DESENFUMAGEM (CONTROLO DEFUMO) EM EDIFÍCIOS DE GRANDEEXTENSÃO.MIGUEL ALEXANDRE PINELO FERNANDESRelatório de Projecto submetido para satisfação parcial dos requisitos do grau deMESTRE EM ENGENHARIA CIVIL — ESPECIALIZAÇÃO EM CONSTRUÇÕES CIVISOrientador: Professor Doutor João Lopes PortoJULHO DE 2008

Desenfumagem (Controlo de Fumo) em Edifícios de grande ExtensãoMESTRADO INTEGRADO EM ENGENHARIA CIVIL 2007/2008DEPARTAMENTO DE ENGENHARIA CIVILTel. 351-22-508 1901Fax 351-22-508 1446 miec@fe.up.ptEditado porFACULDADE DE ENGENHARIA DA UNIVERSIDADE DO PORTORua Dr. Roberto Frias4200-465 PORTOPortugalTel. 351-22-508 1400Fax 351-22-508 1440 feup@fe.up.pt http://www.fe.up.ptReproduções parciais deste documento serão autorizadas na condição que sejamencionado o Autor e feita referência a Mestrado Integrado em Engenharia Civil 2007/2008 - Departamento de Engenharia Civil, Faculdade de Engenharia daUniversidade do Porto, Porto, Portugal, 2008.As opiniões e informações incluídas neste documento representam unicamente oponto de vista do respectivo Autor, não podendo o Editor aceitar qualquerresponsabilidade legal ou outra em relação a erros ou omissões que possam existir.Este documento foi produzido a partir de versão electrónica fornecida pelo respectivoAutor.

À Família.«Os humildes são como a pedra:está no chão mas é sólida.Os orgulhosos são como o fumo:é alto mas dissipa-se.»Santo Agostinho

Desenfumagem (Controlo de Fumo) em Edifícios de grande ExtensãoAGRADECIMENTOSAo longo da execução deste trabalho senti de forma muito clara alguns apoios e estímulos que melevam agora a deixar aqui os meus sinceros agradecimentos.Ao meu orientador Professor João Lopes Porto agradeço profundamente o seu constante apoio, aenorme disponibilidade demonstrada para o esclarecimento de dúvidas e dificuldades relativas aocaminho a seguir. Não posso esquecer os diálogos científicos que me proporcionou e o quanto comeles aprendi.Aos meus Pais por todo o carinho, amizade e por todas as condições que me proporcionaram parapoder realizar este trabalho da melhor forma.À minha irmã pelo ânimo e apoio constantes.A todos os meus amigos pelo apoio imprescindível com que me brindaram nos momentos de maiordesalento.

RESUMODurante a ocorrência de um incêndio a produção de fumo e a sua consequente propagação, dadas assuas características físicas e químicas, gera um ambiente adverso à permanência dos ocupantes doedifício e aos bombeiros na acção de combate ao incêndio. O escoamento do fumo no interior doedifício pode atingir num curto período de tempo locais afastados do espaço de origem do incêndio,ameaçando as vidas humanas presentes no edifício, devido ao risco de inalação de fumo.O controlo de fumo, através de métodos adequados e disposições construtivas apropriadas, constituium procedimento fulcral, para que numa fase inicial do incêndio, se possam evitar vítimas humanas ereduzir danos materiais, na medida em que se facilita por um lado a evacuação dos ocupantes e poroutro a intervenção e acção das entidades responsáveis pelo combate ao incêndio.Neste trabalho são abordados os métodos de controlo do escoamento do fumo em edifícios, bem comoas medidas exigidas pelo projecto de Regulamento Geral de Segurança Contra Incêndio em Edifícios(RG - SCIE), para garantia de segurança face à libertação de fumo em caso de ocorrência de umincêndio no interior de um edifício. É ainda realizada a aplicação prática do controlo de fumo(desenfumagem) a um edifício industrial de grande extensão.PALAVRAS-CHAVE: FUMO, CONTROLO, DESENFUMAGEM, EVACUAÇÃO, SEGURANÇA.

Desenfumagem (Controlo de Fumo) em Edifícios de grande ExtensãoABSTRACTDuring the occurrence of a fire the produce of smoke and the consequent spread due to its physical andchemical characteristics, develops a hostile environment for the building users and firefighters inaction.The smoke often flows inside the building to locations remote from the fire in a short period of time,threatening human lives due to of the risk of inhalation of smoke.The smoke control by adequate methods and constructive measures is a key procedure so that at anearly stage of the fire, can prevent human victims and reduce property damage, because it will makeevacuation of occupants and action of firefighters easier.In this text the smoke control in buildings is analysed and the implementation of techniques tobuildings required by the RG – SCIE (regulation general against fire in buildings) is detailed.Lastly, is made a practical application of the control of smoke (smoke exhaustion) to an industrialbuilding of great extension.KEYWORDS: SMOKE, CONTROL, SMOKE EXHAUSTION, EVACUATION, SECURITY.

ÍNDICE GERALAGRADECIMENTOS . iRESUMO . iiiABSTRACT . v1. INTRODUÇÃO .11.1. INCÊNDIOS EM EDIFÍCIOS .11.2. FUMO EM EDIFÍCIOS .21.3. OBJECTIVOS DO CONTROLO DE FUMO EM EDIFÍCIOS .51.4. CAUSAS DOS INCÊNDIOS .61.5. CARACTERIZAÇÃO DA CAMADA DE FUMO .71.6. DOMÍNIO DE APLICAÇÃO DO PROJECTO DE REGULAMENTO GERAL DE SEGURANÇA CONTRAINCÊNDIOS EM EDIFÍCIOS (RG – SCIE) .102. MÉTODOS DE CONTROLO DE FUMO .133. VARRIMENTO PASSIVO .153.1. EFEITO CHAMINÉ .153.2. ENTRADAS DE AR FRESCO .183.3. SAÍDAS DE FUMO .193.4. ABORDAGEM AO PROJECTO DE RG – SCIE .203.4.1. ADMISSÃO DE AR .203.4.2. EVACUAÇÃO DE FUMO .203.4.3. CONTROLO DE FUMO NOS PÁTIOS E PISOS OU VIAS CIRCUNDANTES .213.4.4. CONTROLO DE FUMO NOS LOCAIS SINISTRADOS .213.4.5. CONTROLO DE FUMO NAS VIAS HORIZONATAIS DE EVACUAÇÃO .223.4.6. CONTROLO DE FUMO NAS VIAS VERTICAIS DE EVACUAÇÃO.223.5. CARACTERIZAÇÃO DOS LOCAIS .233.6. EQUIPAMENTOS DE CONTROLO DE FUMO .243.6.1. BARREIRAS DE CANTONAMENTO .243.6.2. EXUTORES DE FUMO E VÃOS DE FACHADA .303.6.3. GRELHAS, BOCAS E CONDUTAS PARA ADMISSÃO DE AR E EXTRACÇÃO DE FUMO .343.7. CÁLCULO DA ÁREA ÚTIL DA INSTALAÇÃO .363.7.1. EDIFÍCIOS INDUSTRIAIS .40

Desenfumagem (Controlo de Fumo) em Edifícios de grande Extensão3.7.2. EDIFÍCIOS RECEBENDO PÚBLICO . 423.8. MONTAGEM E COMANDO DE EXUTORES DE FUMO E VÃOS DE FACHADA . 433.8.1. MONTAGEM DE EXUTORES E VÃOS DE FACHADA . 433.8.2. COMANDO DE EXUTORES E VÃOS DE FACHADA . 453.8.2.1. Comando mecânico. 463.8.2.2. Comando electromagnético. 473.8.2.3. Comando eléctrico. 473.8.2.4. Comando electrónico. 483.8.2.5. Comando pneumático . 493.8.2.6. Comando hidráulico. 493.8.2.7. Análise final dos sistemas de comando . 493.9. CONCLUSÕES . 504. VARRIMENTO ACTIVO . 514.1. INTRODUÇÃO AO MÉTODO . 514.2. CONTROLO DE FUMO ACTIVO COM PRESSURIZAÇÃO . 514.3. ABORDAGEM AO PROJECTO DE RG – SCIE . 524.3.1. ENTRADAS DE AR . 524.3.2. DIMENSIONAMENTO . 524.3.3. COMANDO DAS INSTALAÇÕES. 524.3.4. CONTROLO DE FUMO NOS PÁTIOS INTERIORES E PISOS OU VIAS CIRCUNDANTES . 524.3.5. CONTROLO DE FUMO NOS LOCAIS SINISTRADOS . 524.3.6. CONTROLO DE FUMO NAS VIAS HORIZONTAIS DE EVACUAÇÃO . 534.3.7. CONTROLO DE FUMO NAS VIAS VERTICAIS DE EVACUAÇÃO . 534.4. CARACTERIZAÇÃO DOS LOCAIS . 534.5. EQUIPAMENTOS DE CONTROLO ACTIVO DE FUMO . 534.6. DIMENSIONAMENTO DE SISTEMAS DE CONTROLO ACTIVO DE FUMO . 554.6.1. ENTRADAS DE AR . 554.6.2. SAÍDAS DE FUMO . 554.6.3. CAUDAIS DE AR E FUMO . 554.6.4. BOCAS DE CONDUTAS. 554.6.5. CONDUTAS DE AR E FUMO. 564.6.6. INSUFLADORES DE AR FRESCO E EXTRACTORES DE FUMO. 57

4.7. CONTROLO DE FUMO EM VIAS HORIZONTAIS DE EVACUAÇÃO .584.8. CONCLUSÕES.595. PRESSURIZAÇÃO .615.1. INTRODUÇÃO HISTÓRICA .615.2. PRINCÍPIOS DE CONTROLO DE FUMO .615.3. ABORDAGEM AO PROJECTO DE RG – SCIE .625.4. FLUXO DE AR E PRESSURIZAÇÃO .635.5. PRESSURIZAÇÃO DA CAIXA DE ESCADAS .685.6. CONCLUSÕES .696. CONCLUSÕES FINAIS .

Desenfumagem (Controlo de Fumo) em Edifícios de grande Extensão MESTRADO INTEGRADO EM ENGENHARIA CIVIL 2007/2008 DEPARTAMENTO DE ENGENHARIA CIVIL Tel. 351-22-508 1901 Fax 351-22-508 1446 miec@fe.up.pt Editado por FACULDADE DE ENGENHARIA DA UNIVERSIDADE DO PORTO Rua Dr. Roberto Frias