than 20% and not a one-to-one replacement or only replacement of lamp and ballast/driver mustmeet the above control requirements in this space type.6HUBBELL LIGHTINGHUBBELL LIGHTING7

Conference / Meeting / Multi-Purpose RoomCodeProvisionON/OFF CONTROLSMinimumControl TypeIntermediate(Choice of)AdvancedLocal switchReadily accessible device(s) to controllighting within an enclosed space. OMNI Ceiling Sensor & Override Switch LightHAWK2 Wall Switch Sensor NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & Control9.4.1.1(b, c)and 9.4.1.1(h)Occupancy sensorManual On - AutoOff or AutomaticPartial On - AutoOffPartial On no more the 50% of full lightoutput. Automatically shuts off lightingpower after vacancy of 20 minutes orless. OMNI Ceiling Sensor & Override Switch LightHAWK2 Wall Switch Sensor NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & Control9.4.1.1.(d)Bi-level lightingcontrol minimumAt least one intermediate step shall bebetween 30% and 70% (inclusive) of fulllighting power. OMNI Ceiling Sensor & Override Switch NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & ControlMulti-level daylightcontrolSensor to reduce lighting in response toavailable daylight when daylight area is150W or greater. Daylight areas definedin definitions. Control points between20 -40% and 50-70% In addition to off.Primary daylight zones must be controlledseparately from secondary zones. NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & ControlFunctional testingTesting shall ensure that occupantsensors, time switches, programmableschedule controls, and photo sensors arecalibrated, programmed, and functioningproperly. NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & ControlReceptacle ControlAutomatically turn OFF at least 50% of thereceptacles in the space. This can eitherbe achieved by switching every alternatereceptacle or 50% of the outlets in eachreceptacle. NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & ControlCONTROL9.4.1.1(e, f)9.4.3ADDITIONALCONTROL8.4.2HUBBELL LIGHTING(Choice of)9.4.1.1(a)LIGHT LEVEL8BasicRequirementsHUBBELL LIGHTING OMNI Ceiling Sensor & Override Switch LightHAWK2 Wall Switch Sensor8HUBBELL LIGHTING9

Office 250 Sq. Ft.CodeProvisionON/OFF CONTROLSMinimumControl TypeRequirementsBasic(Choice of)Intermediate(Choice of)Advanced9.4.1.1(a)Local switchReadily accessible device(s) to controllighting within an enclosed space. OMNI Ceiling Sensor & Override Switch LightHAWK2 Wall Switch Sensor NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & Control9.4.1.1(b, c)and 9.4.1.1(h)Occupancy sensorManual On - AutoOff or AutomaticPartial On - AutoOffPartial On no more the 50% of full lightoutput. Automatically shuts off lightingpower after vacancy of 20 minutes orless. OMNI Ceiling Sensor & Override Switch LightHAWK2 Wall Switch Sensor NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & Control9.4.1.1.(d)Bi-level lightingControlAt least one intermediate step shall bebetween 30% and 70% (inclusive) of fulllighting power. OMNI Ceiling Sensor & Override Switch LightHAWK2 Wall Switch Sensor NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & ControlMulti-level daylightcontrolSensor to reduce lighting in response toavailable daylight when daylight area is150W or greater. Daylight areas definedin definitions. Control points between20 -40% and 50-70% In addition to off.Primary daylight zones must be controlledseparately from secondary zones. NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & ControlFunctional testingTesting shall ensure that occupantsensors, time switches, programmableschedule controls, and photosensors arecalibrated, programmed, and functioningproperly. NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & ControlReceptacle controlAutomatically turn OFF at least 50% of thereceptacles in the space. This can eitherbe achieved by switching every alternatereceptacle or 50% of the outlets in eachreceptacle NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & ControlLIGHT LEVELCONTROL9.4.1.1(e, f)9.4.3ADDITIONALCONTROL8.4.2 OMNI Ceiling Sensor & Override Switch LightHAWK2 Wall Switch SensorNOTE: Alterations of more than 20% and not a one-to-one replacement or only replacement of lamp and ballast/driver mustmeet the above control requirements in this space type.10HUBBELL LIGHTINGHUBBELL LIGHTING11

Office 250 Sq. Ft.CodeProvisionMinimumControl TypeRequirements9.4.1.1(a)Local switchReadily accessible device(s) to controllighting within an enclosed space.9.4.1.1(b) and9.4.1.1(i)Manual On- ProgrammableTimeclock OffScheduled time-of-day operated controlthat turns lighting off at specified timeswhen typically unoccupied. Other buildingsystem signals that turn OFF lights duringvacancy also comply.9.4.1.1(b,c)and 9.4.1.1(h)Occupancy sensorManual On - AutoOff or AutomaticPartial On - AutoOffPartial On no more the 50% of full lightoutput. Automatically shuts off lightingpower after vacancy of 20 minutes orless.9.4.1.1.(d)Bi-level lightingcontrolAt least one intermediate step shall bebetween 30% and 70% (inclusive) of fulllighting power,Multi-level daylightcontrolSensor to reduce lighting in response toavailable daylight when daylight area is150W or greater. Daylight areas definedin definitions. Control points between20 -40% and 50-70% In addition to off.Primary daylight zones must be controlledseparately from secondary zones.Functional testingTesting shall ensure that occupantsensors, time switches, programmableschedule controls, and photosensors arecalibrated, programmed, and functioningproperly.Receptacle controlAutomatically turn OFF at least 50% of thereceptacles in the space. This can eitherbe achieved by switching every alternatereceptacle or 50% of the outlets in eachreceptacleON/OFF CONTROLSBasic(Choice of)Intermediate(Choice of)Advanced NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & Control NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & Control OMNI Ceiling Sensor & Override Switch NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & Control OMNI Ceiling Sensor & Override Switch NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & Control NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & Control NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & Control NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & Control OMNI Ceiling Sensor & Override SwitchORLIGHT LEVELCONTROL9.4.1.1(e, f)9.4.3ADDITIONALCONTROL8.4.2 OMNI Ceiling Sensor & Override SwitchNOTE: Alterations of more than 20% and not a one-to-one replacement or only replacement of lamp and ballast/driver mustmeet the above control requirements in this space type.12HUBBELL LIGHTINGHUBBELL LIGHTING13

CorridorCodeProvisionMinimumControl TypeRequirementBasic(Choice of)Intermediate(Choice of)Advanced9.4.1.1(a)Local switchReadily accessible device(s) to controllighting within an enclosed space. OMNI Ceiling Sensor & Override Switch NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & Control9.4.1.1(h)Vacancy sensorAutomatic OffAutomatically shuts off lighting powerafter vacancy of 20 minutes or less OMNI Ceiling Sensor & Override Switch NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & Control9.4.1.1(i)ProgrammableTimeclock OffScheduled time-of-day operated controlthat turns lighting off at specified timeswhen typically unoccupied. Other buildingsystem signals that turn OFF lights duringvacancy also comply. NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & Control9.4.1.1(g)Occupancy sensorAutomatic PartialOffAutomatically reduces lighting power by atleast 50% after vacancy of 20 minutes orless. NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & ControlMulti-level daylightcontrolSensor to reduce lighting in response toavailable daylight when daylight area is150W or greater. Daylight areas definedin definitions. Control points between20-40% and 50-70% in addition to off.Primary daylight zones must be controlledseparately from secondary zones. NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & ControlFunctional testingTesting shall ensure that occupant sensors,time switches, programmable schedulecontrols, and photo sensors are calibrated,programmed, and functioning properly. NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & ControlORON/OFFCONTROLSLIGHT LEVELCONTROLADDITIONALCONTROL9.4.1.1(e, f)9.4.3 OMNI Ceiling Sensor & Override SwitchNOTE: Alterations of more than 20% and not a one-to-one replacement or only replacement of lamp and ballast/driver mustmeet the above control requirements in this space type.14HUBBELL LIGHTINGHUBBELL LIGHTING15

RestroomCodeProvisionON/OFFCONTROLSLIGHT LEVELCONTROLADDITIONALCONTROL9.4.1.1(h)9.4.1.1(e, f)9.4.3MinimumControl TypeRequirementVacancy sensorAutomatic OffAutomatically shuts off lighting powerafter vacancy of 20 minutes or lessMulti-level daylightcontrolSensor to reduce lighting in responseto available daylight when daylightarea is 150W or greater. Daylightareas defined in definitions. Controlpoints between 20 -40% and 50-70%In addition to off. Primary daylightzones must be controlled separatelyfrom secondary zonesAcceptance testingFunctional testingTesting shall ensure that occupantsensors, time switches, programmableschedule controls, and photosensorsare calibrated, programmed, andfunctioning properly.Basic(Choice of) OMNI Ceiling Sensor & Override Switch OMNI Ceiling Sensor & Override SwitchIntermediate(Choice of)Advanced NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & Control NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & Control NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & ControlNOTE: Alterations of more than 20% and not a one-to-one replacement or only replacement of lamp and ballast/driver mustmeet the above control requirements in this space type.16HUBBELL LIGHTINGHUBBELL LIGHTING17

StairwellCodeProvisionMinimumControl TypeRequirementsVacancy sensorAutomatic OffAutomatically shuts off lighting powerafter vacancy of 20 minutes or less9.4.1.1(i)ProgrammableTimeclock OffScheduled time-of-day operated controlthat turns lighting off at specified timeswhen typically unoccupied. Other buildingsystem signals that turn OFF lights duringvacancy also comply.9.4.1.1(g)Occupancy sensorAutomatic PartialOffAutomatically reduces lighting power byat least 50% after vacancy of 20 minutesor less.9.4.1.1.(d)Bi-level lightingcontrol9.4.1.1(h)Basic(Choice of)Intermediate(Choice of)Advanced NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & Control NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & Control NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & ControlAt least one intermediate step shall bebetween 30% and 70% (inclusive) of fulllighting power NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & ControlMulti-level daylightcontrolSensor to reduce lighting in response toavailable daylight when daylight area is150W or greater. Daylight areas definedin definitions. Control points between20 -40% and 50-70% In addition to off.Primary daylight zones must be controlledseparately from secondary zones NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & ControlFunctional testingTesting shall ensure that occupantsensors, time switches, programmableschedule controls, and photosensors arecalibrated, programmed, and functioningproperly. NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & Control OMNI Ceiling Sensor & Override SwitchORON/OFF CONTROLSLIGHT LEVELCONTROL9.4.1.1(e, f)ADDITIONALCONTROL18HUBBELL LIGHTING8.4.2 OMNI Ceiling Sensor & Override Switch OMNI Ceiling Sensor & Override SwitchNOTE: Alterations of more than 20% and not a one-to-one replacement or only replacement of lamp and ballast/driver mustmeet the above control requirements in this space type.HUBBELL LIGHTING19

Storage Room 1000 Sq. Ft.CodeProvisionON/OFF CONTROLSLIGHT LEVELCONTROLADDITIONALCONTROLMinimumControl TypeRequirements9.4.1.1(a)Local switchReadily accessible device(s) to controllighting within an enclosed space.9.4.1.1(b, c)and 9.4.1.1(h)Occupancy sensorManual On - AutoOff or AutomaticPartial On - AutoOff9.4.1.1(e, f)9.4.3Basic(Choice of)Intermediate(Choice of)Advanced NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & ControlPartial On no more the 50% of full lightoutput. Automatically shuts off lightingpower after vacancy of 20 minutes orless. NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & ControlMulti-level daylightcontrolSensor to reduce lighting in response toavailable daylight when daylight area is150W or greater. Daylight areas definedin definitions. Control points between20 -40% and 50-70% In addition to off.Primary daylight zones must be controlledseparately from secondary zones. NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & ControlFunctional testingTesting shall ensure that occupantsensors, time switches, programmableschedule controls, and photosensors arecalibrated, programmed, and functioningproperly. NX Room Control CX Panel Controls NX Distributed Intelligence PowerHUBB PoE Lighting & Control LightHAWK2 Wall Switch SensorNOTE: Alterations of more than 20% and not a one-to-one replacement or only replacement of lamp and ballast/driver mustmeet the above control requirements in this space type.20HUBBELL LIGHTINGHUBBELL LIGHTING21

NX DISTRIBUTED INTELLIGENCENX plaform is capable of scaling from standalone fixture and room control applications to networked enterprise deployments.NX operates using wired, wireless and hybrid connectivity with native BACnet support.Device Setup AppIn-Fixture ControlsIn-Fixture Control Modules On / Off control and/or twochannel dimmingSuitable for indoor andoutdoor applicationsWireless programmingIn-Fixture Sensor Modules Luminaire-integrated designreduces complexity and designtime Out-of-the-box operation to meetcode and simplify installation Bluetooth enabled sensorsavailable in five versions toaddress occupancy and daylightdimmingNX Radio Modules Provide HubbNETTM wirelessnetwork communication Robust and reliable IEEE802.15.4 2.4GHz radio Remote, in-fixture andon-fixture mounting optionsThe NX Device Setup App provides Bluetooth wireless setup and configuration of NX RoomControl devices and luminaires equipped withan NX In-Fixture module with smart sensor.The mobile App is available in Android andiOS versions for free download from GooglePlay or Apple stores.Accessories Provide dual RJ45 ports forCAT5 daisy-chain connections Offer dual, mini SmartPORT connections for In-Fixturemodules Simple attachment to luminairesIntelliscopeTMIntelliscope provides a unique and powerfultool for calibrating and testing NX In-Fixturesmart sensors. Motion captured by the sensoris displayed in real time relative to the currentsensitivity setting making precise calibrationpossible without the need for repetitive “testmode” trial and error calibration.Room ControlsWall Switch StationsRoom ControllersOccupancy Sensors Intelligent auto-configurationwith devices Automatic code compliance Cat5 plug and play connectivity Embedded IntelliDAPT self-adaptive technology Passive Infrared, Ultrasonic andDual Technology versions Occupancy or vacancy modewith up to 2000 sq. ft. coverageareaDaylight Sensors Open-loop daylighting controls Supports up to 6 lightingzones per room Simple setup using the NXmobile AppSingle and multi-button wall switch stationsare available in specialty pre-configured andprogrammable smart versions. Both offer a selfconfiguration feature that automatically configuresthe wall switch stations to perform the logicalcontrol and code compliant sequence of operation.All NX wall switch stations can be used with RoomControllers, Panels, or In-Fixture Modules in eitherstandalone or networked applications.Interfaces Allow third party interfaces Support A/V, Dry Contacts andHVAC options Mounts to standard junction boxor DIN railEnterprise / Building ControlsArea ControllerArea Controllers Central component forenterprise solutions Real-time programming andmonitoring Native BACnet supportNetwork BridgeNetwork AccessoriesLighting Control Panels Connect Room Controllers toHubbNET network Provide communication link forArea Controllers CAT5 plug and play connectivity Enable connection of additionalNX devices Provide network connectionsand power to NX accessories Mount to standard DIN rail Provides programmableswitching and dimming oflighting circuits Can be used exclusively or aspart of a network solution Available in 8, 16, 24, 32 and 48relay versionsThese are the key components. For a full list of NX products please visit www.hubbellcontrolsolutions.com.22HUBBELL LIGHTINGThe NX Area Controller is the central componentin an enterprise or building networked system. Theinterface is web browser based and does not requirethe installation of any software. A native BACnet interface facilitates a standard TCP/IP connectionproviding monitoring and control of lighting by theBuilding Automation System.These are the key components. For a full list of NX products please visit www.hubbellcontrolsolutions.com.HUBBELL LIGHTING23

POWERHUBB POE LIGHTING & CONTROLHubbell’s PowerHUBB is an enterprise-level, Power over Ethernet (PoE), lighting and control platform that seamlessly integrates luminaires,sensors, user interfaces and software for a scalable, intelligent building control solution.PowerHUBB NodesPowerHUBB's scalable software suite provides configurable options for delivering advanced customized energy saving strategies, buildingautomation integration, and enablement of IoT solutions.From simple lighting control to advanced cloud based energy management analytics, PowerHUBB empowers your lighting to deliver valuebeyond illumination with a data driven, open platform. Provide power distribution and data connectivity for luminairesand control devices RJ45 ports provided for PoE power and bidirectional Input/Output (I/O) connections 1% to 100% dimming range in 1% increments 60W peak operating power External sensor/relay and wall switch connectionsLIGHTING CONTROL SOFTWARE SUITEStandard Lighting Control Software PackageStandard Lighting Control Software Low Voltage SensorsSupports lights, wall controls On/Off/Dim, motion sensors, and daylight sensorsLighting system commissioning, rapid-commissioning, and diagnostic toolsOccupancy control (software-defined)High and low end trimming (software-defined)Daylight harvesting (software-defined)Lighting schedulingADVANCED SOFTWARE SERVICE PACKAGESOMNI ConnectivityOccupancy/Vacancy Wall Mount Sensor Passive Infrared (PIR), Ultrasonic (US) and Dual Technology (DT) versions Proprietary IntelliDAPT Technology eliminates false triggers Optional relay and photocell control API access and test suite Multi-IP network binding managementAutomation AccessLightOWL Occupancy/Vacancy Wall Mount Sensor PIR and DT versions Smart IntelliDAPT Technology eliminates false triggers Optional relay and photocell control DT offered in both US with PIR and US with Acoustic SensorService PackageService (via cloud portal) LightHAWK 2Occupancy/Vacancy Wall Switch Sensor PIR, US and DT versions Manual-ON (Vacancy Sensor) or Automatic-ON (Occupancy Sensor) Smart IntelliDAPT Technology eliminates false triggers Built-in photo sensor for automatic daylight harvesting Single or Dual relay Accepts BACnet commands and inquiries Supports temperature sensorsNear real-time system monitoringSystem status, analytics, statistics, and dashboardsAdvanced multi-recipient email alerts for critical system statusDaily backups of configurationAdvanced Energy* (via cloud portal)Advanced Energy Package* Energy analytics, statistics, dashboards, and interactive reports Energy data repositoryEnterprise Management* (via cloud portal) Multi-site enterprise performance and service dashboards Advanced log dashboard and analyzer Multi-user multi-role cloud portal loginsLow Voltage Wall Stations Supported by I/O connections on PowerHUBB nodes Offered in 1, 2, 3 and 4 button configurations Momentary button action Optional LED indicators available 24 VDC low voltage device24HUBBELL LIGHTING*Service Package RequiredEnterprise Management Package*HUBBELL LIGHTING25

WASP2 AND DIMMING WASP Indoor and outdoor occupancy and photocell sensors for on/off or preset dimmedWASP2 Occupancy and Photocell Sensor Digital Passive Infrared (PIR) sensorMultiple (single and dual) output versionsUnique Smart Cycling for improved fluorescent lamp lifeInterchangeable high/low mount detection lens optionsLow voltage and line voltage models availableFactory Installed & Field Installed Options AvailableDimming WASP Outdoor Motion and Photocell SensorCX COMMERCIAL LIGHTING SYSTEMFeature rich, cost effective lighting control system for switching and 0-10V dimming.CX 8 RELAY MASTER PANEL WITH DIMMING CARD 8 dimming channels 8 - 20AMP relays with 4 relay options - 20A/1P, N/O, 20A/2P, N/O, N/C (14K SSCR)and 30A/1P latching (18K SCCR) Color LCD user interface with keypad 365 day programming with 64 schedules Astronomical and real time clock

Hubbell Controls Application Guide to ASHRAE 90.1 A SUPPLEMENTAL GUIDE TO CODE REVISIONS IMPACTING LIGHTING CONTROL. Hubbell Lighting understands the challenge of code compliance and is here to lessen this burden on end-users. On October 2016 ASHRAE 90.1 2016 Energy Standard for Building