Bulletin 113 January 2021 - Reliable Sprinkler

Transcription

Bulletin 113 January 2021Model XL Quick-ResponseInstitutional SprinklerscULus ListedFeatures Quick response performanceInstitutional applications (correctional and health facility)Standard coverage model listed for light and ordinary hazardoccupanciesExtended Coverage models listed for 16’ x 16’ for light hazardoccupanciesProduct DescriptionThe Model XL Institutional is a quick-response sprinkler with afusible solder link thermal element specially designed for usein institutional applications. Standard coverage and extendedcoverage models are available.Model XL Institutional Pendent SprinklerThe flush style of this sprinkler conceals all operating partswith the exception of the heat sensing link. When the solder ofthe sensing link melts, the operating mechanism releases andallows the deflector to be extended for distributing water. Thesesprinklers are listed for a maximum service pressure of 175 psi(12.0 bar).The Model XL Institutional has been designed for use incorrectional and mental health facilities and in any other typeof institution where attempts by an occupant at self-injury mightinvolve the misuse of a fire sprinkler. The heat sensor is designedto release a suspended load that exceeds 50 lbs. when droppedfrom a 1-inch height. The conical escutcheon assembly is firmlyattached to the sprinkler body with tamper resistant fasteners.The horizontal sidewall model uses an escutcheon with anintegral deflector shelf.Model XL Institutional Horizontal SidewallSprinklerNote: Misuse of or tampering with Reliable Institutional Sprinklerswhich leads to property damage or personal injury, includingdeath, as a result of dismantling or modifying this product for useunrelated to the intended use shall not become the responsibilityof Reliable Automatic Sprinkler Co., Inc.Table AModel XL Institutional Pendent Sprinkler SummarySprinkler ModelXL InstitutionalStandard CoverageXL EC InstitutionalExtended CoverageOrientationListing orApprovalMax. Working Pressurepsi (bar)cULus175 (12.0)Pendent, FlushHorizontal Sidewall,FlushR1314R1334Pendent, FlushHorizontal Sidewall,FlushSprinkler IdentificationNumber (SIN)R1344cULus175 (12.0)R1364www.reliablesprinkler.com

Model XL Institutional Pendent SprinklerSIN R1314Technical SpecificationsStyle: PendentThreads: 1/2” NPT or ISO7-1 R1/2Nominal K-Factor: 5.6 (80)Max. Working Pressure: 175 psi (12.0 bar)Sprinkler Finishes(See Table D)Material SpecificationsBody: CDA AlloyDeflector: BrassYoke: DZR BrassLever Arms: CDA AlloyOperating Element: Nickel AlloySealing Washer: Nickel Alloy, PTFE CoatedCan: Plated SteelTemperature Rating165 F (74 C)SensitivityQuick ResponseSprinkler WrenchZX-Pendent WrenchListings and ApprovalscULus (Light & Ordinary Hazard)Model XL Institutional Pendent Sprinkler DimensionsBulletin 113January 2021Figure 1Page 2 of 6www.reliablesprinkler.com

Model XL Institutional Horizontal Sidewall SprinklerTechnical SpecificationsStyle: Horizontal SidewallThreads: 1/2” NPT or ISO7-1 R1/2Nominal K-Factor: 5.6 (80)Max. Working Pressure: 175 psi (12.0 bar)Material SpecificationsBody: CDA AlloyDeflector: BrassYoke: DZR BrassLever Arms: CDA AlloyOperating Element: Nickel AlloySealing Washer: Nickel Alloy, PTFE CoatedCan: Plated SteelSprinkler Finishes(See Table D)SensitivityQuick ResponseTemperature Rating165 F (74 C)Sprinkler WrenchZX-Horizontal WrenchListings and ApprovalscULus (Light & Ordinary Hazard)Model XL Institutional HSW Sprinkler DimensionsBulletin 113January 2021SIN R1334Figure 2Page 3 of 6www.reliablesprinkler.com

Model XL EC Institutional Pendent SprinklerSIN R1344Technical SpecificationsStyle: PendentThreads: 1/2” NPT or ISO7-1 R1/2Nominal K-Factor: 5.6 (80)Max. Working Pressure: 175 psi (12.0 bar)Sprinkler Finishes(See Table D)Material SpecificationsBody: CDA AlloyDeflector: BrassYoke: DZR BrassLever Arms: CDA AlloyOperating Element: Nickel AlloySealing Washer: Nickel Alloy, PTFE CoatedCan: Plated SteelTemperature Rating165 F (74 C)SensitivityQuick ResponseEscutcheonsConicalSprinkler WrenchZX-Pendent WrenchListings and ApprovalscULus (Light Hazard)Model XL EC Institutional Pendent Sprinkler DimensionsFigure 3Model XL EC Institutional Pendent Minimum Flow and Residual PressureTable BBulletin 113January 2021Max. Coverage Areaft x ft (m x m)Flowgpm (l/min)Pressurepsi (bar)16 x 16 (4.9 x 4.9)26 (98)21.6 (1.48)Page 4 of 6www.reliablesprinkler.com

Model XL EC Institutional Horizontal Sidewall SprinklerTechnical SpecificationsStyle: Horizontal SidewallThreads: 1/2” NPT or ISO7-1 R1/2Nominal K-Factor: 5.6 (80)Max. Working Pressure: 175 psi (12.0 bar)Material SpecificationsBody: CDA AlloyDeflector: BrassYoke: DZR BrassLever Arms: CDA AlloyOperating Element: Nickel AlloySealing Washer: Nickel Alloy, PTFE CoatedCan: Plated SteelSIN R1364Sprinkler Finishes(See Table D)SensitivityQuick ResponseTemperature Rating165 F (74 C)Sprinkler WrenchZX-Horizontal WrenchListings and ApprovalscULus (Light Hazard)Model XL EC Institutional HSW Sprinkler DimensionsFigure 4Model XL EC Institutional Horizontal Sidewall Minimum Flow and Residual PressureTable CDeflector Distancein. (mm)Max. Coverage Areaft x ft (m x m)Flowgpm (l/min)Pressurepsi (bar)4 - 6 (102 - 152)16 x 16 (4.9 x 4.9)26 (98)21.6 (1.48) 6 - 12 ( 152 - 305)16 x 16 (4.9 x 4.9)27 (102)23.2 (1.60)Bulletin 113January 2021Page 5 of 6www.reliablesprinkler.com

Table DFinishesSprinkler(1)Chrome BrightEscutcheonFigure 5Wrenches(2)SatinWhite PaintNotes:(1)Fusible link painted black(2)Other finishes and colors available on special order.Care must be exercised that orifice size, temperature rating,and sprinkler spacing are in accordance with this bulletin andthe latest published standards of the National Fire ProtectionAssociation, and approved by the Authority Having Jurisdiction.Apply a PTFE-based thread sealant or thread sealant tape to thesprinkler threads. Using the Model ZX-Pendent or ZX-SidewallWrench (see Figure 5), install the sprinkler into the fitting andverify the sprinkler is properly oriented.Recommended installation torque is 8-14 lb-ft (11-19 N.m). Donot tighten sprinklers over the maximum recommended torque.Exceeding the maximum recommend torque may cause leakageor impairment of the sprinklers.Shipping caps should be removed only after walls are finishedand when escutcheons are being installed. Each installedsprinkler must include an escutcheon, and only the escutcheonsshown in this bulletin shall be used with the Model XL Institutionalsprinkler. The use of any other escutcheon will void all approvalsand negate all warranties.It is recommended that a pick-proof caulk be applied around thecircumference of each escutcheon to close any gaps with thewall or ceiling.Provision must be made to prevent any axial movement of eachsprinkler away from the ceiling or wall. Reliable provides a retainerflange which is highly recommended for this purpose. Reliableaccepts no liability for property damage or personal injury whenthe retainer assembly is not used or is not installed correctly oninstitutional sprinklers.Use care to avoid damaging the sprinklers before, during andafter installation. Inspect all installed sprinklers to insure that theyhave not been damaged. Replace all sprinklers which have anysign of damage.Note: When replacing Model ZX HSW with Model XL HSW, anescutcheon extender P/N 6814000001 is required.Model ZX-Pendent WrenchModel ZX-Horizontal WrenchMaintenanceReliable Model XL series sprinklers should be inspected andthe sprinkler system maintained in accordance with NFPA25, as well as the requirements of any Authorities HavingJurisdiction.Prior to installation, sprinklers should remain in the original cartonsand packaging until used. This will minimize the potential fordamage to sprinklers that could cause improper operation or nonoperation.Do not clean sprinklers with soap and water, ammonia liquid or anyother cleaning fluids. Remove dust by gentle vacuuming withouttouching the sprinkler.Replace any sprinkler which has been painted (other than factoryapplied). A stock of spare sprinklers should be maintained toallow quick replacement of damaged or operated sprinklers.Failure to properly maintain sprinklers may result in inadvertentoperation or non-operation during a fire event.GuaranteeFor Reliable Automatic Sprinkler Co., Inc. guarantee, terms, andconditions, visit www.reliablesprinkler.com.Ordering InformationSpecify:Sprinkler XL Institutional [Pendent] [Horizontal Sidewall] XL EC Institutional [Pendent] [Horizontal Sidewall]Escutcheon Finish See Table DSprinkler Wrench ZX [Pendent] [Horizontal]Note: Each escutcheon ships complete with escutcheon retainerring, tamper proof screws, and retaining flange. Tamper ResistantScrew bit (PN 6880160020) included in box quantity sprinklerorder only, otherwise order separately.Bulletin 113January 2021Page 6 of 6www.reliablesprinkler.comP/N 9999970228Installation

Sealing Washer: Nickel Alloy, PTFE Coated Can: Plated Steel Sprinkler Finishes (See Table D) Sensitivity Quick Response Temperature Rating 165 F (74 C) Sprinkler Wrench ZX-Pendent Wrench Listings and Approvals cULus (Light & Ordinary Hazard) Model XL Institutional Pendent Sprinkler Dimensions Figure 1 Bulletin 113 January 2021 Page 2 of 6 www.reliablesprinkler.com. Model XL